Serviceline Industrial Sensors
Serviceline Explosion Protection

HART Termination Board HiS1132/CON8-H-LTX-02

HiS1132/CON8-H-LTX-02
  • APACS/QUADLOG replacement FTA
  • Bailey Infi 90 replacement FTA
  • Product connector; PCS wiring
  • Easy switch selectable configurations for AO and AI

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HiS1132/CON8-H-LTX-02

Supply
Rated voltage20 ... 30 V DC
Fusing3.15 A , 5 x 20 mm (0.2 x 0.8 inch)
Power dissipation0.7 W , with Multiplexer
Reverse polarity protectionyes
HART signal channels (intrinsically safe)
HART signal channels
Number of channels32 unbalanced signal loops
Redundancy
Supplyyes
Galvanic isolation
HART signal channels30 V DC
Ambient conditions
Ambient temperature0 ... 55 °C (32 ... 131 °F)
Relative humidity5 ... 90 %, non-condensing
Mechanical specifications
Core cross section2.5 mm2 (16 AWG)
Connectionfield side: fixed screw terminals
control side: PCS-specified connector
RS 485 interface: removable screw terminals
power: removable screw terminals
Massapprox. 700 g
Dimensions333 x 125 x 208 mm (13.1 x 4.9 x 8.2 inch) (W x H x D) , depth including module assembly with HiDMux2700
Height125 mm
Width333 mm
Depth208 mm
MountingDIN rail mounting
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210190
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127242690
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: HiS1132/CON8-H-LTX-02

Function

The Termination Board is designed for easy HiDMux2700 Multiplexer integration with the Siemens Moore APACS/Quadlog system or the Bailey Infi 90 system.

With the Multiplexer integrated into the board and plug-n-play options for choosing the correct DCS connection through the Interface Adapter Card (IAC), this provides a clean and clear access to the HART signals, while reducing the need for marshalling cabinets and reduce equipment that require extra cabinet space.

The HART Termination Board provides a robust solution for on-line HART communications, interfaces up to 32 field located HART devices, and, it allows the user to replace standard DCS field termination panels.

Product Documentation: HiS1132/CON8-H-LTX-02

Language Selection:
ManualsLanguageFile TypeFile Size
Manual DTM description HiDMux2700ENGPDF2278 KB
Manual HiDMux2700ENGPDF8581 KB

Associated Products: HiS1132/CON8-H-LTX-02

Accessory of

32-channel, 24 V DC supply, HART field device input (revision 5 to 7), RS-485 interface, Up to SIL 3 acc. to IEC/EN 61508pa