Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description | ||
---|---|---|
Control Units Ex e, Glass Fiber Reinforced Polyester (GRP) |
Electrical specifications | ||
---|---|---|
Operating voltage | 250 V max. | |
Operating current | 16 A max. | |
Terminal capacity | 2.5 mm2 | |
Terminal torque | 0.8 Nm | |
Function | see data table | |
Mechanical specifications | ||
Enclosure range | LCP | |
Enclosure cover | fully detachable | |
Cover fixing | stainless steel socket cap head screws | |
Screws | M6 | |
Number | 4 | |
Tightening torque | 2 Nm | |
Degree of protection | IP66 | |
Cable entry | cable glands as per specification | |
Number of cable entries | see data table |
|
Defined entry area | face A and face B | |
Material | ||
Enclosure | carbon loaded, antistatic glass fiber reinforced polyester (GRP) | |
Finish | inherent color black | |
Seal | one piece closed cell silicone | |
Mass | see data table | |
Dimensions | see data table | |
Tightening torque | ||
Nut torque at enclosure (SW1) | see datasheets of cable glands | |
Mounting | see data table | |
Grounding | 2.5 mm2 grounding terminal | |
Ambient conditions | ||
Ambient temperature | -40 ... 55 °C (-40 ... 131 °F) -50 °C (-58 °F) on request |
|
Data for application in connection with hazardous areas | ||
EU-type examination certificate | CML 16 ATEX 3009X | |
Marking | ![]() Ex db eb mb IIC T* Gb Ex ib IIC T* Gb Ex db eb ib mb IIC T* Gb Ex tb IIIC T** °C Db T6/T80 °C @ Ta +40 °C T4/T130 °C @ Ta +55 °C |
|
International approvals | ||
IECEx approval | IECEx CML 16.0008X | |
EAC approval | RU C-DE.BH02.B.00016/18 | |
IA approval | MASC S/18-0003X | |
CCC approval | 2020322304002545 | |
Conformity | ||
Degree of protection | EN 60529 | |
Usage category | IEC / EN 60947 | |
CE marking | 0080 or 0102, see type label | |
General information | ||
Ordering information | For standard configured units please see pdf data sheet. For configuration details please contact Customer Service. | |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
Accessories | ||
Optional accessories | engraved traffolyte tag label engraved AISI 316L stainless steel tag label color in-fill stainless steel tag label |
|
Indicators/operating means | ||
Control elements | small footprint max. 4 see data table all NC contacts have a direct opening action for emergency stop functions |
System | Classcode |
---|---|
ECLASS 11.0 | 27144052 |
ECLASS 10.0.1 | 27144052 |
ECLASS 9.0 | 27144052 |
ECLASS 8.0 | 27144052 |
ECLASS 5.1 | 27371228 |
ETIM 8.0 | EC000522 |
ETIM 7.0 | EC000522 |
ETIM 6.0 | EC000522 |
ETIM 5.0 | EC000522 |
UNSPSC 12.1 | 39121314 |
Short instructions, safety information | Language | File Type | File Size |
---|---|---|---|
Brief Instructions Control Units Series LCP* / LCS* (notified body: CML) | ENG | 131 KB | |
Kurzanleitung Befehls- und Meldegeräte Serie LCP* / LCS* (notifizierte Stelle: CML) | GER | 136 KB | |
Brief Instructions Control Units Series LCP* / LCS* (notified body: CML) | RUS | 828 KB |
Statements of compliance | Certificate No. | File Type | File Size |
---|---|---|---|
EU-Declaration of Conformity / EU-Konformitätserklärung | DOC-3243A | 87 KB | |
Certificates | |||
CCC Ex Certificate | 2020322304002545(Pepperl+Fuchs SE,Mannheim) | 2520 KB | |
CML IECEx Certificate of Conformity | IECEx CML 16.0008X | LINK | --- |
Europe CML ATEX | CML 16ATEX3009X | 431 KB | |
Russia | RU C-DE.BH02.B.00574/20 | 2823 KB | |
Sira IECEx Certificate of Conformity | IECEx SIR 13.0021X | LINK | --- |
The versatile control units of the LCP series are available as standard off-the-shelf control units or can be flexibly equipped with a great variety of operators, labels, cable glands and accessories. The comprehensive range of control functions allow the configuration of each control unit to exactly meet any application requirements and ensure optimal space efficiency.
The enclosures are manufactured from glass fiber reinforced polyester.
Durable materials and components of high quality allow the control units to be used in harsh ambient conditions.