General specifications | ||
---|---|---|
Design / Mounting | Motherboard based | |
Supply | ||
Rated voltage | 19.2 ... 35 V DC SELV/PELV | |
Rated current | 210 ... 120 mA | |
Power dissipation | max. 4.2 W | |
Fieldbus connection | ||
Fieldbus type | FOUNDATION Fieldbus | |
Physical layer profile | profile type 114 | |
ITK version | 6 | |
Implementation | resource block function block transducer block |
|
Firmware update | Ethernet | |
Polarity | polarity-sensitive | |
Rated voltage | 9 ... 35 V SELV/PELV | |
Rated current | 0 mA | |
Connection to power link | ||
Connection | ||
Ethernet Interface | ||
Rated voltage | max. 35 V SELV/PELV | |
Port | 100 BASE-TX | |
Protocol | TCP/IP and UDP/IP | |
Services | ICMP , DHCP , AutoIP , HTTP | |
Connection type | RJ-45 socket, 8-pin | |
Transfer rate | 100 MBit/s | |
Diagnostic Bus | ||
Connection | only for the connection to protected circuits | |
Rated voltage | max. 35 V | |
Number of Diagnostic Bus Channels | 2 | |
Number of Diagnostic Modules/Channel | 31 Using Ethernet Interface , 8 Using Fieldbus Interface | |
Termination | integrated | |
Cable length/Channel | 30 m | |
Indicators/operating means | ||
LED ERR | red: Hardware fault | |
LED PWR | green: Power on | |
Fault signal | buzzer on | |
LINK/ACT | yellow | |
CH1, CH2 | yellow: diagnostic bus activity | |
Inputs | ||
Input I, II | ||
Input type | selectable: Frequency input , NAMUR/mechanical contact | |
Frequency | ||
Connection | only passive load | |
Rated voltage | max. 35 V | |
Input frequency | 0.3 Hz to 1 kHz | |
Pulse duration | min. 50 µs | |
Accuracy | ± 1 % | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short-circuit | |
NAMUR | ||
Sensor type | NAMUR sensor according to IEC/EN 60947-5-6 | |
Connection | only passive load | |
Rated voltage | max. 35 V | |
Switching frequency | 10 Hz | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short circuit | |
Input III, IV | ||
Input type | NAMUR/mechanical contact | |
NAMUR | ||
Sensor type | NAMUR sensor according to IEC/EN 60947-5-6 | |
Connection | only passive load | |
Rated voltage | max. 35 V | |
Switching frequency | 10 Hz | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short circuit | |
Input V | ||
Input type | selectable: diagnostic bus CH 1 alarm input , NAMUR/mechanical contact | |
Alarm Input | ||
Connection | only passive load | |
Rated voltage | max. 35 V | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short circuit | |
NAMUR | ||
Sensor type | NAMUR sensor according to IEC/EN 60947-5-6 | |
Connection | only passive load | |
Rated voltage | max. 35 V | |
Switching frequency | 10 Hz | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short circuit | |
Input VI | ||
Input type | selectable: diagnostic bus CH 2 alarm input , NAMUR/mechanical contact | |
Alarm Input | ||
Connection | only passive load | |
Rated voltage | max. 35 V | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short-circuit | |
NAMUR | ||
Sensor type | NAMUR sensor according to IEC/EN 60947-5-6 | |
Connection | only passive load | |
Rated voltage | max. 35 V | |
Switching frequency | 10 Hz | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short circuit | |
Input VII, VIII | ||
Input type | selectable: Pt100 4-wire temperature input , NAMUR/mechanical contact | |
Temperature | ||
Connection | only passive load | |
Rated voltage | max. 35 V | |
Measurement range | -50 ... 90 °C (-58 ... 194 °F) | |
Accuracy | 1 K | |
Measuring current | 1 mA | |
Lead resistance | 4.2 Ω per line | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short-circuit | |
NAMUR | ||
Sensor type | NAMUR sensor according to IEC/EN 60947-5-6 | |
Connection | only passive load | |
Rated voltage | max. 35 V | |
Switching frequency | 10 Hz | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short circuit | |
Humidity | ||
Measurement range | 0 ... 95 % RH | |
Accuracy | 2 % RH | |
Resolution | 0.04 % | |
Outputs | ||
Output I | ||
Output type | selectable: diagnostic bus CH 1 , relay , NO contact | |
Contact loading | 250 V AC/ 6 A resistive load | |
Mechanical life | 1 x 105 switching cycles | |
Response time | turn-on time 7 ms , turn-off time 3 ms | |
Switching frequency | 6 min-1 full load, 1200 min-1 without load | |
Output II | ||
Output type | selectable: diagnostic bus CH 2 , relay , NO contact | |
Contact loading | 250 V AC/ 6 A resistive load | |
Mechanical life | 1 x 105 switching cycles | |
Response time | turn-on time 7 ms , turn-off time 3 ms | |
Switching frequency | 6 min-1 full load, 1200 min-1 without load | |
Output III | ||
Output type | selectable: common alarm , volt-free contact , NC contact | |
Connection | only for the connection to protected circuits | |
Voltage | 50 V DC | |
Current | max. 1 A | |
Output IV | ||
Output type | common alarm , buzzer | |
Galvanic isolation | ||
All circuits/FE | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Output I, II/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 250 Veff | |
