Base Backplane LB9026BP16210.1

LB9026BP16210.1
  • Backplane for LB-System
  • For PROFIBUS DP, PROFIBUS DP V1, PROFINET, and MODBUS RTU
  • Max. 16 slots for I/O modules
  • Mounting in Zone 2, Class I/Div.2 or in the safe area

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of LB9026BP16210.1

General specifications
Suitable componentsExtension Backplane LB9027BP16200.1
Bus Coupler LB8106* , LB8107* , LB8108* , LB8109* , LB8122*
Slots
Bus coupler1
Supply2
I/O modules (single width)max. 16
I/O modules (dual width)max. 8
Supply
Maximum safe voltage Um60 V DC (SELV/PELV)
Input voltage range18 ... 32 V DC (SELV/PELV)
Redundancyno
Fieldbus interface
Fieldbus typePROFIBUS DP/DP-V1, PROFINET or MODBUS RTU , depends on bus coupler
Redundancyno
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2006
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionEN 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20
Massapprox. 1370 g
Dimensions(W x H x D)
440 x 127 x 80 mm (17.3 x 5 x 3.15 inch) , without modules
Data for application in connection with hazardous areas
CertificateBVS 16 ATEX E 089 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2009
EN 60079-15:2010
International approvals
UL approvalE106378
Control drawing116-0321
Approved forcUL (Canada): CL I Zn. 2 IIC; IS circuits for CL I Zn. 0 IIC
ULus (USA): CL I Div. 2 Grp. A, B, C, D; IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G
IECEx approvalIECEx BVS 16.0047X
Approved forEx nA IIC T4 Gc
Marine approval
Bureau Veritas Marine22449/B0 BV
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Documents: LB9026BP16210.1

ManualsLanguageFile TypeFile Size
Manual LB HardwareENGPDF3826 KB
Handbuch LB-HardwareGERPDF3830 KB
Instructions, short instructions, safety information
ИнструкцииBULPDF132 KB
Návod k poużitíCZEPDF129 KB
Instruktions manualDANPDF129 KB
Instruction manualENGPDF135 KB
KasutusjuhendESTPDF125 KB
KäyttöohjeFINPDF125 KB
Manuel d'instructionsFRAPDF132 KB
BetriebsanleitungGERPDF137 KB
Οδηγίες χρήσηςGREPDF140 KB
HandleidingHOLPDF130 KB
Instruction manual / BetriebsanleitungHRVPDF125 KB
Használati útmutatóHUNPDF128 KB
Manuale di istruzioniITAPDF129 KB
Lietošanas pamācībaLAVPDF128 KB
Instrukciju vadovasLITPDF129 KB
Instrukcja obsługiPOLPDF133 KB
Manual de instruçõesPORPDF129 KB
Manual de utilizareRONPDF129 KB
Návod na poużitieSLKPDF129 KB
Navodila za uporaboSLVPDF127 KB
Manual de instruccionesSPAPDF130 KB
ManualSWEPDF127 KB

Approvals+Certificates: LB9026BP16210.1

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of Conformity / EU-KonformitätserklärungDOC-3127BPDF233 KB
Certificates
Bureau Veritas (Maritime) Marine22449/B0 BVPDF287 KB
Canada UL cULE106378 cUL (QUZW7)LINK---
DEKRA EXAM IECEx Certificate of ConformityIECEx BVS 16.0047XLINK---
Europe DEKRA EXAM ATEX Category 3 GBVS 16 ATEX E 089 XPDF1360 KB
Lloyd's Register Marine15/20021PDF2013 KB
USA ULE106378 UL (QUZW)LINK---
Control drawings
Control Drawing UL, cUL / Control Drawing UL, cUL   PDF40 KB

Associated Products: LB9026BP16210.1

Matching system components

Backplane for LB-System, Fieldbus type determined by base backplane, Max. 24 slots for I/O modules, 5 SIL 2 output shutdown segmentspa