Serviceline Industrial Sensors
Serviceline Explosion Protection

Trip amplifier S1SD-1AI-1R

S1SD-1AI-1R
  • 1-channel signal conditioner
  • 24 V DC supply
  • Input bipolar current and voltage sources
  • Relay contact output
  • Accuracy 0.1 %
  • Restart inhibit
  • Configurable by DIP switches and software
  • Connection via screw terminals

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  S1SD-1AI-1R

General specifications
Signal typeAnalog input
Supply
ConnectionPower Bus or terminals 1-, 2+
Rated voltage16.8 ... 31.2 V DC
Power dissipation0.6 W
Power consumption0.8 W
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
Transmission rangelinearity range:
unipolar -1 ... 110 %
bipolar -110 ... 110 %
Input I
Connectionterminals 5, 6, 7-
Input signal0/4 ... 20 mA , 0/2 ... 10 mA , ± 10 mA, ± 20 mA , max. 50 mA
Input resistance≤ 25 Ω
Input II
Connectionterminals 7-, 8+
Input signal0/1 ... 5 V , 0/2 ... 10 V , ± 5 V , ± 10 V , max. 30 V
Input resistance> 1 MΩ
Input III
Connectionterminals 5+, 6-
Input signal0/4 ... 20 mA
Available voltage16 V at 20 mA
Open circuit voltage/short-circuit current≤ 22 V / 30 mA
Input IV
Connectionterminals 5, 7
Input typereset restart inhibit
Output
Connection sidecontrol side
Connectionterminals 3, 4:
Outputsignal, relay
Contact loading253 V AC/2 A/cos φ > 0.7; 126.5 V AC/2 A/cos φ > 0.7; 30 V DC/2 A resistive load
Minimum switch current2 mA / 24 V DC
Energized/De-energized delay≤ 20 ms / ≤ 20 ms
Mechanical life107 switching cycles
Collective error messagePower Bus
Transfer characteristics
Accuracymax. 0.1 % of full-scale value
Influence of ambient temperature< 100 ppm/K of full-scale value
Galvanic isolation
Output/power supplysafe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min
Input/Other circuitssafe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min
Indicators/settings
Display elementsLEDs
Control elementsDIP-switch
keys
Configurationvia DIP switches
via keys
via software
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Degree of protectionIEC 60529:2001
Protection against electrical shockEN 61010-1:2010
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Core cross-section0.5 ... 2.5 mm2 (20 ... 14 AWG)
Massapprox. 70 g
Dimensions6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessoriespower feed module S1SD-2PF
adapter with USB interface S-ADP-USB
Power Bus POWERBUS-SETL5.***
Power Bus POWERBUS-SETH5.***
cover for DIN mounting rail POWERBUS-COV.250
end cap POWERBUS-CAP

Documents: S1SD-1AI-1R

ManualsLanguageFile TypeFile Size
Manual Signal Conditioners SC-SystemENGPDF2152 KB
Handbuch Signaltrenner SC-SystemGERPDF2156 KB
Instruction manuals
ИнструкцииBULPDF125 KB
Návod k poużitíCZEPDF121 KB
Instruktions manualDANPDF120 KB
Instruction manualENGPDF126 KB
KasutusjuhendESTPDF0 KB
KäyttöohjeFINPDF117 KB
Manuel d'instructionsFRAPDF121 KB
BetriebsanleitungGERPDF127 KB
Οδηγίες χρήσηςGREPDF129 KB
HandleidingHOLPDF120 KB
Instruction manual / BetriebsanleitungHRVPDF120 KB
Használati útmutatóHUNPDF120 KB
Manuale di istruzioniITAPDF119 KB
Lietošanas pamācībaLAVPDF120 KB
Instrukciju vadovasLITPDF121 KB
Instrukcja obsługiPOLPDF122 KB
Manual de instruçõesPORPDF0 KB
Manual de utilizareRONPDF120 KB
Návod na poużitieSLKPDF121 KB
Navodila za uporaboSLVPDF120 KB
Manual de instruccionesSPAPDF121 KB
ManualSWEPDF119 KB
Product information
Product Information - Signal Conditioners for Industrial AutomationENGPDF1260 KB
Product Overview SC-SystemENGPDF456 KB
Information produit - Conditionneurs de signaux pour zone non dangereuseFRAPDF1001 KB
Product Overview SC-SystemGERPDF488 KB
Produktinformation - Signaltrenner für die industrielle AutomationGERPDF1338 KB
Product information - Signal Conditioners for Nonhazardous AreasHOLPDF1002 KB
Tender texts
Tender text in GAEB formatENGD816 KB
Tender text in TXT formatENGTXT4 KB
Ausschreibungstext im GAEB-FormatGERD816 KB
Ausschreibungstext im TXT-FormatGERTXT4 KB

Approvals+Certificates: S1SD-1AI-1R

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of Conformity / EU-KonformitätserkärungDOC-2695BPDF374 KB
Certificates
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB

Software: S1SD-1AI-1R

Software ToolsRelease InfoFile TypeFile Size
Configuration software for SC-System: SC-Config / Konfigurations Software für SC-System: SC-Config3.4.0ZIP---

Associated Products: S1SD-1AI-1R

Accessories
Interface for Power Bus, Supply current 3 A, LED status indication, Connection via screw terminalspa
Bus carrier with bus PCB for 35 mm DIN mounting rail, height 7.5 mm, Provides DC supply voltage and the bus connection to all equipped SC-System modules, Standard length 250 mm (9.84 inch), simple to customize to application space, Eliminates daisy-chainspa
Bus carrier with bus PCB for 35 mm DIN mounting rail, height 15 mm, Provides DC supply voltage and the bus connection to all equipped SC-System modules, Standard length 250 mm (9.84 inch), simple to customize to application space, Eliminates daisy-chainspa
Cover for DIN mounting rail, Suitable for Power Bus, Standard length 250 mm (9.84 inch), simple to customize to application space, Packaging unit: 5 piecespa
Fixing of the bus carrier with bus PCB in the DIN mounting rail, Termination of DIN mounting rail, Suitable for Power Bus, Packaging unit: 5 pieces left, 5 pieces rightpa
Isolated USB interface cable, Used with SC-System devices, Configurable via PCpa

Function: S1SD-1AI-1R

This signal conditioner provides the galvanic isolation between field circuits and control circuits.

The device supplies 2-wire and 3-wire transmitters

The device has an input for bipolar current and voltage sources.

The device actuates a relay contact output when it reaches the adjusted limit value.

The device is easily configured by the use of DIP switches or software.

The device has an adjustable on delay, an off delay, or an one-shot function for the relay contact output.

The teach-in function can be used to teach in the limit value.

The device can be powered via terminals or Power Bus.

The New SC-System Signal Conditioner Line

Get to know the most compact solution for general-purpose applications!