Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

Frequency Converter with Direction and Synchronization Monitor KFD2-UFT-Ex2.D

KFD2-UFT-Ex2.D
  • 2-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • Input frequency 1 mHz ... 1 kHz
  • Current output 0/4 mA ... 20 mA
  • Relay contact and transistor output
  • Start-up override
  • Configurable by PACTware or keypad
  • Line fault detection (LFD)

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of KFD2-UFT-Ex2.D

Product Description
24 V DC
General specifications
Signal typeDigital Input
Supply
Connectionterminals 23+, 24- or power feed module/Power Rail
Rated voltage20 ... 30 V DC
Rated currentapprox. 130 mA
Power dissipation2.2 W
Power consumption2.5 W
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
Connectioninput I: terminals 1+, 3-
input II: terminals 4+, 6-
input III: terminals 13+, 14- (control input 1)
input IV: terminals 15+, 14- (control input 2)
Input I, II2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Open circuit voltage/short-circuit current8.2 V / 10 mA
Pulse durationmin. 250 µs , overlap on direction of rotation signal: ≥ 125 µs
Input frequencyrotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
Line fault detectionbreakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input III, IV
Active/PassiveI > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit current18 V / 5 mA
Output
Connection sidecontrol side
Connectionoutput I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 19+, 20-
output IV: terminals 21+, 20-
output V: terminals 7-, 8+
Output I, IIsignal , relay
Contact loading250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
Mechanical life5 x 107 switching cycles
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Output III and IVsignal , electronic output, passive
Contact loading40 V DC
Signal level1-signal: (external voltage) - 2.5 V max. for 10 mA or 3 V max. for 100 mA (100 mA, short-circuit proof) -2.5 V (50 mA, short-circuit/overload proof)
0-signal: switched off (off-state current ≤ 10 µA)
Output Vanalog
Current range0 ... 20 mA or 4 ... 20 mA
Open loop voltagemax. 24 V DC
Loadmax. 650 Ω
Fault signaldownscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Collective error messagePower Rail
Transfer characteristics
Input I and II
Measurement range0.001 ... 1000 Hz
Resolutionslip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz
Accuracyslip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz
Measuring timefrequency measurement: < 100 ms
Influence of ambient temperature0.003 %/K (30 ppm)
Output I, II
Response delay≤ 200 ms
Output V
Resolution< 10 µA
Accuracy< 30 µA
Influence of ambient temperature0.005 %/K (50 ppm)
Galvanic isolation
Input I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input III, IV/power supply and collective errorfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Output I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, IIIreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, IV reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III, IV/power supply and collective errorbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III, IV/input III, IVbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III, IV/Vbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output V/power supply and collective errorfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Interface/power supply and collective errorfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Interface/output III, IVbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Indicators/settings
Display elementsLEDs , display
Control elementsControl panel
Configurationvia operating buttons
via PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
InputEN 60947-5-6:2000
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Mass300 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateTÜV 99 ATEX 1471
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Supply
Maximum safe voltage40 V DC (Attention! Um is no rated voltage.)
Input I and IIterminals 1+, 3-; 4+, 6-: Ex ia
Voltage Uo10.1 V
Current Io13.5 mA
Power Po34 mW (linear characteristic)
Input III and IVterminals 13+, 14-; 15+, 14- non-intrinsically safe
Maximum safe voltage Um40 V (Attention! Um is no rated voltage.)
Output I, IIterminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Maximum safe voltage253 V (Attention! The rated voltage can be lower.)
Contact loading253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 99 ATEX 1471)
Output III and IVterminals 19, 20, 21 non-intrinsically safe
Maximum safe voltage Um40 V DC (Attention! Um is no rated voltage.)
Output Vterminals 8+, 7- non-intrinsically safe
Maximum safe voltage Um40 V DC (Attention! Um is no rated voltage.)
InterfaceRS 232
Maximum safe voltage40 V (Attention! Um is no rated voltage.)
CertificateTÜV 02 ATEX 1885 X
MarkingEx-Hexagon II 3G Ex nA nC IIC T4 Gc
Output I, II
Contact loading50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
Galvanic isolation
Input I, II/other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing16-538FM-12
UL approvalE223772
IECEx approvalIECEx TUN 04.0007
Approved for[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: KFD2-UFT-Ex2.D

