Power supply FB9206D

FB9206D
  • Power supply for 24 V DC
  • Suitable for the supply of 24 I/O modules and 1 bus coupler
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)
  • Use two power supplies for redundancy

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of FB9206D

Slots
Bus coupler2
I/O modules>12, depending on the type
Supply
Connectionwired to Ex e terminals via backplane
Maximum safe voltage Um60 V DC (SELV/PELV)
Input voltage range18 ... 32 V DC (SELV/PELV)
Power dissipationapprox. 15 % of power consumption
Power consumptionmax. 45 W
parallel connection with other FB9206D (autom. power sharing)
Inrush current1.5 A (10 ms)
Output
Voltage5.4 V DC +/- 5% ,
12 V DC + 4/- 2%
PowerP5V ≤ 5.4 W, P12V ≤ 39 W - P5V
Indicators/settings
LED indicatorLED green: OFF in case of loss of 24V or 12V or 5V
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Massapprox. 820 g
Dimensions57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
Data for application in connection with hazardous areas
EU-Type Examination CertificatePTB 97 ATEX 1074 U
MarkingEx-Hexagon II 2 G Ex d IIC Gb
Galvanic isolation
Output/power supplyEN 60950-1 (safety requirement < 60 V, external power supply SELV/PELV)
Directive conformity
Directive 2014/34/EUEN 60079-0:2009
EN 60079-1:2007
EN 60079-11:2007
EN 60079-26:2007
EN 61241-11:2006
International approvals
ATEX approvalPTB 97 ATEX 1075

EAC approvalRussia: RU C-IT.MIII06.B.00129
Marine approval
Lloyd Register15/20021
DNV GL MarineTAA0000034
American Bureau of ShippingT1450280/UN
Bureau Veritas Marine22449/B0 BV

Documents: FB9206D

ManualsLanguageFile TypeFile Size
Manual - FB-Remote-I/O-SystemENGPDF5670 KB
Handbuch - FB-Remote-I/O-SystemGERPDF1453 KB
Instructions, short instructions, safety information
ИнструкцииBULPDF135 KB
Návod k poużitíCZEPDF128 KB
Instruktions manualDANPDF128 KB
Instruction manualENGPDF51 KB
KasutusjuhendESTPDF0 KB
KäyttöohjeFINPDF124 KB
BetriebsanleitungGERPDF53 KB
Οδηγίες χρήσηςGREPDF137 KB
HandleidingHOLPDF0 KB
Instruction manual / BetriebsanleitungHRVPDF128 KB
Használati útmutatóHUNPDF129 KB
Lietošanas pamācībaLAVPDF0 KB
Instrukciju vadovasLITPDF130 KB
Instrukcja obsługiPOLPDF0 KB
Manual de instruçõesPORPDF129 KB
Manual de utilizareRONPDF128 KB
Návod na poużitieSLKPDF129 KB
Navodila za uporaboSLVPDF126 KB
ManualSWEPDF125 KB

CAD+CAE: FB9206D

EPLANFile TypeFile Size
EPLAN Data Portal / EPLAN Data PortalLINK---

Approvals+Certificates: FB9206D

CertificatesCertificate No.File TypeFile Size
American Bureau of Shipping (ABS) Marine15-HG1450280-PDAPDF1468 KB
Bureau Veritas (Maritime) Marine22449/B0 BVPDF287 KB
DNV GL MarineTAA0000034PDF334 KB
Europe PTB ATEX Category 2 GPTB 97 ATEX 1074UPDF2619 KB
Lloyd's Register Marine15/20021PDF2013 KB