Serviceline Industrial Sensors
Serviceline Explosion Protection

I/O hub ICA-16DIO-G16-IO

ICA-16DIO-G16-IO
  • IO-Link Class A
  • IO-Link 1.1.4
  • LED for switching state and fault indication
  • Configuration and control via IO-Link
  • Supply from IO-Link
  • 16 digital inputs/outputs can be configured

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  ICA-16DIO-G16-IO

Product Description
I/O hub with IO-Link interface for 16 freely configurable digital inputs/outputs
General specifications
MTBF134 a
Indicators/operating means
LED PWRLED green: flashing with short break (1 Hz) - IO-Link mode
LED IOSwitch state (IO); multicolor LED
yellow: only IO pin 4 is active
blue: only IO pin 2 is active
green: both IO pin 4 and pin 2 are active
red: overload at sensor supply or output
Electrical specifications
Operating voltage18 ... 30 V DC, PELV
Current limitation of the supply max. 4 A
No-load supply current≤ 25 mA
Operating currentmax. 4 A
Interface
Interface typeIO-Link
IO-Link revision1.1
Device profileIdentification and Diagnosis - I&D
Firmware update
Process dataInputs 3 Byte
- Input signals 16 Bit
- diagnosis signals 5 Bit
Outputs 2 Byte
- Output signals 16 Bit
Vendor ID1 (0x0001)
Device ID985858 (0x0F0B02)
Data transfer rateCOM3 (230.4 kbits/s)
Min. cycle time1 ms
SIO mode supportno
Compatible master port typeClass A
Input
Number/Type16 Inputs for 3-wire sensors (PNP), DC (IO1 ... IO16)
Supplyfrom IO-Link
Current loading capacity180 mA , overload and short-circuit protected
Input current≤ 5 mA (limited internally)
Switching pointType 3 according to IEC 61131-2
Output
Number/Type16 electronic outputs, PNP (IO1 … IO16), overload-proof and short-circuit-proof
Supplyfrom IO-Link
Voltage≥ (UB - 1.5 V)
Current180 mA per output
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
EN 55011:2016
Standard conformity
Degree of protectionEN 60529:2000
InputEN 61131-2:2007
Communication interfaceIEC 61131-9 / IO-Link V1.1.4
Emitted interferenceEN 61000-6-4:2007
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006
Approvals and certificates
UL approval
Load specification DC General Use / DC Pilot Duty
Degree of protection not tested by UL; tested by Pepperl+Fuchs SE
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % non-condensing
Climatic conditionsFor indoor use only
Altitude≤ 5000 m above MSL
Shock and impact resistance30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm / 5 g 5 ... 500 Hz
Pollution degree3
Mechanical specifications
Degree of protectionIP67 / IP68 / IP69k
ConnectionIO-Link: M12 round plug connector in accordance with EN 61076-2-101, LM type (4-pin, connector contacts, screw-locking, A-coded)
Female connector: LF type or similar
IO: M8 round plug connector in accordance with EN 61076-2-104, LF type (4-pin, bushing contacts, screw-locking, A-coded)
Mating connector: LM type or similar
Material
HousingPBT
Mass110 g
Tightening torque, cable gland0.4 Nm (M12 connector),
0.2 Nm (M8 connector)
Dimensions
Height29.35 mm
Width30 mm
Length143 mm
Diameter
Mountingscrew mounting

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001597
ETIM 8.0EC001597
ETIM 7.0EC001597
ETIM 6.0EC001597
ETIM 5.0EC001597
UNSPSC 12.132151705

Details: ICA-16DIO-G16-IO

Function

The ICA-16DIO-G16-IO is an IO-Link field module with 16 freely configurable digital inputs/outputs.

The module and the inputs and outputs are supplied with power via IO-Link.

The inputs and outputs are connected via 4-pin M8 sockets. IO-Link is connected via a 4-pin M12 connector.

The current switching state or an overload of the inputs or outputs is indicated via LEDs.

Product Documentation: ICA-16DIO-G16-IO

Language Selection:
Parameter InformationLanguageFile TypeFile Size
IO-Link Parameter Datasheet ICA-16DIO-G16-IOENGPDF387 KB

Approvals: ICA-16DIO-G16-IO

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
IO-Link Manufacturer DeclarationCERT-7612ALLPDF176 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-7805_ENGENGPDF196 KB
UK Declaration of Conformity (P+F)TDOC-7806_ENGENGPDF171 KB

Software: ICA-16DIO-G16-IO

Language Selection:
Device Description Files/DriversRelease InfoFile TypeFile Size
IODD for ICA-16DIO-G16-IO / IODD für ICA-16DIO-G16-IOV1.00.000 / 2024-10-25ZIP218 KB
Software Tools
IO-Link Offline Parameterization Tool / IO-Link Offline-ParametriertoolV1.00.006 / 2022-07-10ZIP96138 KB
Free Download: White Paper on TCP-Based Communication Protocols (PDF)

This free PDF white paper compares the different TCP-based communication protocols (AMQP, OPC UA, MQTT, REST API) that have found their way up and are considered the enablers of IIoT and Industry 4.0. Get your free download now!

AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability

The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.

AS-Interface Product Range

Get to know our full range of AS-Interface products.