Serviceline Industrial Sensors
Serviceline Explosion Protection

I/O hub IO-Link ICA-16IO-G20-IO-P16

ICA-16IO-G20-IO-P16
  • 16 digital inputs/outputs can be configured
  • Configuration and control via IO-Link
  • IO-Link Class A
  • LED for switching state and fault indication
  • Supply from IO-Link
  • IO-Link 1.1.3

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  ICA-16IO-G20-IO-P16

Product Description
G20 IO-Link module for 16 freely configurable digital inputs/outputs
General specifications
MTBF149 a
Indicators/operating means
LED green<--, -->: IO1..8 / IO9..16 bank indication
LED yellow/redIO1 ... IO16: inputs/outputs status, IO-Link status
Electrical specifications
Operating voltage18 ... 30 V DC, PELV
Current limitation of the supply max. 4 A
No-load supply current≤ 25 mA
Operating currentmax. 4 A
Interface
Interface typeIO-Link
IO-Link revision1.1
Device profileIdentification and Diagnosis - I&D
Process dataInputs 3 Byte
- Input signals 16 Bit
- diagnosis signals 5 Bit
Outputs 2 Byte
- Output signals 16 Bit
Vendor ID1 (0x0001)
Device ID985345 (0x0F0901)
Data transfer rateCOM3 (230.4 kbits/s)
Min. cycle time1 ms
SIO mode supportno
Compatible master port typeClass A
Input
Number/Type16 Inputs for 3-wire sensors (PNP), DC (IO1 ... IO16)
Supplyfrom IO-Link
Current loading capacity200 mA , overload and short-circuit protected
Input current≤ 5 mA (limited internally)
Switching pointType 3 according to IEC 61131-2
Output
Number/Type16 electronic outputs, PNP (IO1 … IO16), overload-proof and short-circuit-proof
Supplyfrom IO-Link
Voltage≥ (UB - 1.5 V)
Current200 mA per output
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
EN 55011:2016
Conformity
Communication interfaceIEC 61131-9:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 61131-9:2013
InputEN 61131-2:2007
Communication interfaceIEC 61131-9 / IO-Link V1.1.3
Emitted interferenceEN 61000-6-4:2007
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006
Ambient conditions
Ambient temperature-30 ... 70 °C (-22 ... 158 °F)
Storage temperature-30 ... 70 °C (-22 ... 158 °F)
Relative humidity85 % non-condensing
Climatic conditionsFor indoor use only
Altitude≤ 5000 m above MSL
Shock and impact resistance30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm / 5 g 5 ... 500 Hz
Pollution degree2
Mechanical specifications
Degree of protectionIP54 according to EN 60529
ConnectionIO-Link: M12 round plug connector in accordance with EN 61076-2-101, LM type (4-pin, connector contacts, screw-locking, A-coded)
Female connector: LF type or similar
IO: M8 round plug connector in accordance with EN 61076-2-104, LF type (4-pin, bushing contacts, screw-locking, A-coded)
Mating connector: LM type or similar
Mass310 g
Dimensions
Height27.5 mm
Width131.5 mm
Length54 mm
Mounting2 clips with ∅ 8 mm drill hole
The module must be secured to a solid, continuous surface using the two lugs
Cable length1 m (IO-Link)
0.2 m (IO1/2, IO15/16), 0.3 m (IO3/4, IO13/14)
0.4 m (IO5/6, IO11/12); 0.5 m (IO7/8, IO9/10)
max. 10 m

Classifications

SystemClasscode
ECLASS 13.027242602
ECLASS 12.027242602
ECLASS 11.027242602
ECLASS 10.0.127242602
ECLASS 9.027242602
ECLASS 8.027242602
ECLASS 5.127242602
ETIM 9.0EC001597
ETIM 8.0EC001597
ETIM 7.0EC001597
ETIM 6.0EC001597
ETIM 5.0EC001597
UNSPSC 12.132151705

Details: ICA-16IO-G20-IO-P16

Function

The ICA-16IO-G20-IO-P16 is an IO-Link field module with 16 freely configurable digital inputs/outputs. The compact housing can be mounted directly in support profiles or cable ducts.

The module and the inputs and outputs are supplied with voltage via IO-Link.

The inputs and outputs are connected via cable outlets with 4-pin M8 sockets. IO-Link is connected via a cable outlet with 4-pin M12 connector.

The current switching state or an overload of the inputs or outputs is indicated via the IN or OUT LEDs.

Product Documentation: ICA-16IO-G20-IO-P16

Language Selection:
ManualsLanguageFile TypeFile Size
ManualENGPDF635 KB

Approvals: ICA-16IO-G20-IO-P16

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
IO-Link Manufacturer DeclarationCERT-7194ALLPDF173 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-7463_ENGENGPDF196 KB
UK Declaration of Conformity (P+F)TDOC-7464_ENGENGPDF171 KB

Software: ICA-16IO-G20-IO-P16

Language Selection:
Device Description Files/DriversRelease InfoFile TypeFile Size
IODD / IODDV1.01.001 / 2023-11-21ZIP228 KB
Software Tools
IO-Link Offline Parameterization Tool / IO-Link Offline-ParametriertoolV1.00.006 / 2022-07-10ZIP96138 KB

Associated Products: ICA-16IO-G20-IO-P16

Accessories
Mounting aidfa
Free Download: White Paper on TCP-Based Communication Protocols (PDF)

This free PDF white paper compares the different TCP-based communication protocols (AMQP, OPC UA, MQTT, REST API) that have found their way up and are considered the enablers of IIoT and Industry 4.0. Get your free download now!

AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability

The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.

AS-Interface Product Range

Get to know our full range of AS-Interface products.