Datasheet excerpt: Technical data of  KFD2-VR-Ex1.12

Product Description
Transmission range 0 V ... 9 V
General specifications
Signal typeAnalog input
Supply
ConnectionPower Rail or terminals 11+, 12-
Rated voltage20 ... 35 V DC
Ripplewithin the supply tolerance
Rated current< 20 mA
Input
Connection sidefield side
Connectionterminals 4+, 5-
Input resistancemin. 10 MΩ
Transmission range0 ... 9 V
Offset voltage/current< 2 mV / < 7 nA
Output
Connection sidecontrol side
Connectionterminals 7-, 8+
Voltage0 ... 9 V
Output resistance≤ 20 Ω
Transfer characteristics
Cut-off frequency1.2 kHz (-3 dB)
Deviation
After calibration± 5 mV at 20 °C (68 °F)
Influence of ambient temperature≤ 0.005 % of range per K
Rise time≤ 0.4 ms
Galvanic isolation
Output/power supplyBasic insulation according to DIN EN 50178, rated insulation voltage of AC 50 V
Indicators/settings
Display elementsLED
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Insulation coordinationEN 50178
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateDMT 01 ATEX E 133
MarkingEx-Hexagon I (M1) [Ex ia] I
Voltage12 V
Current2.8 mA
Power8.4 mW
Supply
Maximum safe voltage250 V (Attention! The rated voltage is lower.)
Output
Maximum safe voltage250 V (Attention! The rated voltage is lower.)
Galvanic isolation
Input/Outputsafe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V
Input/power supplysafe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)

Documents: KFD2-VR-Ex1.12

ManualsLanguageFile TypeFile Size
Manual Isolated Barriers K-systemENGPDF760 KB
Manuel pour Barrières Isolées de Système KFRAPDF759 KB
Handbuch Trennbarrieren K-SystemGERPDF745 KB
Manual Isolated Barriers K-systemRUSPDF4107 KB
Instruction manuals
ИнструкцииBULPDF62 KB
Návod k poużitíCZEPDF57 KB
Instruktions manualDANPDF55 KB
Instruction manualENGPDF49 KB
KasutusjuhendESTPDF53 KB
KäyttöohjeFINPDF53 KB
Manuel d'instructionsFRAPDF91 KB
BetriebsanleitungGERPDF51 KB
Οδηγίες χρήσηςGREPDF65 KB
HandleidingHOLPDF67 KB
Instruction manual / BetriebsanleitungHRVPDF65 KB
Használati útmutatóHUNPDF66 KB
Manuale di istruzioniITAPDF89 KB
Lietošanas pamācībaLAVPDF65 KB
Instrukciju vadovasLITPDF65 KB
Instrukcja obsługiPOLPDF68 KB
Manual de instruçõesPORPDF68 KB
Manual de utilizareRONPDF67 KB
Návod na poużitieSLKPDF126 KB
Manual de instruccionesSPAPDF91 KB
ManualSWEPDF63 KB

Approvals+Certificates: KFD2-VR-Ex1.12

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-0773APDF120 KB
Certificates
Europe DEKRA EXAM ATEX Category (M1)DMT 01 ATEX E 133PDF1310 KB
South Africa MASCMASC M/17-0784PDF280 KB

Associated Products: KFD2-VR-Ex1.12

Accessories

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indication, Connection via spring terminals with push-in connection technologypa
Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indication, Connection via spring terminals with push-in connection technologypa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa

Function: KFD2-VR-Ex1.12

This isolated barrier is used for intrinsic safety applications. It transfers voltage signals from hazardous areas to safe areas.

The input voltage of the terminals 4 and 5 is transferred to the terminals 7 and 8. The terminals 4 and 8 have the same polarity.

It repeats 0 V ... 9 V signals from strain gauges, transducers, and inductive motion sensors with signal frequencies up to 1.2 kHz.