Serviceline Industrial Sensors
Serviceline Explosion Protection

Fieldbus Power Supply KLD2-FBPS-1.12.220

KLD2-FBPS-1.12.220
  • Output: 12 ... 13 V/220 mA
  • For battery or solar-powered applications
  • For demanding environmental conditions
  • Installation in Zone 2/Class I, Div. 2
  • For FOUNDATION Fieldbus H1
  • Fixed, high-availability terminator
  • Low heat dissipation

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KLD2-FBPS-1.12.220

General specifications
Design / MountingCabinet installation
Supply
ConnectionPower Rail or terminals 8+, 11+; 9-, 12-
Rated voltage10 ... 30 V DC
Rated current350 ... 120 mA
Power dissipationtyp. ≤ 0.5 W
Fieldbus interface
Connectionterminals 3+, 6+; 2-, 5-; 1S, 4S (S=screen connection)
Rated voltage12 ... 13 V
Rated current220 mA
Galvanic isolation
Fieldbus segment/Supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 250 V AC
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC/EN 60529
Fieldbus standardIEC 61158-2, ISA S 50.02 part 2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Pollution degreemax. 2, according to IEC 60664
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typeTerminals
Core cross-sectionup to 2.5 mm2
Housing20 mm x 115 mm x 107 mm
Housing materialPolycarbonate
Degree of protectionIP20
Massapprox. 210 g
MountingDIN rail mounting
Data for application in connection with hazardous areas
CertificateTÜV 06 ATEX 553079 X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-7:2015
International approvals
FM approval
FM certificateFM 19 US 0015 X and FM 19 CA 0011 X
FM markingAEx/Ex ec IIC T4
Certificates and approvals
Marine approvalDNV A-14038
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: KLD2-FBPS-1.12.220

Instruction manualsLanguageFile TypeFile Size
ИнструкцииBULPDF132 KB
Návod k poużitíCZEPDF126 KB
Instruktions manualDANPDF126 KB
Instruction manualENGPDF55 KB
KasutusjuhendESTPDF122 KB
KäyttöohjeFINPDF122 KB
Manuel d'instructionsFRAPDF62 KB
BetriebsanleitungGERPDF56 KB
Οδηγίες χρήσηςGREPDF134 KB
HandleidingHOLPDF2 KB
Instruction manual / BetriebsanleitungHRVPDF0 KB
Használati útmutatóHUNPDF127 KB
Manuale di istruzioniITAPDF59 KB
Lietošanas pamācībaLAVPDF126 KB
Instrukciju vadovasLITPDF127 KB
Instrukcja obsługiPOLPDF128 KB
Manual de instruçõesPORPDF0 KB
Manual de utilizareRONPDF126 KB
Návod na poużitieSLKPDF127 KB
Navodila za uporaboSLVPDF0 KB
Manual de instruccionesSPAPDF58 KB
ManualSWEPDF124 KB

Approvals+Certificates: KLD2-FBPS-1.12.220

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-2718APDF85 KB
Certificates
Canada FMFM 19 CA 0011XPDF356 KB
DNV GL MarineTAA0000272PDF78 KB
Europe TUV Nord ATEX II 3 GTÜV 06 ATEX 553079XPDF2011 KB
USA FMFM 19 US 0015XPDF213 KB

Associated Products: KLD2-FBPS-1.12.220

Accessories

Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa
Alternative power supply, Nominal current 4 A, Simple installation, Standard length 50 cm, can be shortened to any length in 4 cm steps, Terminating insulation by end cap, included in the delivery package, With 2 leads for voltage supply and 1 lead for centralized error messagespa

Function: KLD2-FBPS-1.12.220

This fieldbus power supply is an all-in-one module for single fieldbus segments. It adapts current and voltage and provides the impedance filter required. Reliability of communication is enhanced through galvanic isolation between segment and bulk power supply.

This supply is specifically designed for very demanding environmental conditions. Low input ratings and very low heat dissipation are suitable for battery or solar-powered application.

Availability and a long service life are achieved through a passive impedance filter and a design optimized for low heat dissipation. Modules can be mounted with no spacing required in any direction for an optimized and space-saving cabinet layout. The mobile Advanced Diagnostic Module connects directly to test plug sockets located on the plug-in terminal. In conjunction with the modular Segment Protector it is a perfectly expandable solution.

From decisions to planning, installation, and commissioning up to operation and maintenance: Discover how to make the most out of your fieldbus infrastructure …

The Quick Select Product Guide for interface technology, FieldConnex®, and remote I/O connection technologies will help you select the right technology and systems when designing plants.