Serviceline Industrial Sensors
Serviceline Explosion Protection

Termination Board HiCTB16-TRX-RAC-PL-IO16

HiCTB16-TRX-RAC-PL-IO16
  • System board for Schneider Electric, Tricon CX series by Triconex
  • For 16-channel universal I/O card 3902(A)X
  • For 16 modules
  • Supported signal types: DI/DO/AI/TI/AO/UIO
  • 24 V DC supply
  • Hazardous area: pluggable screw terminals, blue
  • Non-hazardous area: Sub-D connector (male), 50-pin
  • Up to SIL 3 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HiCTB16-TRX-RAC-PL-IO16

Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Systematic capability (SC)SC 3
Supply
ConnectionX20: terminals 3, 5(+); 4, 6(-)
Nominal voltage24 V DC , in consideration of rated voltage of used isolators
Voltage drop0.9 V , voltage drop across the series diode on the termination board must be considered
Ripple≤ 10 %
Fusing4 A , in each case for 16 modules
Power dissipation≤ 500 mW , without modules
Reverse polarity protectionyes
Redundancy
SupplyRedundancy available. The supply for the isolators is decoupled, monitored and fused.
Fault indication output
ConnectionX20: terminals 1(+), 2(-)
Output typevolt-free transistor output , not short-circuit protected , not overload protected
Rated voltage30 V DC
Rated current100 mA
Signal levelno fault: (external voltage) - 1 V max. for 100 mA (Tamb = 25 °C (77 °F))
power supply fault/module fault: blocked output (off-state current ≤ 10 µA)
Indicators/settings
Display elementsLED PWR1 (termination board power supply), green LED
LED PWR2 (termination board power supply), green LED
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityEN IEC 61326-3-2:2018 , NE 21:2017
For further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Connection
Field sideexplosion hazardous area: 4 screw terminals per module , blue
Control sidenon-explosion hazardous area: 50-pin Sub-D connector
Supplypluggable screw terminals , black
Fault outputpluggable screw terminals , black
Core cross-sectionscrew terminals 0.25 ... 2.5 mm2 (24 ... 12 AWG)
Materialhousing: polycarbonate, 10 % glass fiber reinforced
Massapprox. 725 g
Dimensions216 x 200 x 163 mm (8.5 x 7.9 x 6.42 inch) , height including module assembly
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateCESI 06 ATEX 022
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Non-hazardous area
Maximum safe voltage250 V (Attention! Um is no rated voltage.)
Galvanic isolation
Field circuit/control circuitsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-11:2012 , EN 50303:2000
International approvals
UL approvalE106378
Control drawing116-0327
IECEx approval
IECEx certificateIECEx CES 06.0003
IECEx marking[Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Documents: HiCTB16-TRX-RAC-PL-IO16

ManualsLanguageFile TypeFile Size
Manual H-System Isolated Barriers and Termination BoardsENGPDF5551 KB
Handbuch Trennbarrieren und Termination Boards H-SystemGERPDF5543 KB
Instruction manuals
ИнструкцииBULPDF143 KB
Návod k poużitíCZEPDF138 KB
Instruktions manualDANPDF137 KB
Instruction manualENGPDF142 KB
KasutusjuhendESTPDF134 KB
KäyttöohjeFINPDF133 KB
Manuel d'instructionsFRAPDF139 KB
BetriebsanleitungGERPDF144 KB
Οδηγίες χρήσηςGREPDF145 KB
HandleidingHOLPDF138 KB
Instruction manual / BetriebsanleitungHRVPDF136 KB
Használati útmutatóHUNPDF138 KB
Manuale di istruzioniITAPDF137 KB
Lietošanas pamācībaLAVPDF137 KB
Instrukciju vadovasLITPDF139 KB
Instrukcja obsługiPOLPDF139 KB
Manual de instruçõesPORPDF138 KB
Manual de utilizareRONPDF137 KB
ИнструкцииRUSPDF144 KB
Návod na poużitieSLKPDF137 KB
Navodila za uporaboSLVPDF136 KB
Manual de instruccionesSPAPDF138 KB
ManualSWEPDF135 KB
Short instructions, safety information
Manufacturer's Declaration Functional SafetyENGPDF208 KB
Technical information
Technical informationENGPDF137 KB

Approvals+Certificates: HiCTB16-TRX-RAC-PL-IO16

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-4840APDF48 KB
Certificates
CESI IECEx Certificate of ConformityIECEx CES 06.0003LINK---
Canada UL cULE106378 cUL (QVAJ7)LINK---
Canada UL cULE106378 cUL (QUZW7)LINK---
China NEPSIGYJ17.1292PDF1919 KB
EAC Pepperl+Fuchs EAC TP TC 020/2011EAEC N RU D-DE.PA01.B.95483/21PDF812 KB
Europe CESI ATEX Category (1) GD ATEX Category (M1)CESI 06 ATEX 022PDF869 KB
India PESO (India) CCOEA/P/HQ/KA/104/5881 (P508977)PDF100 KB
Russia Belarus Kazakhstan EAC EAC TP TC 012/2011EAEC RU C-DE.EX01.B.00102/19PDF9815 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20180415 - E106378 RepRef 20100930PDF576 KB
USA ULE106378 UL (QUZW)LINK---
USA ULE106378 UL (QVAJ)LINK---
Control drawings
Control Drawing UL / Control Drawing UL   PDF166 KB

Associated Products: HiCTB16-TRX-RAC-PL-IO16

Accessories
For Cold Junction Compensation of HiC2081, For HiC Termination Boards, Packaging unit: 8 piecespa
For HiC Termination Boards, 1 piece for 8-position Termination Board, 2 pieces for 16-position Termination Boardpa

Function: HiCTB16-TRX-RAC-PL-IO16

The function of the termination board and the system connector pin assignment is exactly fitted to the requirements of the Triconex Tricon CX system.

The signal is output to the process control system via the system connector.

Information about missing supply voltage of the isolated barriers is available for the system at the volt-free transistor output.

Wiring faults from the field side will be reported via the volt-free transistor output, if this function is supported by the isolators.

The termination board has a robust glass fiber reinforced plastic housing.

The termination board is mounted in the switch cabinet on a 35 mm DIN mounting rail according to EN 60175.