Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description | ||
---|---|---|
HART termination board for K-System HART Multiplexer |
HART signal channels (non-intrinsically safe) | ||
---|---|---|
Load resistor | 220 Ω , switchable on | |
Interface | ||
Type | multiplexer connection : 26-pin NFP-26A (Yamaichi) | |
Signal lines | ||
Rated current | max. 30 mA per channel | |
Indicators/settings | ||
Control elements | DIP-switch |
|
DIP switch | selection of operating mode: - ON: without load resistor - OFF: with load resistor |
|
Factory setting | DIP switches S1 and S2: ON | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 For further information see system description. |
|
Degree of protection | IEC 60529:2001 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | 0 ... 50 °C (32 ... 122 °F) | |
Storage temperature | -15 ... 50 °C (5 ... 122 °F) | |
Relative humidity | ≤ 93 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | ||
Field side | screw terminals , green | |
Control side | screw terminals , green HART : 1 x IDC plug, 26-pin |
|
Core cross-section | screw terminals: 0.25 ... 1.5 mm2 (24 ... 16 AWG) | |
Mass | approx. 200 g | |
Dimensions | 110 x 125 x 67 mm (4.3 x 4.9 x 2.6 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 11 CERT 1930 X | |
Marking | ![]() |
|
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Manuals | Language | File Type | File Size |
---|---|---|---|
Manual KFD*-HM*-16 | ENG | 8323 KB | |
Handbuch KFD*-HM*-16 | GER | 8276 KB |
Statements of compliance | Certificate No. | File Type | File Size |
---|---|---|---|
EU-Declaration of conformity / EU-Konformitätserklärung | DOC-1070A | 187 KB | |
Certificates | |||
EAC Lenpromexpertiza (LPE) EAC TP TC 012/2011 | EAEC RU C-DE.AA71.B.00037/19 | 2835 KB | |
Europe Pepperl+Fuchs Certificate of Compliance ATEX Category 3 | PF11CERT1930 X | 193 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
Accessories | ||||||
|
This HART termination board has 16 terminal blocks to connect up to 16 HART field devices.
It has an integrated, switchable 220 load resistor and an integrated ground capacitor. It also has terminal blocks for the 4 mA ... 20 mA signal to the DCS/ PLC.
A 26-pin flat cable K-HM26 is used for connection of each HART Multiplexers KFD*-HM*-16 to the termination board.
Other termination boards are available. Contact Pepperl+Fuchs for details.