Serviceline Industrial Sensors
Serviceline Explosion Protection

I/O hub ICA-16DIO-G60AL-IO

ICA-16DIO-G60AL-IO
  • Sturdy metallic housing
  • IO-link interface for service and process data
  • 16 digital inputs/outputs can be configured
  • Logic level can be configured per port
  • Filter time can be configured per port
  • Pulse extension can be configured per port

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  ICA-16DIO-G60AL-IO

Product Description
I/O hub with IO-Link interface for 16 digital inputs/outputs
General specifications
UL File NumberE223772
Functional safety related parameters
MTTFd2111 a
Indicators/operating means
LED UAUX Green: Actuator supply voltage OK
Red: Actuator supply voltage < 18 V
LED IO-LinkGreen: module is switched on, no communication
Flashing green: communication OK
Red: signal line overload
LED AOrange: status indicator channel A
Red: peripheral error
LED BWhite: status indicator channel B
Red: peripheral error
LED USGreen: system/sensor supply voltage OK
Red: system/sensor supply voltage < 18 V
Flashing red: sensor supply voltage overload
Electrical specifications
Rated operating voltage18 ... 30 V
Nominal voltage24 V DC
Nominal current16 A
Current consumptiontyp. 80 mA
Current loading capacitymax. 16 A per module (for UL applications, max. 9 A)
Interface
Interface typeIO-Link
IO-Link revision1.1
Device profileIdentification and Diagnosis - I&D
Device ID0x0F0203 (983555)
Transfer rateCOM3 (230.4 kbits/s)
Min. cycle time2 ms
Process data widthInput 4 Byte
Output 4 Byte
SIO mode supportno
Compatible master port typeA
Inputs/Outputs
Number/Type16 digital inputs/outputs, configurable
Inputs: 2-, 3-, 4-wire PNP, DC, supply from US
Outputs: 2-wire PNP, DC, supply from UL
No galvanic isolation between US and UL
short-circuit protected
Sensor supplymax. 500 mA per port (X1 - X8)
Output currentmax. 2 A per channel (X1 - X8) / 4 A per port
max. 9 A per module
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardType 1 according to IEC 61131-2
Emitted interferenceEN 61000-6-2:2005
Noise immunityEN 61000-6-4:2007+A1:2011
Shock resistanceEN 61131-2:2004
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Relative humiditymax. 95 %
Altitude0 ... 2000 m
Shock and impact resistance50 g, 11 ms, all axes
Vibration resistance15 g / 5 ... 500 Hz
Pollution degree3
Mechanical specifications
Degree of protectionIP65/IP67/IP69K
ConnectionPower Supply M12, L-coded
IO-Link M12, A-coded
Inputs/Outputs M12, A-coded
Material
ContactsCuSn, gold-plated
CuNi, gold-plated
HousingDiecast zinc
Plastic partsPA
SealFKM
Mass400 g
Dimensions
Height200 mm
Width59.6 mm
Length21 mm
Construction typeField housing

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001597
ETIM 8.0EC001597
ETIM 7.0EC001597
ETIM 6.0EC001597
ETIM 5.0EC001597
UNSPSC 12.132151705

Details: ICA-16DIO-G60AL-IO

Product Documentation: ICA-16DIO-G60AL-IO

Language Selection:
Product informationLanguageFile TypeFile Size
Installation and user instructions for offline parameterization of IO-Link sensorsENGPDF1788 KB
Manuals
Manual ICA-16DI-G60A-IO, ICA-10DI6DO-G60A-IO, ICA-16DIO-G60AL-IOENGPDF927 KB

Design / Simulation: ICA-16DIO-G60AL-IO

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP6160 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ70 KB

Approvals: ICA-16DIO-G60AL-IO

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
IO-Link Manufacturer DeclarationCERT-4553BALLPDF161 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-4292AALLPDF214 KB

Software: ICA-16DIO-G60AL-IO

Language Selection:
Device Description Files/DriversRelease InfoFile TypeFile Size
IODD for ICA-16DIO-G60AL*-IO / IODD für ICA-16DIO-G60AL*-IOV1.02.000 / 2021-01-20ZIP146 KB
Software Tools
IO-Link Offline Parameterization Tool / IO-Link Offline-ParametriertoolV1.00.006 / 2022-07-10ZIP96138 KB

Associated Products: ICA-16DIO-G60AL-IO

Accessory of

Ethernet IO-Link module with eight IO-Link portsfa

EtherNet/IP IO-Link master with 8 inputs/outputsfa

PROFINET IO IO-Link master with 8 inputs/outputsfa
PROFINET and Modbus IO-Link master with 4 x IO-Link Class A and 4 x IO-Link Class B portsfa
PROFINET IO IO-Link master with 8 inputs/outputs, DIN rail, push-in terminalsfa
EtherNet/IP IO-Link master with 8 inputs/outputs, DIN rail, push-in connectorsfa
EtherNet/IP IO-Link master with 8 inputs/outputs, DIN rail, screw terminalfa
PROFINET IO IO-Link master with 8 inputs/outputs, DIN rail, screw terminalfa
Ethernet IO-Link master with PROFINET S2 redundancyfa
Ethernet IO-Link module with 8 inputs/outputsfa
EtherNet/IP and Modbus IO-Link master with 4 x IO-Link Class A and 4 x IO-Link Class B portsfa
Ethernet IO-Link module with 8 inputs/outputsfa
Firmware variant from ICE3-8IOL-G65L-V1D with Modbus enabled by defaultfa
Accessories
torque screwdriver (0.6 Nm)fa
plug-in cap M12fa
IO-Link master, supply via USB port or separate power supply, LED indicators, M12 plug for sensor connectionfa
Free Download: White Paper on TCP-Based Communication Protocols (PDF)

This free PDF white paper compares the different TCP-based communication protocols (AMQP, OPC UA, MQTT, REST API) that have found their way up and are considered the enablers of IIoT and Industry 4.0. Get your free download now!