AS-Interface power supply VAN-115/230AC-K27

VAN-115/230AC-K27
  • Up to 4 A output load
  • LED operating display
  • 100 V AC up to 240 V AC
  • AS-Interface filter integrated
  • Earth fault detection

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  VAN-115/230AC-K27

Product Description
AS-Interface power supply, data decoupling, 4 A
General specifications
UL File NumberE223176
MTBF100 a
Indicators/operating means
Reset push-button switchearth fault simulation/reset of earth fault display
LED EFDearth fault display; LED red
LED AS-i okLED green:
ON: AS-Interface voltage OK
OFF: overload or no supply voltage
Electrical specifications
FusingT3A 15/250 V HBC (not accessible)
Rated operating voltage85 … 132 VAC
184 … 264 VAC
240 … 300 VDC
Rated operating current2.7 A at 115 VAC
1.3 A at 230 VAC
Supply frequency47 ... 63 Hz (alternatively, DC possible)
Efficiencytyp. 90 % (230 VAC, 4 A)
Galvanic isolationSELV/PELV
Peak inrush current< 3.7 A2s (120 VAC)
< 4.6 A2s (132 VAC)
< 2.5 A2s (230 VAC)
< 3.3 A2s (264 VAC)
Output
Short-circuit protection/overload> 4,2 A
< 6.5 A
Current limitstarts at > 4.2 A
Voltage30.5 VDC ±3 % fixed
Current4 A
Residual ripple< 50 mVSS (500 kHz bandwidth, 50 Ω measurement, with resistive load)
Overvoltage protectedlimited to max. 55 V
Compliance with standards and directives
Directive conformity
EMC Directive 2004/108/ECEN 55022:2006, EN 55011:2009 Class B
EN 61000-6-3:2001 , EN 61204-3:2001
Standard conformity
Noise immunityEN 61000-6-2:2005
Emitted interferenceEN 61000-6-3:2007
EN 61000-3-2:2010
EN 61000-3-3:2009
Galvanic isolationIEC 60364-4-41:2005 (PELV)
IEC 60950:1999 (SELV)
Degree of protectionIEC 60529:2001
Pollution degreeEN 50178:1997
Mech. capacityEN 60068-2-6:2008 (Sinus)
EN 60068-2-64:2009 (Random)
Shock and impact resistanceEN 60068-2-27:1995
Ambient conditions
Ambient temperature-10 ... 70 °C (14 ... 158 °F)
Note derating
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Shock and impact resistance15g/6 ms
10g/11 ms
Vibration resistanceSine 2 - 17.8 Hz: ± 1.6 mm
Sine 17.8 ... 500 Hz : 2 g
Random 2 … 500 Hz: 0.5 m2 (s³)
Pollution degree2
Mechanical specifications
Degree of protectionIP20
Protection class1 (IEC 60536); Protective conductor connection necessary
ConnectionConnection terminals, max. conductor cross-section
Flexible cable: 0.5 … 4 mm2
Rigid cable: 0.5 … 6 mm2
Stripping length 7 mm
Mass650 g
MountingDIN mounting rail

Documents: VAN-115/230AC-K27

Instruction leafletsLanguageFile TypeFile Size
Instruction leaflet / Beipackzettel ALLPDF350 KB

CAD+CAE: VAN-115/230AC-K27

CADFile TypeFile Size
3-D model in IGS format / 3-D-Modell im IGS-FormatIGS6806 KB
3-D model in STP format / 3-D-Modell im STP-FormatSTP2062 KB
CAD Portal / CAD PortalLINK---

Approvals+Certificates: VAN-115/230AC-K27

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-1013CPDF162 KB
Certificates
US CA ULE223176LINK---
Worldwide AS-International Association AS-Interface95001PDF389 KB

Associated Products: VAN-115/230AC-K27

Accessories
AS-Interface Power supply and network checking utilityfa

Function: VAN-115/230AC-K27

The primary switched-mode power supply was designed for fieldbus applications that transfer energy and data together via a two-wire cable
(AS-Interface concept). It supplies a fully extended AS-Interface system with a maximum output current of 4.0 A. Due to the sinusoidal current consumption of the network, harmonics are avoided.

The power supply assumes the function of supplying power, data decoupling for the power source and balancing both output lines
(AS-Interface + and AS-Interface -) with respect to the machine ground (shielded connection). The transformer allows the use of unshielded load cables. The power supply is protected by an internal fuse that eliminates the need for additional device protection measures.

Ground fault monitor GF:

The switch output of the ground fault monitor evaluates any short circuits detected in the AS-Interface system. With the potential-free transistor output, the system can be shut down using the control program. The output is normally closed, but opens when a ground fault is detected. The "GF" LED also signals the presence of a ground fault. This output will close when the power supply is restarted or the reset button is pressed for (> 2 seconds). It is essential to connect the shield to PE or the machine ground to guarantee proper operation.

Checking the ground fault monitor:

Pressing the reset button briefly (< 2 seconds) simulates a ground fault in the device. Detection, evaluation and signaling of a ground fault and the switch output can be tested at suitable intervals. A ground fault generated in this way can be reset by pressing the reset button for (> 2 seconds).