Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

HART Communication Board HiATB01-HART-4X8

HiATB01-HART-4X8
  • 4 x 8-channel
  • 24 V DC supply
  • Suitable for HART communication
  • Dual RS 485 connections
  • Used with HiD/HiC Termination Boards
  • LED for supply status

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HiATB01-HART-4X8

Supply
ConnectionX20: terminals 1, 3 (+); 2, 4 (-)
Nominal voltage24 V DC SELV/PELV
Voltage drop0.9 V , voltage drop across the series diode on the termination board must be considered
Ripple≤ 10 %
Fusing0.5 A
Power dissipation≤ 500 mW , without modules
Reverse polarity protectionyes
Interface
Type/number2 x RS-485
Redundancy
SupplyRedundancy available. Each supply is decoupled.
Indicators/settings
Display elementsLED PWR1 (Termination Board power supply), green LED
LED PWR2 (Termination Board power supply), green LED
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012
For further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connection
Control sideRS-485 : 1 x screw terminal , black
HART : 4 x IDC plug, 34-pin
Supplypluggable screw terminals , black
Core cross-sectionscrew terminals: 0.25 ... 1.5 mm2 (24 ... 12 AWG)
Materialhousing: polycarbonate, 10 % glass fiber reinforced
Massapprox. 210 g
Dimensions50 x 200 x 163 mm (1.97 x 7.9 x 6.42 inch) , height including module assembly
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001

Documents: HiATB01-HART-4X8

ManualsLanguageFile TypeFile Size
Brief instructions HART Interface Solutions H-SystemENGPDF452 KB
Manual DTM description HiDMux2700ENGPDF2278 KB
Manual HiDMux2700ENGPDF8581 KB
Handbuch DTM-Beschreibung HiDMux2700GERPDF2323 KB
Handbuch HiDMux2700GERPDF8545 KB
Kurzanleitung HART Interface Solutions H-SystemGERPDF454 KB

Approvals+Certificates: HiATB01-HART-4X8

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-0675BPDF180 KB
Certificates
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB

Associated Products: HiATB01-HART-4X8

Accessory of

32-channel, 24 V DC supply, HART field device input (revision 5 to 7), RS-485 interface, Up to SIL 3 acc. to IEC 61508pa
System board for Honeywell Safety Manager, For 4 pieces 2-channel card SAO-0220m, For 8 modules, Recommended module: HiC2031 (AO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: SiC plug, 20-pinpa
Accessories
H-System accessory, Connection cable between HART Communication Board and Termination Board, 34-pin cablepa
H-System accessory, Connection cable between HART Communication Board and Termination Board, 34-pin cablepa
H-System accessory, Connection cable between HART Communication Board and Termination Board, 34-pin cablepa
H-System accessory, Connection cable between HART Communication Board and Termination Board, 34-pin cablepa