Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

HART Loop Converter KFD2-HLC-Ex1.D.2W

KFD2-HLC-Ex1.D.2W
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • HART field device input with transmitter power supply
  • Usable as signal splitter (1 input and several outputs)
  • 2 relay contact outputs (change-over contacts)
  • 3 analog outputs 4 mA ... 20 mA
  • Sink and source mode output
  • Configurable by keypad

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of KFD2-HLC-Ex1.D.2W

General specifications
Signal typeAnalog input
Supply
ConnectionPower Rail or terminals 23+, 24-
Rated voltage19 ... 30 V DC
Rated currentapprox. 130 mA at 24 V DC
Power dissipation2.5 W
Power consumption3.1 W
HART signal channels (intrinsically safe)
ConformityHART field device input (revision 5 to 7)
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
Connectionterminals 1, 2, 3, 4, 5, 6
Open circuit voltage/short-circuit currenttyp. 24 V / 28 mA
Input resistance250 Ω , 5 % (terminals 2, 3 and with jumper on 5, 6)
Available voltage≥ 15.5 V at 20 mA, short-circuit protected
Output
Connection sidecontrol side
Connectionoutput I: terminals 10, 11, 12, output II: terminals 16, 17, 18
output III: terminals 7, 8, 9, output IV: terminals 13, 14, 15, output V: terminals 19, 20, 21
Output I, II
Output signalrelay and LED yellow
Mechanical life107 switching cycles
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Output III, IV, V
Output signalanalog
Current range4 ... 20 mA , (source or sink mode)
Loadmax. 650 Ω , source mode
Voltage range5 ... 30 V , sink mode from external supply
Fault signaldownscale I ≤ 2 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) or hold measurement value
Other outputsHART communicator on terminals 22, 24
Collective error messagePower Rail and LED red
Transfer characteristics
Output III, IV, V
Resolutionmax. 2 µA
Accuracy< 20 µA, 10 µA typ.
Influence of ambient temperature< ± 2 µA/K
Duration of measurement/Response delayHART message acquisition time plus 100 ms
Relayprogrammable either for fault or trip value (with direction, hysteresis and delay)
Galvanic isolation
Output I/IIfunctional insulation acc. to IEC 62103, rated insulation voltage 250 Veff
Output I, II/other circuitsreinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms
Output III/IV/V/power supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Indicators/settings
Display elementsLEDs , display
Control elementsControl panel
Configurationvia operating buttons
via PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Mass300 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateBASEEFA 07 ATEX 0174
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Supply
Maximum safe voltage253 V AC (Attention! The rated voltage can be lower.)
Equipmentterminals 1, 4/3 (with link between terminals 4 and 5)
Voltage Uo25.2 V
Current Io104.9 mA
Power Po0.661 W
Equipmentterminals 2, 5/3
Voltage Ui< 28 V
Power Pi< 1.33 W
Voltage Uo1.1 V
Current Io11.9 mA
Power Po4 mW
Output I, IIterminals 10, 11, 12; 16, 17, 18 , non-intrinsically safe
Maximum safe voltage253 V (Attention! Um is no rated voltage.)
Contact loading253 V AC/1 A/cos φ > 0.7; 30 V DC/1 A resistive load (BASEEFA 07 ATEX 0174)
50 V AC/1 A/cos φ > 0.7; 30 V DC/1 A resistive load (Pepperl+Fuchs self-declaration)
Output III, IV, Vterminals 7, 8, 9; 13, 14, 15; 19, 20, 21 , non-intrinsically safe
Maximum safe voltage253 V (Attention! Um is no rated voltage.)
CertificatePF 07 CERT 1141 X
MarkingEx-Hexagon II 3G Ex nA nC IIC T4 Gc
Galvanic isolation
Input/Other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing116-0129
IECEx approval
IECEx certificateIECEx BAS 07.0047
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)

Documents: KFD2-HLC-Ex1.D.2W

ManualsLanguageFile TypeFile Size
Manual Isolated Barriers K-systemENGPDF760 KB
Manual KF**-HLC-**1.D*ENGPDF4267 KB
Manuel pour Barrières Isolées de Système KFRAPDF759 KB
Handbuch KF**-HLC-**1.D*GERPDF4267 KB
Handbuch Trennbarrieren K-SystemGERPDF745 KB
Manual Isolated Barriers K-systemRUSPDF4107 KB
Instruction leaflets
Operator card KF**-HLC-**1.D* / Bedienkarte KF**-HLC-**1.D*ALLPDF981 KB
Instructions, short instructions, safety information
ИнструкцииBULPDF69 KB
Návod k poużitíCZEPDF61 KB
Instruktions manualDANPDF58 KB
Instruction manualENGPDF50 KB
KasutusjuhendESTPDF56 KB
KäyttöohjeFINPDF56 KB
Manuel d'instructionsFRAPDF97 KB
BetriebsanleitungGERPDF62 KB
Οδηγίες χρήσηςGREPDF73 KB
HandleidingHOLPDF72 KB
Instruction manual / BetriebsanleitungHRVPDF70 KB
Használati útmutatóHUNPDF71 KB
Manuale di istruzioniITAPDF93 KB
Lietošanas pamācībaLAVPDF68 KB
Instrukciju vadovasLITPDF68 KB
Instrukcja obsługiPOLPDF72 KB
Manual de instruçõesPORPDF72 KB
Manual de utilizareRONPDF71 KB
Návod na poużitieSLKPDF130 KB
Manual de instruccionesSPAPDF95 KB
ManualSWEPDF66 KB

Approvals+Certificates: KFD2-HLC-Ex1.D.2W

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-0646BPDF112 KB
Certificates
Baseefa IECEx Certificate of ConformityIECEx BAS 07.0047LINK---
Belarus Pattern ApprovalNr. 11709PDF15640 KB
Brasil TUV Rheinland BrazilTÜV 13.2090PDF646 KB
Canada FMCoC 3032427CPDF88 KB
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB
Europe Baseefa ATEX Category (1) G ATEX Category (1) DBaseefa 07 ATEX 0174PDF3311 KB
Europe Pepperl+Fuchs Certificate of Compliance ATEX Category 3 G ATEX Category 3PF 07 CERT 1141XPDF227 KB
Russia Belarus EAC Kazakhstan NANIO "CCVE"TC RU C-IT.GB05.B.00718PDF2731 KB
Russia VNIIMS Pattern ApprovalDE.C.34.004.A No.56757PDF976 KB
South Africa MASCMASC S/17-0873PDF259 KB
USA FMCoC 3032427PDF84 KB
Control drawings
Control Drawing FM / Control Drawing FM   PDF58 KB

Software: KFD2-HLC-Ex1.D.2W

Device type managersRelease InfoFile TypeFile Size
DTM Collection HART Loop Converter / DTM Collection HART Loop Converter1.0.6.0ZIP13857 KB
Software Tools
PACTware 4.1 SP5 / PACTware 4.1 SP54.1.0.52ZIP50675 KB
PACTware 5.0 / PACTware 5.05.0.3.2ZIP56301 KB

Associated Products: KFD2-HLC-Ex1.D.2W

Accessories

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
For HART Loop Converters, Frame application, like e. g. PACTware, must be installed separatelypa
Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indication, Connection via spring terminalspa
Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indication, Connection via spring terminalspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Internet download possiblepa