Serviceline Industrial Sensors
Serviceline Explosion Protection

Universal Input/Output (HART) LB7004A

LB7004A
  • 4-channel
  • Analog input, digital input,
    analog output, digital output
  • Installation in Zone 2 or safe area
  • Supply circuit 21.5 V (4 mA)
  • HART communication via field bus or service bus
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD): one LED per channel
  • Permanently self-monitoring
  • Module can be exchanged under voltage

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  LB7004A

Slots
Occupied slots1
Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies LB9***
Power dissipation2.15 W
Power consumption3.3 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
Analog input
Number of channels4
Suitable field devices
Field devicepressure converter
Field device [2]flow converter
Field device [3]level converter
Field device [4]Temperature Converter
Field device interface
Connection2-wire transmitter
Connectionterminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Transmitter supply voltagemin. 15 V at 20 mA ; 21.5 V at 4 mA
Input resistance15 Ω
Line fault detectioncan be switched on/off for each channel via configuration tool , configurable via configuration tool
Short-circuitfactory setting: > 21 mA Can be parameterized in the range 0 ... 22 mA
Open-circuitfactory setting: < 3.6 mA Can be parameterized in the range 0 ... 22 mA
HART communicationyes
HART secondary variableyes
Analog output
Number of channels4
Suitable field devices
Field deviceProportional Valve
Field device [2]I/P converters
Field device [3]on-site display
Connectionterminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Line fault detectioncan be switched on/off for each channel via configuration tool , configurable via configuration tool
Short-circuitfactory setting: < 50 Ω configurable between 0 ... 26 mA
Open-circuitdeviation of preset output value > 0.5 mA
Load750 Ω max.
HART communicationyes
HART secondary variableyes
Watchdogoutput off 0.5 s after serious fault
Digital input
Number of channels4
Sensor interface
Connection [2]volt-free contact
Connectionterminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Digital signals (active)
Switching point: ON> 2.1 mA
Switching point: OFF< 1.2 mA
Line fault detectioncan be switched on/off for each channel via configuration tool
Connectionmechanical switch with additional resistors (see connection diagram)
Short-circuit> 7 mA
Open-circuit< 0.1 mA
Digital output
Number of channels4
Suitable field devices
Field deviceSolenoid Valve
Field device [2]audible alarm
Field device [3]visual alarm
Connectionterminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8-
Drive capability12 V / 22 mA
Open loop voltagemin. 22.7 V
Current limit22 mA
Internal resistor385 Ω
Line fault detectioncan be switched on/off for each channel via configuration tool
Test current0.4 mA
Short-circuit< 50 Ω
Open-circuit< 0.2 mA
Transfer characteristics
Deviation
After calibration0.1 % of the signal range at 20 °C (68 °F)
Influence of ambient temperature0.01 %/K of the signal range
Refresh timeapprox. 100 ms (4 channels)
Indicators/settings
LED indicationPower LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1-4) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1)
Configuration LED (AI, AO, DI, DO) white: selected channel mode
Codingoptional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2006
Conformity
Electromagnetic compatibilityNE 21:2007
Degree of protectionIEC 60529:2000
Environmental testEN 60068-2-14:2009
Shock resistanceEN 60068-2-27:2009
Vibration resistanceEN 60068-2-6:2008
Damaging gasEN 60068-2-42:2003
Relative humidityEN 60068-2-78:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 (module) , mounted on backplane
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Massapprox. 100 g
Dimensions16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Data for application in connection with hazardous areas
CertificateBVS 12 ATEX E 115 X
MarkingEx-Hexagon II 3 G Ex nA [ic] IIC T4 Gc
Galvanic isolation
Rated voltage250 V field circuits to control and supply circuits
Input/power supply, internal bussafe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Output/power supply, internal bussafe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2009
EN 60079-11:2007
EN 60079-15:2010
International approvals
ATEX approvalBVS 12 ATEX E 115 X
IECEx approvalBVS 11.0068X
Approved forEx nAc [ic] IIC T4
Marine approval
Lloyd Register15/20021
Bureau Veritas Marine22449/B0 BV
General information
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Documents: LB7004A

ManualsLanguageFile TypeFile Size
Functional Safety ManualENGPDF974 KB
Manual LB HardwareENGPDF6465 KB
Handbuch Funktionale SicherheitGERPDF978 KB
Handbuch LB-HardwareGERPDF3892 KB
Instruction manuals
ИнструкцииBULPDF145 KB
Návod k poużitíCZEPDF0 KB
Instruktions manualDANPDF139 KB
Instruction manualENGPDF65 KB
KasutusjuhendESTPDF134 KB
KäyttöohjeFINPDF134 KB
Manuel d'instructionsFRAPDF82 KB
BetriebsanleitungGERPDF67 KB
Οδηγίες χρήσηςGREPDF151 KB
HandleidingHOLPDF0 KB
Instruction manual / BetriebsanleitungHRVPDF138 KB
Használati útmutatóHUNPDF141 KB
Manuale di istruzioniITAPDF79 KB
Lietošanas pamācībaLAVPDF137 KB
Instrukciju vadovasLITPDF139 KB
Instrukcja obsługiPOLPDF142 KB
Manual de instruçõesPORPDF0 KB
Manual de utilizareRONPDF0 KB
Návod na poużitieSLKPDF140 KB
Navodila za uporaboSLVPDF137 KB
Manual de instruccionesSPAPDF80 KB
ManualSWEPDF137 KB

Approvals+Certificates: LB7004A

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-1038BPDF233 KB
Certificates
Bureau Veritas (Maritime) Marine22449/B0 BVPDF287 KB
DEKRA EXAM IECEx ia IECEx nAIECEx BVS 11.0068XLINK---
EAC NANIO "CCVE" EAC TP TC 012/2011RU C-DE.AA87.B.01017PDF5859 KB
Europe DEKRA EXAM II 3 G ATEXBVS 12 ATEX E 115 XPDF2587 KB
Lloyd's Register Marine15/20021PDF2013 KB
Worldwide Pepperl+FuchsCERT-4551PDF300 KB

Function: LB7004A

The device is a configurable universal module. Each channel can operate in the following modes:
- As an analog input (AI) it feeds 2-wire transmitters.
- As an analog output (AO) it can drive proportional valves, I/P converters, or local indicators.
- As a digital input (DI) it reads dry contacts.
- As a digital output (DO) it can drive solenoids, sounders, or LED.
A combination of analog and digital I/O is possible.

Channel LEDs indicate the status of each channel. White LEDs indicate whether AI, AO, DI, DO are selected.

The signals are galvanically isolated from the bus and the power supply.

PROFINET Gateway

The new, Zone 2, Class I/Div. 2 certified remote I/O PROFINET gateway from Pepperl+Fuchs opens the door for Industry 4.0 applications in process industries.