Advanced Diagnostic Gateway with Ethernet and FF-H1 Interface and I/O KT-MB-GT2AD.FF.IO

KT-MB-GT2AD.FF.IO
  • System integration kit for Advanced Diagnostics
  • PCS integration via Diagnostic Manager or device DTM
  • Simple automatic setup of Advanced Diagnostics
  • Alarm handling and integrated I/O for cabinet monitoring/control
  • For FOUNDATION Fieldbus and PROFIBUS PA
  • Installation in Zone 2

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KT-MB-GT2AD.FF.IO

General specifications
Design / MountingMotherboard based
Supply
Rated voltage19.2 ... 35 V DC SELV/PELV
Rated current210 ... 120 mA
Power dissipationmax. 4.2 W
Fieldbus connection
Fieldbus typeFOUNDATION Fieldbus
Physical layer profileprofile type 114
ITK version6
Implementationresource block1x RS
function block4x MDI, 1x MDO, 1x MAI, 1x DI
transducer block16x ADM TB, 1x IO TB
Firmware updateEthernet
Polaritypolarity-sensitive
Rated voltage9 ... 35 V SELV/PELV
Rated current0 mA
Connection to power link
Connection
Ethernet Interface
Rated voltagemax. 35 V SELV/PELV
Port100 BASE-TX
ProtocolTCP/IP and UDP/IP
ServicesICMP , DHCP , AutoIP , HTTP
Connection typeRJ-45 socket, 8-pin
Transfer rate100 MBit/s
Diagnostic Bus
Connectiononly for the connection to protected circuits
Rated voltagemax. 35 V
Number of Diagnostic Bus Channels2
Number of Diagnostic Modules/Channel31 Using Ethernet Interface , 8 Using Fieldbus Interface
Terminationintegrated
Cable length/Channel30 m
Indicators/operating means
LED ERRred: Hardware fault
LED PWRgreen: Power on
Fault signalbuzzer on
LINK/ACTyellow
CH1, CH2yellow: diagnostic bus activity
Inputs
Input I, II
Input typeselectable: Frequency input , NAMUR/mechanical contact
Frequency
Connectiononly passive load
Rated voltagemax. 35 V
Input frequency0.3 Hz to 1 kHz
Pulse durationmin. 50 µs
Accuracy± 1 %
Cable lengthmax. 30 m
Line fault detectionlead breakage , short-circuit
NAMUR
Sensor typeNAMUR sensor according to IEC/EN 60947-5-6
Connectiononly passive load
Rated voltagemax. 35 V
Switching frequency10 Hz
Cable lengthmax. 30 m
Line fault detectionlead breakage , short circuit
Input III, IV
Input typeNAMUR/mechanical contact
NAMUR
Sensor typeNAMUR sensor according to IEC/EN 60947-5-6
Connectiononly passive load
Rated voltagemax. 35 V
Switching frequency10 Hz
Cable lengthmax. 30 m
Line fault detectionlead breakage , short circuit
Input V
Input typeselectable: diagnostic bus CH 1 alarm input , NAMUR/mechanical contact
Alarm Input
Connectiononly passive load
Rated voltagemax. 35 V
Cable lengthmax. 30 m
Line fault detectionlead breakage , short circuit
NAMUR
Sensor typeNAMUR sensor according to IEC/EN 60947-5-6
Connectiononly passive load
Rated voltagemax. 35 V
Switching frequency10 Hz
Cable lengthmax. 30 m
Line fault detectionlead breakage , short circuit
Input VI
Input typeselectable: diagnostic bus CH 2 alarm input , NAMUR/mechanical contact
Alarm Input
Connectiononly passive load
Rated voltagemax. 35 V
Cable lengthmax. 30 m
Line fault detectionlead breakage , short-circuit
NAMUR
Sensor typeNAMUR sensor according to IEC/EN 60947-5-6
Connectiononly passive load
Rated voltagemax. 35 V
Switching frequency10 Hz
Cable lengthmax. 30 m
Line fault detectionlead breakage , short circuit
Input VII, VIII
Input typeselectable: Pt100 4-wire temperature input , NAMUR/mechanical contact
Temperature
Connectiononly passive load
Rated voltagemax. 35 V
Measurement range-50 ... 90 °C (-58 ... 194 °F)
Accuracy1 K
Measuring current1 mA
Lead resistance4.2 Ω per line
Cable lengthmax. 30 m
Line fault detectionlead breakage , short-circuit
NAMUR
Sensor typeNAMUR sensor according to IEC/EN 60947-5-6
Connectiononly passive load
Rated voltagemax. 35 V
Switching frequency10 Hz
Cable lengthmax. 30 m
Line fault detectionlead breakage , short circuit
Humidity
Measurement range0 ... 95 % RH
Accuracy2 % RH
Resolution0.04 %
Outputs
Output I
Output typeselectable: diagnostic bus CH 1 , relay , NO contact
Contact loading250 V AC/ 6 A resistive load
Mechanical life1 x 105 switching cycles
Response timeturn-on time 7 ms , turn-off time 3 ms
Switching frequency6 min-1 full load, 1200 min-1 without load
Output II
Output typeselectable: diagnostic bus CH 2 , relay , NO contact
Contact loading250 V AC/ 6 A resistive load
Mechanical life1 x 105 switching cycles
Response timeturn-on time 7 ms , turn-off time 3 ms
Switching frequency6 min-1 full load, 1200 min-1 without load
Output III
Output typeselectable: common alarm , volt-free contact , NC contact
Connectiononly for the connection to protected circuits
Voltage50 V DC
Currentmax. 1 A
Output IV
Output typecommon alarm , buzzer
Galvanic isolation
All circuits/FEfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Output I, II/other circuitsfunctional insulation acc. to IEC 62103, rated insulation voltage 250 Veff
Ethernet/Supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Ethernet/other circuitsfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Fieldbus/other circuitsfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Diagnostic Bus/other circuitsfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Low voltage
Directive 73/23/EECEN 61010-1:2010
Standard conformity
Galvanic isolationIEC 62103
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Climatic conditionsDIN IEC 721
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
EthernetIEEE 802.3
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F) hazardous area
-40 ... 70 °C (-40 ... 158 °F) safe area horizontal DIN rail mounting
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance5 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Pollution degreemax. 2, according to IEC 60664
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Housing materialPolycarbonate
Housing widthsee dimensions
Housing heightsee dimensions
Housing depthsee dimensions
Degree of protectionIP20
Mass500 g
MountingDIN rail mounting
Data for application in connection with hazardous areas
FOUNDATION Fieldbus
ConnectionFor connection to circuits with safe limited voltage according to IEC 60079-11:2011, type of protection "ic"
Voltage Uimax. 35 V
CertificateTÜV 14 ATEX 115980 X
MarkingMotherboard MB-FB-GT.AD.FF.IO Ex-Hexagon II 3 G Ex nA nC IIC T4 Gc , Gateway Ex-Hexagon II 3 G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
IECEx approvalIECEx TUN 14.0003X
Approved forMotherboard Ex nA nC IIC T4 Gc , Gateway Ex nA IIC T4 Gc
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 11.027242692
ECLASS 10.0.127242692
ECLASS 9.027242692
ECLASS 8.027242692
ECLASS 5.127242692
ETIM 8.0EC001604
ETIM 7.0EC001604
ETIM 6.0EC001604
ETIM 5.0EC001604
UNSPSC 12.139121008

