Serviceline Industrial Sensors
Serviceline Explosion Protection

Fieldbus module ICE1-8DI8DO-G60L-V1D

ICE1-8DI8DO-G60L-V1D
  • Multiprotocol-compatible
  • M12 power connector
  • Sturdy metallic housing
  • Web-based configuration

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  ICE1-8DI8DO-G60L-V1D

Product Description
Ethernet IO module with 8 digital inputs/outputs
General specifications
UL File NumberE223772
Indicators/operating means
LED indicationsee manual
Rotary switchSetting the fieldbus protocol
Electrical specifications
Rated operating voltage18 ... 30 V
Nominal voltage24 V DC
Current consumption120 mA
Current loading capacityMax. 2 x 16 A per module
(Loop-through current via L-coded power supply)
Total current: max. 9 A per module
Galvanic isolationbetween US and UL
Interface 1
Interface typeIndustrial Ethernet
Physical M12, D-coded
ProtocolPROFINET IO with media redundancy protocol (MRP)
EtherNet/IP with Device Level Ring (DLR)
EtherCAT
Transfer rate10/100 Mbps
Inputs/Outputs
Number/Type8 digital inputs (X1 – X4), 8 digital outputs (X5 – X8)
Inputs: 2-, 3-, 4-wire PNP, DC, supply from US
Outputs: 2-, 3-, 4-wire, PNP, DC, supply from UL
Short-circuit protected
Sensor supplymax. 200 mA Per port (X1 – X4) via US
Output rated operating currentmax. 2 A per channel (X5 – X8) / 4 A Per port via UL
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011
Standard conformity
Degree of protectionEN 60529:2000
Emitted interferenceEN 61000-6-4:2007+A1:2011
Noise immunityEN 61000-6-2:2005
Shock resistanceEN 61131-2:2004
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Cold start temperature-40 °C (-40 °F)
Relative humiditymax. 95 %
Altitude0 ... 2000 m
Shock and impact resistance50 g, 11 ms, all axes
Vibration resistance15 g at 5 - 500 Hz
Pollution degree3
Mechanical specifications
Contact elementsPA
Degree of protectionIP65/IP67/IP69K
ConnectionPower Supply M12, L-coded
Fieldbus M12, D-coded
Inputs/Outputs M12, A-coded
Material
ContactsCuSn, gold-plated
CuNi, gold-plated
HousingDiecast zinc
SealFKM
Mass500 g
Tightening torque, fastening screws1 Nm
Tightening torque, cable glandmax. 0.5 Nm
Construction typeField housing
Tightening torque of clamping screws0.5 Nm

Documents: ICE1-8DI8DO-G60L-V1D

ManualsLanguageFile TypeFile Size
Manual ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1DENGPDF6805 KB
Handbuch ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1DGERPDF6841 KB
Instruction manuals
Safety reference / SicherheitshinweisALLPDF20 KB

Approvals+Certificates: ICE1-8DI8DO-G60L-V1D

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-3185APDF162 KB
Certificates
ODVA Ethernet/IPFile No. 11612.01PDF69 KB
US CA ULE223772LINK---
WorldwideZ11883PDF298 KB

Software: ICE1-8DI8DO-G60L-V1D

DriversRelease InfoFile TypeFile Size
EtherNet/IP EDS-Files / EtherNet/IP EDS-Dateien04/2019ZIP73 KB
Ethercat configuration File / Ethercat-Konfigurations-Datei03/2018ZIP28 KB
PROFINET GSDML-Files / PROFINET GSDML-Dateien03/2019ZIP66 KB

Associated Products: ICE1-8DI8DO-G60L-V1D

Accessories

Cable connector, M12, 4-pin, D-coded, shielded, non pre-wiredfa

Y distributor, M12 connector on M12 socket/socketfa

Blind plug for M12 socketsfa
Single-ended female cordset, M12, L-coded, 5-pin, PUR cablefa
Cordset, M12 to M12, L-coded, 5-pin, PUR cablefa
Cordset, M12 to M12, L-coded, 5-pin, PUR cablefa
Cordset, M12 to M12, L-coded, 5-pin, PUR cablefa
Connection cable, M12 to RJ-45, PUR cable 4-pin, CAT5efa
Ethernet bus cable, M12 to M12, PUR cable 4-pin, CAT5efa
Y connecting cable, M12 to 2xM12, 4-pin, PUR cablefa
Single-ended female cordset, M12, L-coded, field attachablefa
torque screwdriver (0.6 Nm)fa
plug-in cap M12fa

Function: ICE1-8DI8DO-G60L-V1D

The ICE1-8DI8DO-G60L-V1D is a multiprotocol fieldbus module with 8 digital inputs and 8 digital outputs.

The G60L design in fully cast metal housing is resistant to mechanical damage and environmental influences. The G60L has protection class IP65/IP67.

The fieldbus module serves as an interface between the controller of a fieldbus system and the field level. Thanks to its multiprotocol capability, the fieldbus module supports the Ethernet communication protocols PROFINET, EtherNet/IP, and EtherCAT.

An L-coded M12 connector plug used for supplying power enables a current rating of up to 2 x 16 A. The inputs and outputs are equipped with A-coded M12 connector plugs. Connection to the fieldbus is achieved using a D-coded M12 connector plug.

The communication protocols are configured either manually via a rotary switch or automatically. The diagnostics display status information for each channel via LEDs. An integrated web server enables access to the fieldbus module. Information regarding the status of the module is also displayed and network parameters such as the IP address and subnet mask can be configured.