Power supply FB9215B2

FB9215B2
  • Multi range power supply 90 ... 253 V AC
  • Suitable for the supply of 24 I/O modules and 1 bus coupler
  • Use two power supplies for redundancy
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of FB9215B2

Slots
Bus coupler2
I/O modules>12, depending on the type
Supply
Connectionwired to Ex e terminals via backplane
Maximum safe voltage Um253 V AC
Input voltage range90 ... 253 V AC
Power dissipationapprox. 18 % of power consumption
Power consumptionmax. 47 W
parallel connection with other FB9215B2 (autom. power sharing)
Inrush current (< 2 ms)30 A max. (115 V AC)
50 A max. (230 V AC)
Input
Input frequency50 ... 60 Hz
Output
Voltage5.4 V DC +/- 5% ,
12 V DC +/- 3%
PowerP5V ≤ 5.4 W, P12V ≤ 39 W - P5V
Indicators/settings
LED indicatorLED green: OFF in case of loss of main power or internal voltages (12 V, 5.4 V)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Conformity
Electromagnetic compatibilityNE 21:2007
Degree of protectionIEC 60529:2000
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Massapprox. 890 g
Dimensions57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
Data for application in connection with hazardous areas
EU-Type Examination CertificatePTB 97 ATEX 1074 U
MarkingEx-Hexagon II 2 G Ex d IIC Gb
Galvanic isolation
Output/power supplyEN 60950-1 (safety requirement < 60 V, external power supply SELV/PELV)
Directive conformity
Directive 2014/34/EUEN 60079-0:2009
EN 60079-1:2007
EN 60079-11:2007
EN 60079-26:2007
EN 61241-11:2006
International approvals
EAC approvalRussia: RU C-IT.MIII06.B.00129
Marine approval
Lloyd Register15/20021
American Bureau of ShippingT1450280/UN
Bureau Veritas Marine22449/B0 BV

Documents: FB9215B2

ManualsLanguageFile TypeFile Size
Manual - FB-Remote-I/O-SystemENGPDF5670 KB
Handbuch - FB-Remote-I/O-SystemGERPDF1453 KB
Instructions, short instructions, safety information
ИнструкцииBULPDF135 KB
Návod k poużitíCZEPDF128 KB
Instruktions manualDANPDF128 KB
Instruction manualENGPDF51 KB
KasutusjuhendESTPDF126 KB
KäyttöohjeFINPDF124 KB
BetriebsanleitungGERPDF53 KB
Οδηγίες χρήσηςGREPDF0 KB
HandleidingHOLPDF0 KB
Instruction manual / BetriebsanleitungHRVPDF128 KB
Használati útmutatóHUNPDF0 KB
Lietošanas pamācībaLAVPDF0 KB
Instrukciju vadovasLITPDF130 KB
Instrukcja obsługiPOLPDF0 KB
Manual de instruçõesPORPDF129 KB
Manual de utilizareRONPDF128 KB
Návod na poużitieSLKPDF129 KB
Navodila za uporaboSLVPDF0 KB
ManualSWEPDF125 KB

CAD+CAE: FB9215B2

EPLANFile TypeFile Size
EPLAN Data Portal / EPLAN Data PortalLINK---

Approvals+Certificates: FB9215B2

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-1802APDF232 KB
Certificates
Bureau Veritas (Maritime) Marine22449/B0 BVPDF287 KB
Europe PTB ATEX Category 2 GPTB 97 ATEX 1074UPDF2619 KB
Lloyd's Register Marine15/20021PDF2013 KB