PS3500 Power Supply Backplane - 6-position PS3500-TB-6

PS3500-TB-6
  • 6-position backplane for PS2500/PS3500 series power modules
  • Multiple input/output wiring configurations
  • Removable terminals for easy wiring
  • Serial or parallel fault bus
  • ATEX, IECEx, and cULus approvals for Div 2/Zone 2

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  PS3500-TB-6

Product Description
6 position N+1 Power Supply Backplane for use with PS2500 and PS3500 N+1 Power Supplies.
Interface
Typediagnostic bus: RS 485
Input
Rated valuesterminal ratings: current 6.5 A per slot
Voltage90 ... 250 V AC, 44 ... 66 Hz; 90 ... 300 V DC
Output
Rated valuesterminal ratings: current 65 A, voltage 300 V
Fault signalremovable terminals : power module alarm
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EURefer to DoC for all directives and standards met.
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionEN 60529
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % , noncondensing
Shock resistance15 g , 11 ms
Vibration resistance1 g , 58 ... 150 Hz
Mechanical specifications
Core cross-sectioninput terminals: 4 mm2 (10 AWG)
output terminals: 10 mm2 (6 AWG)
Housing materialPowder Coated, 1010 Cold Rolled Steel
Degree of protectionIP20
Massapprox. 2.9 kg   ( 6.375 lbs )
Dimensions193 x 78 x 486 mm (7.6 x 3.1 x 19.1 inch)
Data for application in connection with hazardous areas
CertificateDEMKO 12 ATEX 1103387X
MarkingEx-Hexagon II3 G Ex nA IIC T4 Gc
International approvals
UL approvalcULus Listed
E230669
E350173
Approved forClass I/Div 2, ABCD Class I, Zone 2, Grp IIC T4
IECEx approvalIECEx UL 13.0082X
Ex nA nC IIC T4 Gc

Documents: PS3500-TB-6

ManualsLanguageFile TypeFile Size
PS3500-N+1 Redundant Power Supply Installation and Operation ManualENGPDF2753 KB
Technical information
Power Supply Reliability USAPDF3099 KB
Product information
Unrelenting Current Powering Availability with PS3500 Power SuppliesENGPDF5743 KB

CAD+CAE: PS3500-TB-6

CADFile TypeFile Size
DWG files for PS3500 power supply system / CAD-Dateien 2-DZIP10039 KB

Approvals+Certificates: PS3500-TB-6

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-B011APDF56 KB
Certificates
ATEX CertificateDEMKO 12 ATEX 1103387XPDF1730 KB
EAC Lenpromexpertiza (LPE) EAC TP TC 012/2011EAEC RU C-DE.AA71.B.00037/19PDF2835 KB
IECEx Certificate of ConformityIECEx UL 13.0082XLINK---
India CCOEA/P/HQ/MH/104/4005(P357976)PDF695 KB
UL Hazardous LocationE350173 (NRAD, NRAD7)PDF242 KB
UL Ordinary LocationE230669 (NMTR, NMTR7)PDF242 KB

Associated Products: PS3500-TB-6

Matching system components
PS3500 Power Supply Module - 22.5 V - 30 Vpa
PS3500 Diagnostic Module for use with PS3500 power supplies.pa

Function: PS3500-TB-6

The PS3500-TB-6 is a 6-position backplane used by the PS2500/PS3500 series power supply modules. Power configuration and alarms are controlled by DIP switches on the backplane. The backplane connects to universal AC (90- 250 V) or DC (90-300 V) inputs and supports redundancy.

The PS3500-TB-6 allows a maximum of 90 A of output power, 75 A in N+1 configuration or 45 A in triple redundant mode. Automatic load sharing of all of the power modules is built into the backplane. Input and output lines can be wired independently or in parallel, providing easy configuration of N+1 redundancy.

The fault bus can be configured in serial or parallel combinations.