Terminal Module HiD2900TOP

HiD2900TOP
  • 2-channel
  • 24 V DC supply (bus powered)
  • Field circuit protected by fuse

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HiD2900TOP

General specifications
Signal typeUniversal
Supply
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage20.4 ... 30 V via Termination Board
Power dissipation0.2 W
Current≤ 75 mA (per channel)
Control circuit
ConnectionSL1: 8a(+), 7a(-); 10a(+), 9a(-)
Signal0 ... 20 mA
0 ... 5 V
Internal resistor250 Ω via DIP switch and programmable
Field circuit
Connectionterminals 1, 2, 3, 4
Signal0 ... 20 mA
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityFor further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature0 ... 60 °C (32 ... 140 °F)
Relative humidity5 ... 90 %, non-condensing up to 35 °C (95 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 140 g
Dimensions18 x 114 x 135 mm (0.7 x 4.5 x 5.3 inch) (W x H x D)
Height114 mm
Width18 mm
Depth135 mm
Mountingon termination board
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210107
ECLASS 12.027210107
ECLASS 11.027210107
ECLASS 10.0.127210107
ECLASS 9.027210107
ECLASS 8.027210107
ECLASS 5.127210107
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiD2900TOP

Function

The device supports the pass-through of non-intrinsically safe signals from and to the control. The device uses the terminal block on the front side.

Each channel can be configured via DIP switches for the pass-through of the input signal or the output signal. At the same time, the field device can be supplied via the power supply of the termination board.
The device has an internal resistor. Use this resistance, if you want to convert a 0 mA ... 20 mA signal to a 0 V ... 5 V signal. Choose this function via DIP switches.

This device mounts on a HiD Termination Board.

Product Documentation: HiD2900TOP

Language Selection:
Safety and Security DocumentationLanguageFile TypeFile Size
Instruction manualENGPDF164 KB
Manuals
System ManualENGPDF5438 KB