Serviceline Industrial Sensors
Serviceline Explosion Protection
Not available for purchase
Not available for purchase

AS-Interface actuator module VAA-4A-G5-V2-Ex

VAA-4A-G5-V2-Ex
  • Use in hazardous area
  • Category, ignition protection category
    [exsign] II (1GD) 2G EEx em [ia] IIB/IIC T4
  • Outputs EEx ia IIC
  • Connection of 4 switch valves
  • Function display for bus and outputs

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  VAA-4A-G5-V2-Ex

Product Description
G5 Ex module
4 valve outputs
General specifications
Node typeStandard node
EC-Type Examination CertificateDMT 99 ATEX E 072
Group, category, type of protectionEx-Hexagon II (1GD)2G EEx em [ia] IIB/IIC T4
Intrinsically safe input and output circuits can be laid in the 1G and 1D category areas.
Indicators/operating means
LED PWR/CHKdual-LED green/red
green: AS-Interface voltage, normal operation
red: communication error or address 0
LED OUTSwitching state (output); 4 LED yellow
Electrical specifications
Rated operating voltage26.5 ... 31.6 V PELV from AS-Interface
Rated operating current≤ 250 mA
Maximum safe voltage40 V
Output
Number/Type4 outputs EEx ia IIC for controlling intrinsically safe valves
Values in accordance with EC-Type Examination Certificate
Voltage≤ 28 V DC
Current≤ 110 mA
Power≤ 770 mW
Internal resistor≥ 258 Ω
Type of protection EEx ia IIB EEx ia IIC
External capacitance ≤ 650 nF ≤ 83 nF
External inductance ≤ 10 mH ≤ 1 mH
Nominal values(typically)
Open loop voltage26 V
Short-circuit current50 mA
Internal resistor270 Ω
Curve angle points (nominal values)12.5 V DC, 50 mA
Programming instructions
ProfileS-8.F
IO code8
ID codeF
Data bits (function via AS-Interface) input output
D0 - OUT1
D1 - OUT2
D2 - OUT3
D3 - OUT4
Parameter bits (programmable via AS-i)function
P0/P1(Output conditions on failure of the AS-Interface communication) 0/0 Outputs old value
0/1 outputs not controlled
1/0 outputs controlled
1/1 outputs not controlled
P2not used
P3not used
Ambient conditions
Ambient temperature-20 ... 65 °C (-4 ... 149 °F)
Storage temperature-20 ... 85 °C (-4 ... 185 °F)
Mechanical specifications
Degree of protectionIP54 according to EN 60529
Connectionscrew terminals
Mass1.5 kg
Mountingscrew mounting

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Details: VAA-4A-G5-V2-Ex

Free Download: White Paper on TCP-Based Communication Protocols (PDF)

This free PDF white paper compares the different TCP-based communication protocols (AMQP, OPC UA, MQTT, REST API) that have found their way up and are considered the enablers of IIoT and Industry 4.0. Get your free download now!

AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability

The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.

AS-Interface Product Range

Get to know our full range of AS-Interface products.