Ethernet/Supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Ethernet/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Fieldbus/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Diagnostic Bus/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Low voltage | ||
Directive 73/23/EEC | EN 61010-1:2010 | |
Standard conformity | ||
Galvanic isolation | IEC 62103 | |
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Climatic conditions | DIN IEC 721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ethernet | IEEE 802.3 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) hazardous area -40 ... 70 °C (-40 ... 158 °F) safe area horizontal DIN rail mounting |
|
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 95 % non-condensing | |
Shock resistance | 5 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Pollution degree | max. 2, according to IEC 60664 | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Housing material | Polycarbonate | |
Housing width | see dimensions | |
Housing height | see dimensions | |
Housing depth | see dimensions | |
Degree of protection | IP20 | |
Mass | 500 g | |
Mounting | DIN rail mounting | |
Data for application in connection with hazardous areas | ||
FOUNDATION Fieldbus | ||
Connection | For connection to circuits with safe limited voltage according to IEC 60079-11:2011, type of protection "ic" | |
Voltage | max. 35 V | |
Certificate | TÜV 14 ATEX 115980 X | |
Marking | Motherboard MB-FB-GT.AD.FF.IO ![]() ![]() |
|
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx TUN 14.0003X | |
Approved for | Motherboard Ex nA nC IIC T4 Gc , Gateway Ex nA IIC T4 Gc | |
General information | ||
Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 11.0 | 27242692 |
ECLASS 10.0.1 | 27242692 |
ECLASS 9.0 | 27242692 |
ECLASS 8.0 | 27242692 |
ECLASS 5.1 | 27242692 |
ETIM 8.0 | EC001604 |
ETIM 7.0 | EC001604 |
ETIM 6.0 | EC001604 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
Manuals | Language | File Type | File Size |
---|---|---|---|
Manual Diagnostic Manager | ENG | 25397 KB | |
Instruction manuals | |||
Инструкции | BUL | 233 KB | |
Instruction manual / Betriebsanleitung | CHS | 326 KB | |
Návod k poużití | CZE | 225 KB | |
Instruktions manual | DAN | 224 KB | |
Instruction manual | ENG | 230 KB | |
Kasutusjuhend | EST | 221 KB | |
Käyttöohje | FIN | 220 KB | |
Manuel d'instructions | FRA | 228 KB | |
Betriebsanleitung | GER | 230 KB | |
Οδηγίες χρήσης | GRE | 234 KB | |
Handleiding | HOL | 225 KB | |
Instruction manual / Betriebsanleitung | HRV | 224 KB | |
Használati útmutató | HUN | 226 KB | |
Manuale di istruzioni | ITA | 225 KB | |
Lietošanas pamācība | LAV | 224 KB | |
Instrukciju vadovas | LIT | 226 KB | |
Instrukcja obsługi | POL | 228 KB | |
Manual de instruções | POR | 227 KB | |
Manual de utilizare | RON | 226 KB | |
Návod na poużitie | SLK | 226 KB | |
Navodila za uporabo | SLV | 224 KB | |
Manual de instrucciones | SPA | 228 KB | |
Manual | SWE | 222 KB | |
Short instructions, safety information | |||
Quick Start Guide Diagnostic Manager | ENG | 1520 KB | |
Documents | |||
End-user software license agreement (EULA) | ENG | 37 KB |
Certificates | Certificate No. | File Type | File Size |
---|---|---|---|
China SITIIAS CCC Ex Certificate | 2020322310003538 (Singapore) | 1333 KB | |
Europe TUV Nord ATEX Category 3 Zone 2 | TÜV 14 ATEX 115980 X | 474 KB | |
TUV Nord Zone 2 | IECEx TUN 14.0003X | LINK | --- |
Worldwide Fieldbus Foundation | IT082700 | 50 KB | |
Declaration of Conformity | |||
EU Declaration of Conformity / EU-Konformitätserklärung | DOC-0596D | 1041 KB |
Software Tools | Release Info | File Type | File Size |
---|---|---|---|
DD/CFF files HD2-GT-2AD.FF.IO / DD/CFF-Dateien HD2-GT-2AD.FF.IO | 0102/010102 | ZIP | 266 KB |
Diagnostic Gateway FF DTM / Diagnostic Gateway FF DTM | 2.2.3.3527 | ZIP | 65378 KB |
Pepperl+Fuchs Discovery and Configuration Tool (PFDCT) / Pepperl+Fuchs Discovery and Configuration Tool (PFDCT) | 2.3.0.273 | ZIP | 4728 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
Accessories | ||||||
|
||||||
|
The FieldConnex ® Diagnostic Gateway is the interface between stationary Advanced Diagnostic Modules (ADM) and the control system. It offers access to all ADM data in two ways: via Ethernet and the Diagnostic Manager software or via FOUNDATION Fieldbus H1 and DTM/EDD or both.
The gateway configures itself and automatically detects the ADMs. The Diagnostic Manager automatically finds gateways on the same subnet. The setup of the diagnostic bus and all connected modules is automatic. This significantly simplifies engineering of FieldConnex ® Advanced Diagnostics.
Inputs for frequency, temperature, humidity, and NAMUR sensors and 2 relay contacts allow control of the control cabinet. The cabinet and physical layer diagnostics become easy-to-manage plant assets.