Ultrasonic sensor UC500-D1-3K-V7

UC500-D1-3K-V7
  • Specially for level monitoring in vessels
  • Large operating voltage range
    10 V DC ... 253 V DC
    20 V AC ... 253 V AC
  • 3 relay outputs
  • Parameter assignment via DIP-switches
  • Temperature compensation
  • Cable socket included with delivery

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  UC500-D1-3K-V7

Product Description
Single head system
General specifications
Sensing range60 ... 550 mm
Dead band0 ... 60 mm
Standard target plate100 mm x 100 mm
Transducer frequencyapprox. 380 kHz
Response delay> 10 s, relay
< 1 s, LEDs
Indicators/operating means
LED redLED 1: overfill indication
LED 4: underfill indication
LED green/yellowLED 2: overfill warning and normal operation
LED 3: normal operation and underfill warning
DIP switchsetting of the switch points/operating modes
Electrical specifications
Operating voltage10 ... 253 V DC
20 ... 253 V AC , 47 ... 63 Hz
No-load supply current< 30 mA with UB = 30 V DC
< 110 mA at UB = 10 V DC
< 25 mA at UB = 220 V AC
Output
Output type3 relay outputs, normally open/closed, selectable
Range hysteresis20 mm
Contact loading253 V AC/150V DC, 3 A (ohm. load)
Life spanelectrical: 105 switching cycles with ohmic load
(3 A/253 V AC or 3 A/30 V DC)
minimum contact load: 100 µA/100 mV DC
mechanical: 20 x 106 switching cycles
Temperature influence< 4 %
Fusing≤ 3 A Slow-blow fuse per output in accordance with IEC 60127-2 Sheet 5 required. Recommendation: after a short circuit, check that the device is functioning correctly.
Compliance with standards and directives
Standard conformity
StandardsEN IEC 60947-5-2:2020
IEC 60947-5-2:2019
Approvals and certificates
CCC approvalself-declaration
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Degree of protectionIP65
ConnectionFemale connector, V7 (7-pin), 90°
Wire cross section: ≤1.5 mm2
cable diameter ∅7 ... 9 mm
Material
Housingcover: PC
housing: PBT
threaded flange: stainless steel
installation connector/cable socket: PETP
Transducerepoxy resin/hollow glass sphere mixture; polyurethane foam
Mass700 g
Dimensions
Length107 mm
Diameter75 mm
NoteIn case of loss or damage, the cable socket must be replaced by an identical cable socket (type V7-W) from Pepperl+Fuchs!

Classifications

SystemClasscode
ECLASS 13.027272803
ECLASS 12.027272803
ECLASS 11.027272803
ECLASS 10.0.127272803
ECLASS 9.027272803
ECLASS 8.027272803
ECLASS 5.127272803
ETIM 9.0EC001849
ETIM 8.0EC001849
ETIM 7.0EC001849
ETIM 6.0EC001849
ETIM 5.0EC001849
UNSPSC 12.141111960

Details: UC500-D1-3K-V7

Product Documentation: UC500-D1-3K-V7

Language Selection:
Brief InstructionsLanguageFile TypeFile Size
Instruction leaflet / BeipackzettelALLPDF332 KB

Design / Simulation: UC500-D1-3K-V7

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP221 KB
CAD Portal / CAD PortalALLLINK---

Approvals: UC500-D1-3K-V7

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
China CCC SDOC2020970305000212ALLPDF684 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-4248AALLPDF46 KB
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F)DOC-5522ALLPDF39 KB