General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Fieldbus connection | ||
Self current consumption | max. 6 mA (for version TCP-LBF-IA1.36.IE.1) , max. 0 mA (for version TCP-LBF-IA1.36.IE.0) | |
Indicators/operating means | ||
LED ERR | green flashing: status OK , red flashing: maintenance required , (for version TCP-LBF-IA1.36.IE.1) | |
Electrical specifications | ||
Rated voltage | 36 V | |
Rated current | 600 mA | |
Voltage protection level | ||
Line/Line | max. 50 V category B2 10/700µsec , 25 A max. 50 V category C1 8/20µsec , 300 A max. 55 V category C2 8/20µsec , 5 kA max. 46 V category C3 1kV/µsec , 10 A |
|
Line/Earth | max. 1060 V category B2 10/700µsec , 50 A per line max. 800 V category C1 8/20µsec , 300 A per line max. 1.5 kV category C2 8/20µsec , 5 kA per line max. 1.3 kV category C3 1kV/µsec , 50 A per line max. 1080 V category D1 10/350µsec , 500 A per line |
|
Screen/Shield indirectly grounded (via GDT) | max. 500 V category B2 10/700µsec , 100 A max. 600 V category C1 8/20µsec , 500 A max. 720 V category C2 8/20µsec , 10 kA max. 550 V category C3 1kV/µsec , 100 A max. 570 V category D1 10/350µsec , 1 kA |
|
Reaction time | ||
Line/Line | max. 1 ns | |
Line/Earth | max. 100 ns | |
Screen/Shield-Earth | max. 100 ns | |
Overstressed fault mode | acc. IEC 61643-21 line inoperable mode 3 | |
Series resistance in line | 2 Ω +/- 5 % | |
Impulse durability | ||
Per line | 5 kA category C2 8/20µsec | |
Screen/Shield indirectly grounded (via GDT) | 1 kA category D1 10/350µsec 10 kA category C2 8/20µsec |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NAMUR NE 21 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Climatic conditions | IEC 60721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Surge protection | IEC 61643-21 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | ≤ 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | screw terminals | |
Core cross-section | flexible wire 2.5 mm2 solid wire max. 4 mm2 | |
Housing material | Polyamide PA 6.6 | |
Degree of protection | IP20 | |
Mass | 80 g | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | SIRA 12 ATEX 2128X | |
Marking | ![]() |
|
Voltage | 24 V | |
Current | 500 mA | |
Internal capacitance | 2 nF | |
Internal inductance | 0.1 µH | |
Certificate | SIRA 12 ATEX 4176X | |
Marking | ![]() ![]() |
|
Voltage | 33 V | |
Current | 600 mA | |
Internal capacitance | 2 nF | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 | |
Supplementary information | FISCO field device | |
International approvals | ||
CSA approval | CoC 2595441 | |
Control drawing | 116-0365 | |
Approved for | Class I, Division 1, Groups A, B, C, D T4 Class I, Zone 0, Ex ia IIC T4 Class I, Zone 2, Ex ic IIC T4 Class I, Zone 0, AEx ia IIC T4 Class I, Zone 2, AEx ic IIC T4 Class I, Division 2, Groups A, B, C, D T4 Class I, Zone 2, Ex nL IIC T4 Class I, Zone 2, Ex na IIC T4 Class I, Zone 2, AEx nAc IIC T4 |
|
IECEx approval | IECEx SIR 12.0051X | |
Approved for | Ex ia IIC T4 | |
Certificates and approvals | ||
Marine approval | DNV A-14038 |
System | Classcode |
---|---|
ECLASS 11.0 | 27242692 |
ECLASS 10.0.1 | 27242692 |
ECLASS 9.0 | 27242692 |
ECLASS 8.0 | 27242692 |
ECLASS 5.1 | 27242692 |
ETIM 8.0 | EC002584 |
ETIM 7.0 | EC002584 |
ETIM 6.0 | EC002584 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121610 |
Manuals | Language | File Type | File Size |
---|---|---|---|
Manual Fieldbus Surge Protector, TPH-LBF-IA1.36* , TCP-LBF-IA1.36* , SCP-LBF-IA1.36* | ENG | 3287 KB | |
Instruction manuals | |||
Инструкции | BUL | 200 KB | |
Návod k poużití | CZE | 0 KB | |
Instruktions manual | DAN | 133 KB | |
Instruction manual | ENG | 65 KB | |
Kasutusjuhend | EST | 188 KB | |
Käyttöohje | FIN | 189 KB | |
Manuel d'instructions | FRA | 135 KB | |
Betriebsanleitung | GER | 67 KB | |
Οδηγίες χρήσης | GRE | 0 KB | |
Handleiding | HOL | 0 KB | |
Instruction manual / Betriebsanleitung | HRV | 192 KB | |
Használati útmutató | HUN | 0 KB | |
Manuale di istruzioni | ITA | 133 KB | |
Lietošanas pamācība | LAV | 193 KB | |
Instrukciju vadovas | LIT | 194 KB | |
Instrukcja obsługi | POL | 0 KB | |
Manual de instruções | POR | 196 KB | |
Manual de utilizare | RON | 195 KB | |
Návod na poużitie | SLK | 195 KB | |
Navodila za uporabo | SLV | 192 KB | |
Manual de instrucciones | SPA | 133 KB | |
Manual | SWE | 191 KB |
CAD | File Type | File Size | |
---|---|---|---|
3-D model / 3-D-Modell | STP | 5495 KB | |
CAD Portal / CAD Portal | LINK | --- | |
Dimension drawing 2-D (DXF) / Abmessungszeichnung 2-D (DXF) | ZIP | 454 KB |
Statements of compliance | Certificate No. | File Type | File Size |
---|---|---|---|
EU-Declaration of conformity / EU-Konformitätserklärung | DOC-0814B | 91 KB | |
Certificates | |||
Brasil TUV Rheinland Brazil | TÜV 14.1589 X | 755 KB | |
Canada, USA CSA Ex i and Ex n | CSA 13.2595441X | 114 KB | |
DNV GL Marine | TAA0000272 | 78 KB | |
EAC Pepperl+Fuchs EAC TP TC 020/2011 | EAEC N RU D-DE.EA11.B.00321 | 1485 KB | |
Europe CSA ATEX Category 1 G | Sira 12 ATEX 2128X | 215 KB | |
Europe Sira II 3 G ATEX Category 3 G | Sira 12 ATEX 4176X | 52 KB | |
India PESO (India) CCOE | A/P/HQ/KA/104/5866 (P506129) | 100 KB | |
Sira IECEx Certificate of Conformity | IECEx SIR 12.0051X | LINK | --- |
Control drawings | |||
Control Drawing CSA / Control Drawing CSA | 92 KB |
Accessory of | ||||||
---|---|---|---|---|---|---|
|
||||||
Matching System Components | ||||||
|
||||||
|
||||||
|
This fieldbus surge protector is in accordance with IEC 61158-2 and mounts on the trunk connector of FieldConnex ® device couplers, protecting them. It directs power surges to earth via gas discharge tubes. It is certified intrinsically safe for circuits in hazardous areas up to Zone 0/Div. 1 and DART fieldbus. The surge protector is installed in Zone 1 … 2 or Div. 1 … 2.
Integrated diagnostics (option) continuously monitor wear caused by surges. The end of the useful life and thus the need for exchange is indicated in two ways: via an LED and in the control room via the FieldConnex ® Advanced Diagnostics software.