ManualsLanguageFile TypeFile Size
Installation and configuration guide Device Type Manager (DTM)ENGPDF8665 KB
Manual Isolated Barriers K-systemENGPDF760 KB
Manual KF**-UFT-(Ex)2.DENGPDF1611 KB
Manuel pour Barrières Isolées de Système KFRAPDF759 KB
Handbuch KF**-UFT-(Ex)2.DGERPDF1422 KB
Handbuch Trennbarrieren K-SystemGERPDF745 KB
Installations- und Konfigurationsanleitung Device Type Manager (DTM)GERPDF8463 KB
Manual Isolated Barriers K-systemRUSPDF4107 KB
Instruction leaflets
Operator card KF**-UFT-**2.D / Bedienkarte KF**-UFT-**2.DALLPDF831 KB
Instructions, short instructions, safety information
ИнструкцииBULPDF69 KB
Návod k poużitíCZEPDF61 KB
Instruktions manualDANPDF58 KB
Instruction manualENGPDF50 KB
KasutusjuhendESTPDF56 KB
KäyttöohjeFINPDF56 KB
Manuel d'instructionsFRAPDF97 KB
BetriebsanleitungGERPDF62 KB
Οδηγίες χρήσηςGREPDF73 KB
HandleidingHOLPDF72 KB
Instruction manual / BetriebsanleitungHRVPDF70 KB
Használati útmutatóHUNPDF71 KB
Manuale di istruzioniITAPDF93 KB
Lietošanas pamācībaLAVPDF68 KB
Instrukciju vadovasLITPDF68 KB
Instrukcja obsługiPOLPDF72 KB
Manual de instruçõesPORPDF72 KB
Manual de utilizareRONPDF71 KB
Návod na poużitieSLKPDF130 KB
Manual de instruccionesSPAPDF95 KB
ManualSWEPDF66 KB

Approvals+Certificates: KFD2-UFT-Ex2.D

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-0169CPDF76 KB
Certificates
Australia Test SafeANZEx 17.3006XPDF6788 KB
Belarus Pattern ApprovalNr. 11709PDF15640 KB
Brasil TUV Rheinland BrazilTÜV 14.0357PDF641 KB
CA ULE223772 cUL (NRAQ7)LINK---
Canada FMCoC 3009603CPDF39 KB
China NEPSIGYJ 161233PDF2979 KB
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB
Europe TUV Nord ATEX Category (1)TÜV 99 ATEX 1471PDF2701 KB
Europe TUV Nord ATEX Category 3 GTÜV 02 ATEX 1885XPDF1101 KB
India CCOEA/P/HQ/MH/104/3928(P354023)PDF598 KB
Russia Belarus EAC Kazakhstan NANIO "CCVE"TC RU C-IT.GB05.B.00718PDF2731 KB
Russia VNIIMS Pattern ApprovalDE.C.33.004.A No.34620PDF4530 KB
South Africa MASCMASC MS/17-0881PDF334 KB
TUV Nord IECEx Certificate of ConformityIECEx TUN 04.0007LINK---
Test Safe IECEx Certificate of ConformityIECEx TSA 18.0007XLINK---
USA FMCoC 3009603PDF40 KB
USA ULE223772 UL (NRAQ)LINK---
Control drawings
Control Drawing FM / Control Drawing FM   PDF156 KB

Software: KFD2-UFT-Ex2.D

Device type managersRelease InfoFile TypeFile Size
DTM Collection Interface Technology 2 / DTM Collection Interface Technology 21.4.110.71ZIP33316 KB
Software Tools
PACTware 4.1 SP5 / PACTware 4.1 SP54.1.0.52ZIP50675 KB
PACTware 5.0 / PACTware 5.05.0.3.2ZIP56301 KB

Associated Products: KFD2-UFT-Ex2.D

Accessories
For K-, E- and H-System, Frame application, like e. g. PACTware, must be installed separatelypa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Internet download possiblepa