Serviceline Industrial Sensors
Serviceline Explosion Protection

SMART Current Driver HiC2031

HiC2031
  • 1-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Current output up to 650 Ω load
  • Low power dissipation
  • Up to SIL 2 acc. to IEC 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HiC2031

General specifications
Signal typeAnalog output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage19 ... 30 V DC bus powered via Termination Board
Ripple≤ 10 %
Rated current≤ 30 mA at 24 V
Power dissipation≤ 600 mW at 20 mA and 500 Ω load
Power consumption≤ 700 mW
Input
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-)
Input signal4 ... 20 mA , limited to approx. 26 mA
Input voltageopen loop voltage of the control system < 30 V
Voltage dropapprox. 6 V at 20 mA
Input resistance> 100 kΩ, with field wiring open
Output
Connection sidefield side
ConnectionSL2: 5a(+), 5b(-)
Voltage≥ 13 V at 20 mA
Current4 ... 20 mA
Load0 ... 650 Ω
Ripple20 mV rms
Transfer characteristics
Deviationat 20 °C (68 °F), 4 ... 20 mA
< 0.1 % of full scale, incl. non-linearity and hysteresis
Influence of ambient temperature< 2 µA/K (-20 ... 70 °C (-4 ... 158 °F))
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 1 mApp signal 0 ... 3 kHz (-3 dB)
Rise time10 to 90 % ≤ 10 ms
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Output/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Indicators/settings
Display elementsLED
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012
EN 61326-3-2:2008
For further information see system description.
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2012
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Mountingon Termination Board
Codingpin 1 and 3 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateCESI 06 ATEX 017
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
OutputEx ia
Supply
Maximum safe voltage250 V AC (Attention! Um is no rated voltage.)
EquipmentSL2: 5a(+), 5b(-)
Voltage Uo25.2 V
Current Io100 mA
Power Po630 mW
Internal capacitance Ci5.7 nF
Internal inductance Li negligible
CertificateCESI 19 ATEX 027 X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015
International approvals
FM approval
FM certificateFM 19 US 0122 X , FM 19 CA 0065 X
Control drawing116-0470 (cFMus)
UL approvalE106378
Control drawing116-0458 (cULus)
IECEx approval
IECEx certificateIECEx CES 06.0002X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: HiC2031

ManualsLanguageFile TypeFile Size
Functional Safety ManualENGPDF491 KB
Manual H-System Isolated Barriers and Termination BoardsENGPDF5551 KB
Handbuch Funktionale SicherheitGERPDF495 KB
Handbuch Trennbarrieren und Termination Boards H-SystemGERPDF5543 KB
Instruction manuals
ИнструкцииBULPDF152 KB
Návod k poużitíCZEPDF147 KB
Instruktions manualDANPDF146 KB
Instruction manualENGPDF152 KB
KasutusjuhendESTPDF142 KB
KäyttöohjeFINPDF142 KB
Manuel d'instructionsFRAPDF147 KB
BetriebsanleitungGERPDF152 KB
Οδηγίες χρήσηςGREPDF155 KB
HandleidingHOLPDF146 KB
Instruction manual / BetriebsanleitungHRVPDF145 KB
Használati útmutatóHUNPDF148 KB
Manuale di istruzioniITAPDF145 KB
Lietošanas pamācībaLAVPDF145 KB
Instrukciju vadovasLITPDF146 KB
Instrukcja obsługiPOLPDF149 KB
Manual de instruçõesPORPDF146 KB
Manual de utilizareRONPDF146 KB
Návod na poużitieSLKPDF146 KB
Navodila za uporaboSLVPDF144 KB
Manual de instruccionesSPAPDF146 KB
ManualSWEPDF142 KB

CAD+CAE: HiC2031

CADFile TypeFile Size
Dimension drawing 2-D (DXF) / Abmessungszeichnung 2-D (DXF)ZIP16364 KB

Approvals+Certificates: HiC2031

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-4563PDF191 KB
Certificates
Belarus Pattern ApprovalNr. 11708PDF8943 KB
Brasil TUV Rheinland BrazilTÜV 16.0820PDF1291 KB
CESI IECEx Certificate of ConformityIECEx CES 06.0002XLINK---
Canada FMFM19CA0065XPDF374 KB
Canada UL cULE106378 cUL (QUZW7)LINK---
Canada UL cULE106378 cUL (QVAJ7)LINK---
China NEPSIGYJ17.1286PDF1683 KB
DNV GL MarineTAA00002EDPDF72 KB
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB
Europe CESI ATEX Category (1) D ATEX Category (M1) ATEX Category (1) GCESI 06 ATEX 017PDF788 KB
Europe CESI ATEX Category 3CESI 19 ATEX 027XPDF492 KB
Korea KOSHA15-AV4BO-0594PDF661 KB
Russia Belarus Kazakhstan EAC EAC TP TC 012/2011EAEC RU C-DE.EX01.B.00102/19PDF9815 KB
USA FMFM19US0122XPDF346 KB
USA ULE106378 UL (QVAJ)LINK---
USA ULE106378 UL (QUZW)LINK---
Worldwide TUV Rheinland Functional Safety Certificate968/FSP 1937.00/19PDF620 KB
Control drawings
Control drawing CSA / Control drawing CSA   PDF35 KB
Control drawing CSA / Control drawing CSA   PDF35 KB

Function: HiC2031

This isolated barrier is used for intrinsic safety applications.

It repeats the input signal from a control system to drive HART I/P converters, valve actuators, and displays located in a hazardous area.

Digital signals are superimposed on the analog values at the field side or control side and are transferred bi-directionally.

An open field circuit presents a high impedance to the control side to allow alarm conditions to be monitored by the control system.

This device mounts on a HiC termination board.