Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Electrical specifications | ||
Rated voltage | 33 V | |
Rated current | 500 mA | |
Voltage protection level | ||
Line/Line | max. 58 V category C1/C2 8/20µsec max. 50 V category C3 1kV/µsec max. 51 V category B2 10/700µsec max. 55 V category D1 10/350µsec |
|
Line/Earth | max. 1400 V category C1/C2 8/20µsec max. 1100 V category C1/C2 1kV/µsec max. 1000 V category B2 10/700µsec max. 1300 V category D1 10/350µsec |
|
Screen/Shield directly grounded | max. 25 V category C1/C2 8/20µsec max. 20 V category D1 10/350µsec |
|
Screen/Shield indirectly grounded (via GDT) | max. 700 V category C1/C2 8/20µsec max. 600 V category C3 1kV/µsec max. 500 V category B2 10/700µsec max. 600 V category D1 10/350µsec |
|
Reaction time | ||
Line/Line | max. 1 ns | |
Line/Earth | max. 100 ns | |
Screen/Shield-Earth | max. 100 ns | |
Overstressed fault mode | acc. IEC 61643-21 line inoperable mode 3 lines 1 and 2 at 15,5kA (8/20µsec) lines 3 and 4 at 30kA (8/20µsec) | |
Series resistance in line | 1 Ω +/- 5 % | |
Impulse durability | ||
Per line | 1 kA category D1 10/350µsec , 5 kA category C1/C2 8/20µsec |
|
Screen/Shield directly grounded | 5 kA category D1 10/350µsec | |
Screen/Shield indirectly grounded (via GDT) | 4 kA category D1 10/350µsec , 10 kA category C1/C2 8/20µsec |
|
Capacitance | ||
Line/Line | 800 pF | |
Line/Earth | 16 pF | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Climatic conditions | IEC 60721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Surge protection | IEC 61643-21 | |
Ambient conditions | ||
Ambient temperature | -50 ... 80 °C (-58 ... 176 °F) | |
Storage temperature | -50 ... 85 °C (-58 ... 185 °F) | |
Relative humidity | ≤ 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Mechanical specifications | ||
Connection type | screw terminals | |
Core cross-section | flexible wire 2.5 mm2 solid wire max. 4 mm2 | |
Housing material | Polyamide PA 6.6 | |
Degree of protection | IP20 | |
Mass | Protection Module 20 g , base module 40 g | |
Mounting | 35 mm DIN mounting rail | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | KEMA 09 ATEX 0191 X | |
Marking | ![]() |
|
Voltage | 30 V | |
Current | 500 mA | |
Internal capacitance | negligible 0 nF | |
Internal inductance | negligible 0 µH | |
Certificate | KEMA 09 ATEX 0190 X | |
Marking | ![]() ![]() |
|
Voltage | 33 V | |
Current | 500 mA | |
Internal capacitance | negligible 0 nF | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 | |
International approvals | ||
CSA approval | CSA 2437472 | |
Control drawing | 116-0361 | |
Approved for | Class I, Zone 1, AEx/Ex ia IIC T4...T6, Class I, Zone 2, AEx nC IIC T4...T6, Class I, Zone 2, Ex nL IIC T4...T6, Class I, Zone 2, AEx/Ex nA IIC T4...T6 Class I Div. 1, GP A, B, C, D T4...T6, Class I Div. 2, GP A, B, C, D T4...T6, Class I Div. 2, GP A, B, C, D T4...T6 |
|
IECEx approval | IECEx KEM 09.0088X | |
Approved for | Ex ia [ia Ga] IIC T4/T5/T6 Gb , Ex ic IIC T4/T5/T6 Gc , Ex nA IIC T4/T5/T6 Gc |
|
Certificates and approvals | ||
Marine approval | pending | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 11.0 | 27242692 |
ECLASS 10.0.1 | 27242692 |
ECLASS 9.0 | 27242692 |
ECLASS 8.0 | 27242692 |
ECLASS 5.1 | 27242692 |
ETIM 8.0 | EC002584 |
ETIM 7.0 | EC002584 |
ETIM 6.0 | EC002584 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121610 |
Manuals | Language | File Type | File Size |
---|---|---|---|
Manual DP-LBF-I1.36* | ENG | 1134 KB | |
Instruction manuals | |||
Инструкции | BUL | 199 KB | |
Návod k poużití | CZE | 193 KB | |
Instruktions manual | DAN | 0 KB | |
Instruction manual | ENG | 66 KB | |
Kasutusjuhend | EST | 189 KB | |
Käyttöohje | FIN | 0 KB | |
Manuel d'instructions | FRA | 131 KB | |
Betriebsanleitung | GER | 68 KB | |
Οδηγίες χρήσης | GRE | 0 KB | |
Handleiding | HOL | 194 KB | |
Instruction manual / Betriebsanleitung | HRV | 192 KB | |
Használati útmutató | HUN | 194 KB | |
Manuale di istruzioni | ITA | 129 KB | |
Lietošanas pamācība | LAV | 191 KB | |
Instrukciju vadovas | LIT | 192 KB | |
Instrukcja obsługi | POL | 195 KB | |
Manual de instruções | POR | 195 KB | |
Manual de utilizare | RON | 0 KB | |
Návod na poużitie | SLK | 193 KB | |
Navodila za uporabo | SLV | 192 KB | |
Manual de instrucciones | SPA | 131 KB | |
Manual | SWE | 190 KB |
CAD | File Type | File Size | |
---|---|---|---|
Dimension drawing 2-D (DXF) / Abmessungszeichnung 2-D (DXF) | ZIP | 754 KB |
Statements of compliance | Certificate No. | File Type | File Size |
---|---|---|---|
EU-Declaration of conformity / EU-Konformitätserklärung | DOC-0688B | 91 KB | |
Certificates | |||
Canada USA CSA | CoC 2437472 cUs | 49 KB | |
EAC VELES EAC TP TC 012/2011 | EAEC RU C-DE.AD07.B.04575/22 | 2397 KB | |
Europe KEMA ATEX | KEMA 09 ATEX 0191X | 1043 KB | |
Europe KEMA ATEX Category 3 G | KEMA 09 ATEX 0190X | 1022 KB | |
India PESO (India) CCOE | A/P/HQ/KA/104/5815 (P482701) | 78 KB | |
KEMA Ex i and Ex n IECEx Certificate of Conformity | IECEx KEM 09.0088X | LINK | --- |
Control drawings | |||
Control Drawing CSA / Control Drawing CSA | 442 KB |
The modular surge protector for fieldbus consists of a base (DB …), and a plug-in module (DP-LBF-I1.36*) and is in accordance with IEC 61158-2. It directs power surges to earth via gas discharge tubes, protecting field devices. The device is certified intrinsically safe for circuits in hazardous area Zone 0 … 2/Div. 1 … 2, and for DART fieldbus. The surge protector is installed in Zone 1 … 2 or Div. 1 … 2.
Choices support all concepts: interrupting/non-interrupting module exchange and direct/indirect grounding of the shield. The plug-in module can be exchanged without tools.
The surge protectors support coordinated use in a lightning protection zone concept in accordance with IEC 61312-1. Installation in cabinets or junction boxes requires a minimum amount of wiring.