Serviceline Industrial Sensors
Serviceline Explosion Protection

HART Multiplexer Slave KFD0-HMS-16

KFD0-HMS-16
  • 16-channel
  • No external power required
  • HART field device input (revision 5 to 7)
  • Used with HART Multiplexer Master KFD2-HMM-16
  • Up to SIL 3 acc. to IEC 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KFD0-HMS-16

Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
Connectionvia 14-channel flat cable form master KFD2-HMM-16
HART signal channels (non-intrinsically safe)
ConformityHART field device input (revision 5 to 7)
Connection26-pin flat cable for analog connections
14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16
Leakage current< 3 µA at -20 ... 85 °C (-4 ... 185 °F)
Terminating resistorexternal 230 ... 500 Ω standard (up to 1000 Ω possible)
Output voltage≥ 400 mV ss (with the terminator resistance specified above)
Output resistance100 Ω or smaller, capacitive coupling
Input impedanceaccording to HART specification
Input voltage range0.08 ... 4 V ss ; typ. ± 5.2 V as local reference
Indicators/settings
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) , housing type B1
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
CertificatePF 07 CERT 1143 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-15:2010
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: KFD0-HMS-16

ManualsLanguageFile TypeFile Size
Manual KFD*-HM*-16ENGPDF8323 KB
Handbuch KFD*-HM*-16GERPDF8276 KB
Instruction manuals
ИнструкцииBULPDF61 KB
Návod k poużitíCZEPDF55 KB
Instruktions manualDANPDF54 KB
Instruction manualENGPDF47 KB
KasutusjuhendESTPDF51 KB
KäyttöohjeFINPDF51 KB
Manuel d'instructionsFRAPDF88 KB
BetriebsanleitungGERPDF50 KB
Οδηγίες χρήσηςGREPDF63 KB
HandleidingHOLPDF64 KB
Instruction manual / BetriebsanleitungHRVPDF64 KB
Használati útmutatóHUNPDF64 KB
Manuale di istruzioniITAPDF85 KB
Lietošanas pamācībaLAVPDF62 KB
Instrukciju vadovasLITPDF62 KB
Instrukcja obsługiPOLPDF65 KB
Manual de instruçõesPORPDF65 KB
Manual de utilizareRONPDF65 KB
Návod na poużitieSLKPDF123 KB
Manual de instruccionesSPAPDF87 KB
ManualSWEPDF61 KB

Approvals+Certificates: KFD0-HMS-16

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-0777BPDF64 KB
Certificates
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB
Europe Pepperl+Fuchs Certificate of Compliance ATEX Category 3PF 07 CERT 1143 XPDF209 KB
exida Functional Safety AssessmentP+F 02/4-11 R006PDF348 KB

Software: KFD0-HMS-16

Device type managersRelease InfoFile TypeFile Size
DTM Collection HART-Multiplexer / DTM Collection HART-Multiplexer2.0.0.130ZIP12240 KB
Software Tools
PACTware 4.1 SP6 / PACTware 4.1 SP64.1.0.53ZIP43327 KB
PACTware 5.0 / PACTware 5.05.0.5.31ZIP44203 KB

Associated Products: KFD0-HMS-16

Matching System Components

Connection board for K-System HART Multiplexer, 16-channel, Interface for series connection or parallel connection, Integrated, switchable 220 Ω resistorpa
Matching System Components

16-channel, 24 V DC supply (Power Rail), HART field device input (revision 5 to 7), Up to 15 KFD0-HMS-16 slave units can be connected, Up to SIL 3 acc. to IEC 61508pa
Accessories

K-System accessory, Connection cable for KFD2-HMM-16 to up to 15 KFD0-HMS-16, 14-pin flat cablepa

K-System accessory, Connection cable for KF*-HM*-16 to Termination Board, 26-pin flat cablepa
Communication DTM, Frame application, like e. g. PACTware, must be installed separatelypa
Human machine interface, For HiDMux2700, For KFD2-HMM-16/KFD0-HMS-16pa
Device DTM, For HART multiplexers, Communication DTMpa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa

Function: KFD0-HMS-16

This HART Multiplexer Slave operates up to 16 analog field instruments. It can be operated only with the HART Multiplexer Master KFD2-HMM-16 and is powered by the master across a 14- pin flat cable connection.

Up to 15 slaves can be connected to the master.

The slave address is set with a 16- position rotary switch (addresses 1 ... 16). If only one slave is connected to the master, then the slave address should be 1. If multiple slaves are connected, slaves must be assigned addresses in ascending order.

The analog signals are fed into the slave by means of a 26-pin flat cable. Sixteen leads are reserved for the HART signal of the analog measurement circuits. The remaining 10 leads are assigned to ground.