HiC2025A
  • 1-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Input for 2-wire SMART transmitters and current sources
  • Output for 4 mA ... 20 mA or 1 V ... 5 V
  • Low power dissipation
  • Reduced intrinsically safe parameters
  • Up to SIL 2 acc. to IEC 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HiC2025A

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Rated voltage19 ... 30 V DC bus powered via Termination Board
Ripple≤ 10 %
Rated current≤ 45 mA at 24 V and 20 mA source mode output
Power dissipation≤ 800 mW
Power consumption≤ 1.1 W
Input
Connection sidefield side
ConnectionSL2: 5a(+), 1b(-); 5a(+), 5b(-)
Input signal4 ... 20 mA limited to approx. 26 mA
Voltage dropapprox. 5 V on SL2: 5a(+), 1b(-)
Available voltage≥ 14.7 V at 20 mA
≥ 18 V at 4 mA on SL2: 5a(+), 5b(-)
Output
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-)
Load0 ... 350 Ω (source mode)
Output signal4 ... 20 mA or 1 ... 5 V (on 250 Ω, 0.1 % internal shunt)
4 ... 20 mA (sink mode), operating voltage 10 ... 30 V
Ripple20 mV rms
Transfer characteristics
Deviationat 20 °C (68 °F)
< 0.1 % of full scale, incl. non-linearity and hysteresis (source mode and sink mode 4 ... 20 mA)
≤ ± 0.2 % incl. non-linearity and hysteresis (source mode 1 ... 5 V)
Influence of ambient temperature< 2 µA/K (-20 ... 70 °C (-4 ... 158 °F))
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Settling time≤ 50 ms
Rise time/fall time≤ 10 ms
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Indicators/settings
Display elementsLED
Control elementsDIP-switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012
EN 61326-3-2:2008
For further information see system description.
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2012
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Mountingon Termination Board
Codingpin 2 and 3 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateCESI 06 ATEX 017
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
InputEx ia
Supply
Maximum safe voltage250 V AC (Attention! Um is no rated voltage.)
EquipmentSL2: 5a(+), 5b(-)
Voltage Uo25.2 V
Current Io93 mA
Power Po586 mW
EquipmentSL2: 5a(+), 1b(-)
Voltage Ui30 V
Current Ii128 mA
Voltage Uo1 V
Current Io100 mA
Power Po25 mW
CertificateCESI 19 ATEX 027 X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015
International approvals
FM approval
FM certificateFM 19 US 0122 X , FM 19 CA 0065 X
Control drawing116-0470 (cFMus)
UL approvalE106378
Control drawing116-0458 (cULus)
IECEx approval
IECEx certificateIECEx CES 06.0002X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: HiC2025A

ManualsLanguageFile TypeFile Size
Functional Safety ManualENGPDF521 KB
Manual H-System Isolated Barriers and Termination BoardsENGPDF5551 KB
Handbuch Funktionale SicherheitGERPDF525 KB
Handbuch Trennbarrieren und Termination Boards H-SystemGERPDF5543 KB
Instruction manuals
ИнструкцииBULPDF152 KB
Návod k poużitíCZEPDF147 KB
Instruktions manualDANPDF146 KB
Instruction manualENGPDF150 KB
KasutusjuhendESTPDF142 KB
KäyttöohjeFINPDF142 KB
Manuel d'instructionsFRAPDF147 KB
BetriebsanleitungGERPDF152 KB
Οδηγίες χρήσηςGREPDF155 KB
HandleidingHOLPDF146 KB
Instruction manual / BetriebsanleitungHRVPDF145 KB
Használati útmutatóHUNPDF148 KB
Manuale di istruzioniITAPDF146 KB
Lietošanas pamācībaLAVPDF145 KB
Instrukciju vadovasLITPDF146 KB
Instrukcja obsługiPOLPDF149 KB
Manual de instruçõesPORPDF146 KB
Manual de utilizareRONPDF146 KB
Návod na poużitieSLKPDF146 KB
Navodila za uporaboSLVPDF144 KB
Manual de instruccionesSPAPDF146 KB
ManualSWEPDF143 KB

CAD+CAE: HiC2025A

CADFile TypeFile Size
Dimension drawing 2-D (DXF) / Abmessungszeichnung 2-D (DXF)ZIP16364 KB

Approvals+Certificates: HiC2025A

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-4563PDF191 KB
Certificates
CESI IECEx Certificate of ConformityIECEx CES 06.0002XLINK---
Europe CESI ATEX Category (1) D ATEX Category (M1) ATEX Category (1) GCESI 06 ATEX 017PDF788 KB
Europe CESI ATEX Category 3CESI 19 ATEX 027XPDF492 KB
Worldwide TUV Rheinland Functional Safety Certificate968/FSP 1937.00/19PDF620 KB

Function: HiC2025A

This isolated barrier is used for intrinsic safety applications.

The device supplies 2-wire transmitters in the hazardous area, and can also be used with current sources.

It transfers the analog input signal to the safe area as an isolated current value.

Bi-directional communication is supported for SMART transmitters that use current modulation to transmit data and voltage modulation to receive data.

The output is selected as a current source, current sink, or voltage source via DIP switches.

This device mounts on a HiC Termination Board.