Serviceline Industrial Sensors
Serviceline Explosion Protection

Fieldbus Power Conditioner KLD2-PC-1.1.IEC

KLD2-PC-1.1.IEC
  • Output: 14.7 ... 30.7 V/1 A
  • For very high segment load
  • High-power trunk for high device count and long cable lengths
  • Installation only in safe areas
  • For FOUNDATION Fieldbus H1
  • Selectable, high-availability terminator
  • Low heat dissipation
  • Supply via Power Rail

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KLD2-PC-1.1.IEC

Supply
ConnectionPower Rail or terminals 8+, 11+; 9-, 12-
Rated voltage16 ... 32 V DC
Rated current1.02 A
Power dissipation16 ... 32 V at 1 A: ≤ 1.86 W; typ. 1.6 W
Fieldbus interface
Field-side
Connectionterminals 3+, 6+; 2-, 5-; 1S, 4S (S=screen connection)
Rated voltage14.7 ... 30.7 V DC
Rated current1 A
Terminating impedance100 Ω switchable off and on via rotary switch: 1 -> on; 0 -> off
Error message output
ConnectionPower Rail or terminals 7, 10
Rated voltage32 V DC
Rated current10 mA
Voltage drop1.2 V at 10 mA
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Standard conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC/EN 60529
Fieldbus standardIEC 61158-2, ISA S 50.02 part 2
Climatic conditionsDIN IEC 721
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Pollution degreemax. 2, according to IEC 60664
Mechanical specifications
Connection typeTerminals
Core cross-sectionup to 2.5 mm2
Housing20 mm x 115 mm x 107 mm
Degree of protectionIP20
Massapprox. 100 g
MountingDIN rail mounting
International approvals
UL approvalUL E106378, CUL E106378
Approved forClass I, Division 2, Groups A, B, C, D

Documents: KLD2-PC-1.1.IEC

ManualsLanguageFile TypeFile Size
Operating instructions KLD2-PC-1.1.IECUSAPDF2633 KB
Technical information
Bulk Power Supply SpecificationENGPDF115 KB

Approvals+Certificates: KLD2-PC-1.1.IEC

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of Conformity / EU-KonformitätserklärungDOC-3620PDF85 KB
Certificates
Canada UL cULE106378 cUL (QUZW7)LINK---
USA ULE106378 UL (QUZW)LINK---
Worldwide Fieldbus FoundationPS001100PDF158 KB

Associated Products: KLD2-PC-1.1.IEC

Accessories

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa
Alternative power supply, Nominal current 4 A, Simple installation, Standard length 50 cm, can be shortened to any length in 4 cm steps, Terminating insulation by end cap, included in the delivery package, With 2 leads for voltage supply and 1 lead for centralized error messagespa

Function: KLD2-PC-1.1.IEC

The fieldbus power conditioner is an all-in-one module for single fieldbus segments. It provides short-circuit limitation (1 A) and impedance matching only. The output voltage depends on the bulk power voltage.

The device feeds high power to the trunk for maximum cable lengths and high device count in any hazardous area. Fieldbus couplers provide explosion protection for live work at the spur.

Availability and a long service life are achieved through: only one passive impedance filter per segment with CREST for superior signal transmission, optimized design for low power dissipation and high-availability fieldbus termination. Any mounting direction allows optimized and space-saving cabinet layout.