Serviceline Industrial Sensors
Serviceline Explosion Protection

PNIO/MOD Fieldbus module ICE3-8IOL-G65L-V1D

ICE3-8IOL-G65L-V1D
  • Web-based configuration of module and IO-Link devices
  • Integrated IODD storage for more than 100 IODDs
  • Downloadable module configuration
  • M12 L-coded power connector
  • PROFINET IO, Modbus/TCP and OPC UA Support

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  ICE3-8IOL-G65L-V1D

Product Description
PROFINET IO IO-Link master with 8 inputs/outputs
General specifications
UL File NumberE360395
Indicators/operating means
LED indicationsee manual
Rotary switchSetting the IP address
Electrical specifications
Rated operating voltage20 ... 30 V DC
Nominal voltage24 V DC
Current consumptiontyp. 120 mA
Current loading capacityMax. 2 x 16 A per module
(Loop-through current via L-coded power supply)
Total current: max. 6.7 A per module
Galvanic isolationbetween US and UA
Interface 1
Interface typeIndustrial Ethernet
Physical M12, D-coded
ProtocolPROFINET IO + Modbus TCP + OPC UA
Transfer rate10/100 Mbps
Inputs/Outputs
Number/Type8 x IO-Link Class A (X1 – X8)
Configurable as:
Max. 8 IO-Link and 8 digital outputs
Max. 16 digital inputs
Max. 8 digital inputs and 8 digital outputs
short-circuit protected
Sensor supplyPort 1: max. 1.6 A Via L+ (pin 1)
Port 3: max. 1 A via L+ (pin 1)
Ports 2 and 4 – 8: max. 500 mA per port via L+ (pin 1)
Output rated operating currentmax. 200 mA Per port via C/Q (pin 4)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61000-6-2 , EN 61000-6-4
Standard conformity
Degree of protectionEN 60529
Fieldbus standardType 1 according to IEC 61131-2, EN 61131-9
Electrical safetyCSA C22.2 No. 61010-1-12
UL 61010-1, IEC 61010-2-201
Emitted interferenceEN 61000-6-4, FCC Part 15 Subpart B, ICES-001, AS/NZS CISPR 11
Noise immunityEN 61000-6-2 , EN 61131-2 , EN 61131-9
Shock resistanceEN 60068-2-27
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humiditymax. 95 %
Altitude0 ... 2000 m
Shock and impact resistance15g, 11ms, half-sine
Mechanical specifications
Degree of protectionIP67
ConnectionPower Supply M12, L-coded
Fieldbus M12, D-coded
Inputs/Outputs M12, A-coded
Material
HousingMolded Polyamide 66
Mass454 g
Tightening torque, fastening screws8 Nm
Tightening torque, cable glandmax. 0.5 Nm

Documents: ICE3-8IOL-G65L-V1D

ManualsLanguageFile TypeFile Size
ManualENGPDF21210 KB
HandbuchGERPDF14865 KB

CAD+CAE: ICE3-8IOL-G65L-V1D

CADFile TypeFile Size
3-D model in IGS format / 3-D-Modell im IGS-FormatIGS20978 KB
3-D model in STP format / 3-D-Modell im STP-FormatSTP6572 KB

Approvals+Certificates: ICE3-8IOL-G65L-V1D

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-4275BPDF258 KB
Certificates
Canada, USA UL ULE360395LINK---
PNO VZ12476PDF52 KB
Worldwide IO-Link Manufacturer DeclarationCERT-5231APDF56 KB

Software: ICE3-8IOL-G65L-V1D

Software ToolsRelease InfoFile TypeFile Size
PROFINET GSDML Files ICE3 Modules / PROFINET GSDML-Dateien ICE3 Module10/2019ZIP18 KB
PortVision DX v5.02 / PortVision DX v5.022020-03ZIP26026 KB

Associated Products: ICE3-8IOL-G65L-V1D

Accessories

Cable connector, M12, 4-pin, D-coded, shielded, non pre-wiredfa

Blind plug for M12 socketsfa

Y distributor, M12 connector on M12 socket/socketfa
Single-ended female cordset, M12, L-coded, 5-pin, PUR cablefa
Cordset, M12 to M12, L-coded, 5-pin, PUR cablefa
Connection cable, M12 to RJ-45, PUR cable 4-pin, CAT5efa
Ethernet bus cable, M12 to M12, PUR cable 4-pin, CAT5efa
Y connecting cable, M12 to 2xM12, 4-pin, PUR cablefa
Single-ended female cordset, M12, L-coded, field attachablefa
torque screwdriver (0.6 Nm)fa
plug-in cap M12fa
I/O hub with IO-Link interface for 10 digital inputs and 6 digital outputsfa
I/O hub with IO-Link interface for 16 digital inputs/outputsfa

Function: ICE3-8IOL-G65L-V1D

The module is a PROFINET IO fieldbus module with 8 type A IO-Link master ports according to IO-Link standard V1.1.

The fieldbus module serves as an interface between the controller of a PROFINET IO fieldbus system and IO-Link devices in the field level. The integrated web server and IODD interpreter enabling complete configuration of the fieldbus module and attached IO-Link devices without the need for special software tools. Information regarding the status of the module is also displayed and network parameters such as the IP address and subnet mask can be configured. The module is capable of storing all configuration enabling stand-alone usage without a higher-level PLC. MutliLink simultaneously provides data access via different communication protocols like PROFINET IO, Modbus/TCP and OPC UA to multiple controllers. An L-coded M12 connector plug used for supplying power enables a current rating of up to 2 x 16 A.

The inputs and outputs are equipped with A-coded M12 connector plugs. Connection to the fieldbus is achieved using a D-coded M12 connector plug.

Status information for each channel is displayed via LEDs as a diagnostic function.