Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Supply | ||
---|---|---|
Rated voltage | 3.6 V DC , battery operated | |
Power dissipation/power consumption | < 0.09 W | |
Input | ||
Connection | terminals 1, 2, 3, 4 | |
RTD | type Pt100, Pt1000 (IEC 751: 1995; GOST: alpha = 0.391) | |
Connection | 2-wire: 2 sensors, 3- or 4-wire: 1 sensor | |
Lead resistance | max. 10 Ω | |
Measurement loop monitoring | sensor breakage | |
Thermocouples | type E, J, K, T (IEC 584-1) | |
Cold junction compensation | internal , external | |
Measurement loop monitoring | sensor breakage | |
Measurement range | type K: -270 ... 1370 °C type T: -270 ... 400 °C type E: -270 ... 1000 °C type J: -210 ... 1200 °C |
|
Resistor | ||
Measurement range | 0 ... 500 Ω , 0 ... 4000 Ω | |
Voltage | mV Input | |
Measurement range | -100 ... 100 mV , 0 ... 300 mV | |
Input resistance | ≥ 1 MΩ | |
Output | ||
Interface | internal antenna | |
Output variables | PV: input 1 (°C, Ω, mV) SV: input 2 (°C, Ω, mV) TV: CJC temperature (°C) estimated battery life (days) battery voltage (volts) residual battery capacity (%) |
|
Communication | WirelessHART specifications - physical layer: IEEE 802.15.4.2006 - frequency band: 2.4 GHz (ISM band, licence free) - transmission rate: 250 kBit/s - maximum transmit power: +10 dBm (EIRP) - transmission range: outdoor 250 m, indoor 50 m (under reference conditions) - communication standard: WirelessHART |
|
Transfer characteristics | ||
Temperature measuring range | sensor type: - TC type E: -200 ... 1000 °C, accuracy ± 0,5 °C - TC type J: -200 ... 750 °C, accuracy ± 1 °C - TC type T: -200 ... 400 °C, accuracy ± 1 °C - TC type K: -140 ... 1300 °C, accuracy ± 1 °C - RTD type Pt100: -200 ... 850 °C, accuracy ± 0,5 °C - 100 mV, accuracy ± 20 µV - 300 mV, accuracy ± 40 µV |
|
Accuracy | - internal cold junction compensation error ± 1,5 °C (typ. acc. to IEC 61298-3) - external cold junction compensation error ± 1 °C (typ.) - resolution error < 0.1 °C - accuracy TC ± 20 µV - accuracy RTD: ± 100 mΩ |
|
Indicators/settings | ||
Display elements | LED PWR (battery status), one green LED LED COM (communication status), one yellow LED LED FLT (fault signal), one red LED |
|
Control elements | 2 push buttons: - power On/Off - Join Trigger - Device Status Trigger - 2-wire RTD Wire Compensation - battery replacement confirmation |
|
Configuration | wired interface: - HART 7.1, FSK compatible - transmission rate: 1200 Bit/s - used for device commissioning with an handheld terminal or a configuration tool (DTM) |
|
Parameter assignment | - sampling period: 1, 2, 5, 10, 30 seconds or 1, 2, 5, 10, 30, 60 minutes - transmit power: configurable 0 dBm or 10 dBm (EIRP) - sensor type - mapping of input measuring values 1 and 2 into primary variable (PV) and secondary variable (SV) - publishing of up to three messages from the device, transmission rate selectable from 4 seconds to 60 minutes |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 99/5/EC | ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 , FCC ID: SJC-M2140 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Accuracy | IEC 61298-3 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Relative humidity | 5 ... 95 %, noncondensing | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 |
|
Mechanical specifications | ||
Degree of protection | IP65 | |
Mass | approx. 1000 g | |
Dimensions | 77 x 129 x 177 mm (3 x 5.08 x 6.97 inch) | |
Height | 177 mm | |
Width | 129 mm | |
Depth | 77 mm | |
Mounting | panel or pole mounting | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | IMQ 09 ATEX 008X | |
Marking | II 2(1)G Ex ia [ia] IIC T4 | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007 | |
International approvals | ||
FM approval | CoC 3042534 | |
IECEx approval | IECEx INE 09.0025X | |
Approved for | Ex ia IIC T4 | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
Accessories | ||
Designation | battery W-BAT-B1-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-F7MK External cold junction compensation W-ACC-CJC |
System | Classcode |
---|---|
ECLASS 13.0 | 27210129 |
ECLASS 12.0 | 27210129 |
ECLASS 11.0 | 27210129 |
ECLASS 10.0.1 | 27210129 |
ECLASS 9.0 | 27210129 |
ECLASS 8.0 | 27210190 |
ECLASS 5.1 | 27242692 |
ETIM 9.0 | EC002919 |
ETIM 8.0 | EC002919 |
ETIM 7.0 | EC002919 |
ETIM 6.0 | EC002919 |
ETIM 5.0 | EC001596 |
UNSPSC 12.1 | 39121008 |
The device is designed to connect RTDs or thermocouples from the hazardous area and provide the according temperature values into a WirelessHART network.
It has an internal cold junction compensation for thermocouples.
A fault is indicated by a red flashing LED per NAMUR NE44.
The unit is easily configurable with a configuration tool (DTM).
For additional information, refer to the manual and www.pepperl-fuchs.com.
System Descriptions | Language | File Type | File Size |
---|---|---|---|
Patent Information | ENG | 365 KB | |
Brief Instructions | |||
Brief Instructions - WirelessHART Network | ENG | 2045 KB | |
Operating instructions WHA-UT-F7B1-0-PP-Z1-Ex2 / Betriebsanleitung WHA-UT-F7B1-0-PP-Z1-Ex2 | ALL | 90 KB | |
Safety and Security Documentation | |||
Instruction manual | ENG | 65 KB | |
Manuals | |||
Manual WirelessHART Temperature Converter WHA-UT-F7B1-0-PP-Z1-Ex2 | ENG | 1413 KB | |
Software Information | |||
Software Release Notes WHA-UT | ENG | 42 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 2-D / CAD 2-D | ALL | ZIP | 568 KB |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
Europe IMQ ATEX Category 2 (1) | IMQ 09 ATEX 008X | ALL | 425 KB | |
INERIS IECEx Certificate of Conformity | IECEx INE 09.0025X | ALL | LINK | --- |
India Radio Approval | ETA 2192/2012/WRLO | ALL | 513 KB | |
Japan CETECOM ICT Radio / Connection | 202-LSA064 / D 12-0051 202 | ALL | 181 KB | |
Korea Radio Approval | KCC-RRM-PFG-WHA-UT | ALL | 728 KB | |
Singapore IMDA Radio Approval | N2698-20 | ALL | 55 KB | |
South Africa MASC | MASC S/22-8642X | ALL | 484 KB | |
USA FM | CoC 3042534 | ALL | 171 KB |
Device Description Files/Drivers | Release Info | File Type | File Size |
---|---|---|---|
DTM Collection WirelessHART V1.0.2.4 / DTM Collection WirelessHART V1.0.2.4 | ZIP | 22259 KB | |
DD Collection for WirelessHART / DD Collection für WirelessHART | ZIP | 3114 KB |