Serviceline Industrial Sensors
Serviceline Explosion Protection

I/O hub ICA-16DIO-G11-IO

ICA-16DIO-G11-IO
  • IO-Link interface for service and process data
  • 16 digital inputs/outputs can be configured
  • Logic level can be configured per port
  • Filter time can be configured per port
  • Pulse extension can be configured per port

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  ICA-16DIO-G11-IO

Product Description
I/O hub with IO-Link interface for 16 freely configurable digital inputs/outputs
General specifications
MTBF144 a
Indicators/operating means
LED PWRLED green: flashing with short break (1 Hz) - IO-Link mode
LED PSwitch state (IO); multicolor LED
yellow: only IO pin 4 is active
blue: only IO pin 2 is active
green: both IO pin 4 and pin 2 are active
red: overload at sensor supply or output
Electrical specifications
Operating voltage18 ... 30 V DC, PELV
Current limitation of the supply max. 4 A
No-load supply current≤ 25 mA
Operating currentmax. 4 A
Interface
Interface typeIO-Link
IO-Link revision1.1
Device profileIdentification and Diagnosis - I&D
Firmware update
Process dataInputs 3 Byte
- Input signals 16 Bit
- diagnosis signals 5 Bit
Outputs 2 Byte
- Output signals 16 Bit
Vendor ID1 (0x0001)
Device ID985602 (0x0F0A02)
Data transfer rateCOM3 (230.4 kbits/s)
Min. cycle time1 ms
SIO mode supportno
Compatible master port typeClass A
Input
Number/Type16 Inputs for 3-wire sensors (PNP), DC (P1 ... P8)
Supplyfrom IO-Link
Current loading capacity180 mA , overload and short-circuit protected
Input current≤ 5 mA (limited internally)
Switching pointType 3 according to IEC 61131-2
Output
Number/Type16 electronic outputs, PNP (P1 … P86), overload-proof and short-circuit-proof
Supplyfrom IO-Link
Voltage≥ (UB - 1.5 V)
Current180 mA per output
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
EN 55011:2016
Standard conformity
Degree of protectionEN 60529:2000
InputEN 61131-2:2007
Communication interfaceIEC 61131-9 / IO-Link V1.1.4
Emitted interferenceEN 61000-6-4:2007
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006
Approvals and certificates
UL approval
Load specification DC General Use / DC Pilot Duty
Degree of protection not tested by UL; tested by Pepperl+Fuchs SE
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % non-condensing
Climatic conditionsFor indoor use only
Altitude≤ 5000 m above MSL
Shock and impact resistance30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm / 5 g 5 ... 500 Hz
Pollution degree3
Mechanical specifications
Degree of protectionIP68 / IP69K
ConnectionIO-Link: M12 round plug connector in accordance with EN 61076-2-101, LM type (4-pin, connector contacts, screw-locking, A-coded)
Female connector: LF type or similar
P: M12 round plug connector in accordance with EN 61076-2-101, LF type (4-pin, socket contacts, screw-locking, A-coded)
Mating connector: LM type or similar
Material
HousingPBT PC
Mounting screwStainless steel 1.4305 / AISI 303
Mass200 g
Tightening torque, housing screws1.8 Nm
Tightening torque, cable gland0.4 Nm
Dimensions
Height46 mm
Diameter85 mm
Connectionheight 11 mm
Construction typeField housing
MountingMounting plate

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001597
ETIM 8.0EC001597
ETIM 7.0EC001597
ETIM 6.0EC001597
ETIM 5.0EC001597
UNSPSC 12.132151705

Details: ICA-16DIO-G11-IO

Function

The ICA-16DIO-G11-IO is an IO-Link field module with 16 freely configurable digital inputs/outputs.

The module and the inputs and outputs are supplied with power via IO-Link.

The inputs and outputs are connected via 4-pin M12 sockets. IO-Link is connected via a 4-pin M12 connector.

The current switching state or an overload of the inputs or outputs is indicated via LEDs.

Product Documentation: ICA-16DIO-G11-IO

Language Selection:
Parameter InformationLanguageFile TypeFile Size
IO-Link Parameter Datasheet ICA-16DIO-G11-IOENGPDF391 KB

Design / Simulation: ICA-16DIO-G11-IO

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP4807 KB

Approvals: ICA-16DIO-G11-IO

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
IO-Link Manufacturer DeclarationCERT-7612ALLPDF176 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-7790_ENGENGPDF196 KB
UK Declaration of Conformity (P+F)TDOC-7791_ENGENGPDF171 KB

Software: ICA-16DIO-G11-IO

Language Selection:
Device Description Files/DriversRelease InfoFile TypeFile Size
IODD for ICA-16DIO-G11-IO / IODD für ICA-16DIO-G11-IOV1.00.000 / 2024-10-25ZIP350 KB
Software Tools
IO-Link Offline Parameterization Tool / IO-Link Offline-ParametriertoolV1.00.006 / 2022-07-10ZIP96138 KB

Associated Products: ICA-16DIO-G11-IO

Accessories
torque screwdriver (0.6 Nm)fa
plug-in cap M12fa
IO-Link master, supply via USB port or separate power supply, LED indicators, M12 plug for sensor connectionfa
Free Download: White Paper on TCP-Based Communication Protocols (PDF)

This free PDF white paper compares the different TCP-based communication protocols (AMQP, OPC UA, MQTT, REST API) that have found their way up and are considered the enablers of IIoT and Industry 4.0. Get your free download now!

AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability

The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.

AS-Interface Product Range

Get to know our full range of AS-Interface products.