AS-Interface analog module VBA-4A-G11-I/U-F

VBA-4A-G11-I/U-F
  • Addressing jack
  • Degree of protection IP68 / IP69K
  • Function display for bus, external auxiliary voltage and outputs
  • Supply for outputs from AS-Interface or from bulk power
  • Accuracy ± 0.15 %
  • Current or voltage output
  • Integrated shielding
  • Channel-specific output monitoring
  • Communication monitoring

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of VBA-4A-G11-I/U-F

Product Description
G11 analog module
4 analog outputs
General specifications
Slave typeStandard slave
AS-Interface specificationV3.0
Required master specification≥ V2.1
UL File NumberE223772
Functional safety related parameters
MTTFd220 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Indicators/operating means
LED AS-i/FAULTStatus display; multi-colour LED
Green: normal operation
Red: communication fault
Flashing yellow/red: address 0
Flashing green/red: peripheral fault
LED ANALOGStatus of output signal; yellow LED
Yellow: Output value within range
Yellow flashing: lead breakage (on current output) or output value out of range
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INT/EXTstatus display output supply; LED green
green: output supply from AS-Interface
off: output supply from auxiliary voltage
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 75 mA (without outputs) / max. 200 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Output
Number/Type4 analog outputs
Current: 0 ... 20 mA
Voltage: 0 ... 10 V
Supplyfrom AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT)
Loadvoltage output: min. 1 kΩ
current output: max. 600 Ω
Current loading capacity≤ 120 mA (signal current + actuator supply) from AS-Interface; overload and short-circuit protected
≤ 700 mA (signal current + actuator supply) from external bulk power supply UAUX, overload and short-circuit protected
ResolutionVoltage output: 3 mV
Current output: 6 µA
Accuracy0.15 % of full-scale value
Temperature influence1 µA/K or 0,3 mV/K
Short-circuit currentvoltage output: max. 22 mA
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Programming instructions
ProfileS-7.3.6
IO code7
ID code3
ID1 codeF
ID2 code6
Data bits (function via AS-Interface)The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i)function
P0Watchdog:
P0=1 (default), watchdog active
P0=0, watchdog inactive
P1Output mode:
P1=1 (default), 4x current output
P2=0, 4x voltage output
P2Indication of peripheral fault:
P2=1 (default), peripheral fault is reported
P2=0, peripheral fault is not reported
P3Automatic mode:
P3=1 (default), manual setting of output mode
P3=0, automatic load detection (mixed mode possible)
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Pollution degree3
Mechanical specifications
Degree of protectionIP68 / IP69K
ConnectionAS-Interface/UAUX: cable piercing method, flat cable yellow/flat cable black
Outputs: M12 round connector
Material
HousingPBT PC
Mounting screwStainless steel 1.4305 / AISI 303
Mass200 g
Tightening torque, housing screws1.8 Nm
Tightening torque, cable gland0.4 Nm
MountingMounting plate

Documents: VBA-4A-G11-I/U-F

ManualsLanguageFile TypeFile Size
Manual VBA-2A-G11-I* & VBA-4A-G11-I/U-F ENGPDF3049 KB
Handbuch VBA-2A-G11-I* & VBA-4A-G11-I/U-FGERPDF3053 KB
Instruction leaflets
Instruction leaflet / Beipackzettel ALLPDF900 KB

Approvals+Certificates: VBA-4A-G11-I/U-F

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-2931APDF165 KB
Certificates
EU Ecolab Material ResistanceECOLABPDF1797 KB
US CA ULE223772LINK---
Worldwide AS-International Association AS-Interface95301PDF381 KB

Associated Products: VBA-4A-G11-I/U-F

Accessories

AS-Interface Handheld with accessoryfa

Blind plug for M12 socketsfa

Adapter cable module/hand-held programming devicefa

AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability

The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.

AS-Interface Product Range

Download the AS-Interface Product Overview

Get to know our full range of AS-Interface products.