Documents: KT-MB-GT2AD.FF.IO

ManualsLanguageFile TypeFile Size
Manual Diagnostic ManagerENGPDF25397 KB
Instruction manuals
ИнструкцииBULPDF233 KB
Instruction manual / BetriebsanleitungCHSPDF326 KB
Návod k poużitíCZEPDF225 KB
Instruktions manualDANPDF224 KB
Instruction manualENGPDF230 KB
KasutusjuhendESTPDF221 KB
KäyttöohjeFINPDF220 KB
Manuel d'instructionsFRAPDF228 KB
BetriebsanleitungGERPDF230 KB
Οδηγίες χρήσηςGREPDF234 KB
HandleidingHOLPDF225 KB
Instruction manual / BetriebsanleitungHRVPDF224 KB
Használati útmutatóHUNPDF226 KB
Manuale di istruzioniITAPDF225 KB
Lietošanas pamācībaLAVPDF224 KB
Instrukciju vadovasLITPDF226 KB
Instrukcja obsługiPOLPDF228 KB
Manual de instruçõesPORPDF227 KB
Manual de utilizareRONPDF226 KB
Návod na poużitieSLKPDF226 KB
Navodila za uporaboSLVPDF224 KB
Manual de instruccionesSPAPDF228 KB
ManualSWEPDF222 KB
Short instructions, safety information
Quick Start Guide Diagnostic ManagerENGPDF1520 KB
Documents
End-user software license agreement (EULA)ENGPDF37 KB

Approvals+Certificates: KT-MB-GT2AD.FF.IO

CertificatesCertificate No.File TypeFile Size
China SITIIAS CCC Ex Certificate2020322310003538 (Singapore)PDF1333 KB
Europe TUV Nord ATEX Category 3 Zone 2TÜV 14 ATEX 115980 XPDF474 KB
TUV Nord Zone 2IECEx TUN 14.0003XLINK---
Worldwide Fieldbus FoundationIT082700PDF50 KB
Declaration of Conformity
EU Declaration of Conformity / EU-KonformitätserklärungDOC-0596DPDF1041 KB

Associated Products: KT-MB-GT2AD.FF.IO

Matching System Components

System integration kit for Advanced Diagnostics, PCS integration via Diagnostic Manager or device DTM, System integration kit for Advanced Diagnostics, PCS integration via Diagnostic Manager or device DTM, Simple automatic setup of Advanced Diagnostics, Common alarm handling, For FOUNDATION Fieldbus and PROFIBUS PA, International, Europepa
Accessories
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Internet download possiblepa

Function: KT-MB-GT2AD.FF.IO

The FieldConnex ® Diagnostic Gateway is the interface between stationary Advanced Diagnostic Modules (ADM) and the control system. It offers access to all ADM data in two ways: via Ethernet and the Diagnostic Manager software or via FOUNDATION Fieldbus H1 and DTM/EDD or both.

The gateway configures itself and automatically detects the ADMs. The Diagnostic Manager automatically finds gateways on the same subnet. The setup of the diagnostic bus and all connected modules is automatic. This significantly simplifies engineering of FieldConnex ® Advanced Diagnostics.

Inputs for frequency, temperature, humidity, and NAMUR sensors and 2 relay contacts allow control of the control cabinet. The cabinet and physical layer diagnostics become easy-to-manage plant assets.

Ethernet-APL enables continuous communication across all hierarchy levels. Learn more about the pioneering technology …

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

From decisions to planning, installation, and commissioning up to operation and maintenance: Discover how to make the most out of your fieldbus infrastructure …

The Quick Select Product Guide for interface technology, FieldConnex®, and remote I/O connection technologies will help you select the right technology and systems when designing plants.