Serviceline Industrial Sensors
Serviceline Explosion Protection

Solenoid Driver HiC2873

HiC2873
  • 1-channel isolated barrier
  • 24 V DC supply (bus or loop powered)
  • Output 40 mA at 12 V DC, 55 mA current limit
  • Contact or logic control input
  • Entity parameter Io/Isc = 110 mA
  • Line fault detection (LFD)
  • Test pulse immunity
  • Up to SIL 2 acc. to IEC/EN 61508 (bus powered)
  • Up to SIL 3 acc. to IEC/EN 61508 (loop powered)

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HiC2873

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Rated voltage20.4 ... 30 V DC loop powered
20.4 ... 30 V DC bus powered via Termination Board
Input current62 mA at 24 V, 300 Ω load
Power dissipation1 W at 24 V, 300 Ω load
Input
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-) loop powered
SL1: 10a(+), 9a(-) bus powered
Control inputexternal switch (dry contact or open collector) non isolated or logic signal input fully floating
Signal level1-signal: 15...30 V DC (current limited to 3 mA) or contact close (internal 10 kΩ pull-up)
0-signal: 0...5 V DC or contact open
Power dissipation1 W at 24 V, 300 Ω load for loop powered
Inrush current0.2 A , 15 ms loop powered
Output
Connection sidefield side
ConnectionSL2: 5a(+), 5b(-)
Internal resistorapprox. 240 Ω
Current≤ 40 mA
Voltage≥ 12 V
Current limit55 mA
Open loop voltageapprox. 22.5 V
Loadnominal 0.1 ... 5 kΩ
Switching frequency- bus powered: filter OFF: max. 150 Hz, filter ON: max. 15 Hz
- loop powered: max. 10 Hz
Energized/De-energized delay- bus powered: filter OFF: 1 ms, filter ON: 10 ms
- loop powered: switch-on 50 ms, switch-off 6 ms (300 Ω load)
Line fault detection
Short-circuit< 25 Ω
Open-circuit> 100 kΩ
Test current< 4 mA
Fault indication output
ConnectionSL1: 6b
Output typeopen collector transistor (internal fault bus)
Fault current4 mA pulsing (20 ms ON, 200 ms OFF)
Fault levellead short-circuit detection at < 25 Ω
lead breakage detection at > 100 kΩ typical
Galvanic isolation
Output/power supply, inputs, and collective errorsafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Indicators/settings
Display elementsLEDs
Control elementsDIP switch
Factory settingbus powered, logic level control, line fault detection enabled
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Height106 mm
Width12.5 mm
Depth128 mm
Mountingon termination board
Codingpin 1 and 4 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateCESI 10 ATEX 046
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
OutputEx ia Ga, Ex ia Da, Ex ia Ma
Voltage25.2 V
Current110 mA
Power693 mW
Supply
Maximum safe voltage253 V AC (Attention! Um is no rated voltage.)
CertificateKIWA 15 ATEX 0036 X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018
International approvals
FM approval
Control drawing116-0431 (cFMus)
UL approval
Control drawing116-0383 (cULus)
IECEx approval
IECEx certificateIECEx CES 10.0017
IECEx KIWA 15.0018X
IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: HiC2873

Function

This isolated barrier is used for intrinsic safety applications.

The device supplies power to solenoids, LEDs and audible alarms located in a hazardous area.

It is controlled with a loop powered control signal, switch contact, transistor, or logic signal.

At full load, 12 V at 40 mA (with 55 mA current limit) is available for the hazardous area application.

Line fault detection of the field circuit is indicated by a red LED and an output on the fault bus.

This device mounts on a HiC termination board.

Product Documentation: HiC2873

Language Selection:
Product informationLanguageFile TypeFile Size
Application Guideline Solenoid DriversENGPDF734 KB
Safety and Security Documentation
Instruction manualENGPDF168 KB
Functional Safety ManualENGPDF1399 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiC2873

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP2770 KB
CAD Portal / CAD PortalALLLINK---
CAE
EPLAN macros H-System devices (EMA) / EPLAN-Makros Geräte H-System (EMA)ALLZIP3536 KB

Approvals: HiC2873

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
Brasil TUV Rheinland BrazilTÜV 18.3033ALLPDF301 KB
Canada FMFM 17 CA 0057XALLPDF328 KB
Europe CESI ATEX Category (1) D ATEX Category (M1) ATEX Category (1) GCESI 10 ATEX 046ALLPDF907 KB
Europe KIWA ATEX Category 3 GKIWA 15 ATEX 0036XALLPDF97 KB
KIWA Ex ec IECEx Certificate of Conformity Zone 2IECEx KIWA 15.0018XALLLINK---
Korea KOSHA15-AV4BO-0597ALLPDF630 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20181016 - E106378 RepRef 20140228ALLPDF260 KB
USA FMFM 17 US 0111XALLPDF330 KB
United Arab Emirates SGS Gulf Limited ECASEx23-12-96808/E23-12-099954/NB0002ALLPDF603 KB
United Arab Emirates SGS Gulf Limited ECASEx23-12-96809/E23-12-099955/NB0002ALLPDF602 KB
Worldwide CESI IECEx Certificate of ConformityIECEx CES 10.0017ALLLINK---
exida Functional Safety AssessmentP+F 11/07-044 R034 V1R2ALLPDF577 KB
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF88 KB
Control drawing FM / Control drawing FM   ALLPDF89 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0930CALLPDF49 KB

Associated Products: HiC2873

Accessory of
System board for Yokogawa ProSafe-RS, For 16-channel DO card SDV541, For 16 modules, Recommended modules: HiC2871 (DO), HiC2873 (DO), HiC2877 (DO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: Yokogawa, Control system type: ProSafe-RSpa
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 16-channel DO cards 3604E and 3624, For 16 modules, Recommended modules: HiC2873 (DO), HiC2877 (DO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: Triconex, Control system type: Triconpa
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 32-channel (16+16) DO cards 3625 and 3664, For 32 modules, Recommended modules: HiC2873 (DO), HiC2877 (DO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 32, Signal type: Digital Output, Manufacturer: Triconex, Control system type: Triconpa
System board for Schneider Electric, Tricon CX series by Triconex, TAN48 approval, For 16-channel universal I/O card 3902(A)X and AO card 3809(A)X, For 16 modules, Supported signal types: DI/DO/AI/TI/AO/UIO, 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: Sub-D connector (male), 50-pin, Up to SIL 3 acc. to IEC/EN 61508, Number of modules: 16, Signal type: Analog output
Universal, Manufacturer: Triconex, Control system type: Tricon CXpa
System board for Schneider Electric, Tricon CX series by Triconex, TAN48 approval, For 32-channel (16+16) DO card 3626X, For 16 modules, Recommended modules: HiC2871A (DO), HiC2873 (DO), HiC2883 (DO), HiC5861 (DO), HiC5863 (DO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: Triconex, Control system type: Tricon CXpa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.