Slots |
Occupied slots | 2 |
Supply |
Connection | backplane bus |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** |
Power dissipation | 2.15 W |
Power consumption | 3.3 W |
Internal bus |
Connection | backplane bus |
Interface | manufacturer-specific bus to standard com unit |
Analog input |
HART communication | yes |
HART secondary variable | no |
Analog output |
Number of channels | 4 |
Suitable field devices | |
| Field device | Proportional Valve |
| Field device [2] | I/P converters |
| Field device [3] | on-site display |
Connection | terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8- |
Current | 0 ... 25 mA short-circuit protected |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool |
| Short-circuit | factory setting: < 50 Ω configurable between 0 ... 26 mA |
| Open-circuit | deviation of preset output value > 0.5 mA |
Load | 750 Ω max. |
HART communication | yes |
HART secondary variable | yes |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication |
Transfer characteristics |
Deviation | |
| After calibration | 0.1 % of the signal range at 20 °C (68 °F) |
| Influence of ambient temperature | 0.1 %/10 K of the signal range |
Refresh time | 100 ms |
Indicators/settings |
LED indication | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) |
Coding | optional mechanical coding via front socket |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2006 |
Conformity |
Electromagnetic compatibility | NE 21:2007 |
Degree of protection | IEC 60529:2000 |
Environmental test | EN 60068-2-14:2009 |
Shock resistance | EN 60068-2-27:2009 |
Vibration resistance | EN 60068-2-6:2008 |
Damaging gas | EN 60068-2-42:2003 |
Relative humidity | EN 60068-2-78:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 95 % non-condensing |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) |
Mass | approx. 750 g |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) |
Data for application in connection with hazardous areas |
EU-Type Examination Certificate | BVS 12 ATEX E 015 X |
| Marking | II 2(1) G Ex d [ia Ga] IIC T4 Gb
II (1) D [Ex ia Da] IIIC |
Output | |
| Voltage | 27 V |
| Current | 87 mA |
| Power | 575 mW (linear characteristic) |
Galvanic isolation | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 |
International approvals |
ATEX approval | BVS 12 ATEX E 015 X |
INMETRO | Brazil: TÜV 14.1595X |
EAC approval | Russia: RU C-IT.MIII06.B.00129 |
Marine approval | |
| Lloyd Register | 15/20021 |
| American Bureau of Shipping | T1450280/UN |
| Bureau Veritas Marine | 22449/B0 BV |
General information |
System information | The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate. |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |