AS-Interface sensor/actuator module VBA-4E3A-KE-ZEJQ/E2L

VBA-4E3A-KE-ZEJQ/E2L
  • Housing with removable and color coded terminals
  • Communication monitoring
  • Inputs for 2- and 3-wire sensors
  • Addressing jack
  • Power supply of outputs from the external auxiliary voltage
  • Selectable supply to the sensors: External or from the module
  • Function display for bus, external auxiliary voltage, internal sensor supply, inputs, and outputs
  • Red LED per channel, lights up in the event of output overload
  • Switchable lead breakage detection (outputs)
  • A/B slave with extended addressing possibility for up to 62 slaves

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  VBA-4E3A-KE-ZEJQ/E2L

Product Description
KE switch cabinet module
4 inputs and 3 outputs
General specifications
Slave typeA/B slave
AS-Interface specificationV3.0
Required master specification≥ V2.1
UL File NumberE223772
Indicators/operating means
LED FAULTError display; red LED
red: communication error, i.e. address is 0
red flashing: overload internal input supply, i.e. overload or lead interruption outputs
LED INTInternal input supply active; LED green
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INswitching state (input); 4 LED yellow
LED OUTSwitching state (output); 3 LED yellow/red
yellow: Output active
red: Output overload or lead breakage
Electrical specifications
Auxiliary voltage (input)12 ... 30 V DC PELV
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 35 mA (without sensors) / max. 190 mA
Protection classIII
Surge protectionUEXT, UAUX, Ue: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
Supplyfrom AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Voltage21 ... 31 V DC (INT)
Current loading capacity≤ 150 mA, overload- and short-circuit protected (INT)
Input current≤ 9 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)≤ 3 mA
1 (attenuated)≥ 5 mA
Signal delay< 1 ms (input/AS-Interface)
Output
Number/Type3 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
CurrentO1 max. 3 A, O2/O3 max. 1.5 A, total 6 A (TB ≤ 40 °C)
O1 max. 2 A, O2/O3 max. 1 A, total 4 A (TB ≤ 60 °C)
Voltage≥ (UAUX - 0.5 V)
Usage categoryDC-13
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
InputEN 61131-2:2004
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Programming instructions
ProfileS-7.A.0
IO code7
ID codeA
ID1 code7
ID2 code0
Data bits (function via AS-Interface) input output
D0 IN1 O1
D1 IN2 O2
D2 IN3 O3
D3 IN4 -
Parameter bits (programmable via AS-i)function
P0Communication monitoring
P0 = 0 monitoring = off, the outputs maintain the status if communication fails
P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
P1Input filter
P1 = 0 input filter on, pulse suppression ≤ 2 ms
P1 = 1 input filter off (default settings)
P2Lead breakage outputs
P2 = 0 lead breakage on
P2 = 1 lead breakage off (default settings)
P3not used
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Pollution degree2
Mechanical specifications
Degree of protectionIP20
Connectionremovable terminals
rated connection capacity:
rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2
for multiple-wire connection with two wires of equal cross-section:
flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material
HousingPA 66-FR
Mass150 g
MountingDIN mounting rail
Tightening torque of clamping screws0.5 Nm ... 0.6 Nm

Documents: VBA-4E3A-KE-ZEJQ/E2L

Instruction leafletsLanguageFile TypeFile Size
Instruction leaflet / Beipackzettel ALLPDF1392 KB

CAD+CAE: VBA-4E3A-KE-ZEJQ/E2L

CADFile TypeFile Size
3-D model in IGS format / 3-D-Modell im IGS-FormatIGS138 KB
3-D model in STP format / 3-D-Modell im STP-FormatSTP112 KB
CAD Portal / CAD PortalLINK---

Approvals+Certificates: VBA-4E3A-KE-ZEJQ/E2L

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-1009BPDF162 KB
Certificates
Canada UL cULE106378 cUL (QUZW7)LINK---
USA ULE106378 UL (QUZW)LINK---
Worldwide AS-International Association AS-InterfaceZU 86704PDF363 KB

Associated Products: VBA-4E3A-KE-ZEJQ/E2L

Accessories

AS-Interface Handheld with accessoryfa

Adapter cable module/hand-held programming devicefa

AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability

The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.

AS-Interface Product Range

Get to know our full range of AS-Interface products.