Serviceline Industrial Sensors
Serviceline Explosion Protection

AS-Interface analog module VBA-2A-KE5-IL/UL

VBA-2A-KE5-IL/UL
  • Housing with push-in connection technology and mechanically coded terminal blocks
  • Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
  • Power supply of outputs from the external auxiliary voltage
  • Function display for bus, external auxiliary voltage and outputs

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  VBA-2A-KE5-IL/UL

Product Description
Switch cabinet module
Two analog outputs
General specifications
Slave typeStandard slave
AS-Interface specificationV3.0
Required master specification≥ V2.1
UL File NumberE223772
MTBF197 a
Indicators/operating means
LED FAULTFault indication: red LED
Red: communication error or address is 0
Red flashing: peripheral fault
LED PWRAS-Interface voltage; green LED
Green: voltage OK
Flashing green: address 0 or peripheral error
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED OUTStatus of output signal; yellow LED
Yellow: output value within value range
Continually on: current mode
1.4 s on/0.1 s off: voltage mode
Flashing yellow: wire break (at current output) or output value outside of value range
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 75 mA
Protection classIII
Current consumptionIAUX ≤ 650 mA
Surge protectionUAUX, Ue: overvoltage category II, safe isolated power supplies (PELV)
Output
Number/TypeTwo analog outputs
Current: 0 mA ... 20 mA
Voltage: 0 V ... 10 V
SupplyFrom auxiliary voltage UAUX
Loadvoltage output: min. 1 kΩ
current output: max. 600 Ω
Current loading capacity≤ 600 mA (signal current + actuator power supply) from external auxiliary voltage UAUX, overload-proof and short-circuit proof
ResolutionVoltage output: 3 mV
Current output: 6 µA
Accuracy0.15 % of full-scale value
Temperature influence1 µA/K or 0,3 mV/K
Short-circuit currentvoltage output: max. 22 mA
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Programming instructions
ProfileS-7.3.5
IO code7
ID code3
ID1 codeF
ID2 code5
Data bits (function via AS-Interface)The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i)function
P0Watchdog:
P0=1 (default), watchdog active
P0=0, watchdog inactive
P1Output mode O1:
P1=1 (default), current output
P1=0, voltage output
P2Indication of peripheral fault:
P2=1 (default), peripheral fault is reported
P2=0, peripheral fault is not reported
P3Output mode O2:
P3=1 (default), current output
P3=0, voltage output
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Shock and impact resistance15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree2
Mechanical specifications
Degree of protectionIP20
ConnectionRemovable push-in terminals
rated connection capacity:
rigid: 0.20 mm2 ... 1.5 mm2
flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2
flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Material
HousingPA 66-FR
Mass110 g
MountingDIN mounting rail
NoteMax. length of jumpers = 5 cm

Documents: VBA-2A-KE5-IL/UL

ManualsLanguageFile TypeFile Size
ManualENGPDF1983 KB
HandbuchGERPDF2595 KB
Instruction leaflets
Instruction leaflet / Beipackzettel ALLPDF133 KB

Approvals+Certificates: VBA-2A-KE5-IL/UL

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-3534PDF162 KB
Certificates
US CA ULE223772LINK---
Worldwide AS-International Association AS-InterfaceZU 129002PDF134 KB

Associated Products: VBA-2A-KE5-IL/UL

Accessories

AS-Interface Handheld with accessoryfa

Adapter cable module/hand-held programming devicefa
Jumper for switch cabinet modules with spring terminals or screw terminalsfa

AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability

The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.

AS-Interface Product Range

Get to know our full range of AS-Interface products.