Serviceline Industrial Sensors
Serviceline Explosion Protection

Termination Board FC-GPCS-RIO16-PF

FC-GPCS-RIO16-PF
  • System board for Honeywell Universal Safety IO
  • System board for Honeywell Universal Process IO
  • For 16-channel cards USIO and UPIO
  • For 16 modules
  • Recommended modules: HiC2831R2 (DI), HiC2853R2 (DI), HiC2871 (DO), HiC2025 (AI), HiC2031 (AO)
  • Recommended system cable: CAB-HON-**-S37C32-MX-01000
  • 24 V DC supply
  • Hazardous area: pluggable screw terminals, blue
  • Non-hazardous area: Sub-D connector (male), 37-pin

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  FC-GPCS-RIO16-PF

Supply
Connectionterminal block TB3 (1-, 2+; 3-, 4+)
Nominal voltage24 V DC , in consideration of rated voltage of used isolators
Voltage drop0.9 V , voltage drop across the series diode on the termination board must be considered
Ripple≤ 10 %
Fusing4 A
Power dissipation≤ 500 mW , without modules
Reverse polarity protectionyes
Redundancy
SupplyRedundancy available. The supply for the isolators is decoupled, monitored and fused.
Fault indication output
Output typevolt-free contact
Contact loading30 V DC , 1 A
Indicators/settings
Display elementsLEDs PWR ON (power supply)
- LED power supply I, green LED
- LED power supply II, green LED
LED Fault (fault indication), red LED
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2017
For further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connection
Field sideexplosion hazardous area: pluggable screw terminals , blue
Control sidenon-explosion hazardous area: 37-pin Sub-D connector
Supplypluggable screw terminals , black
Fault outputpluggable screw terminals , black
Core cross-sectionscrew terminals: 0.25 ... 2.5 mm2 (24 ... 12 AWG)
Materialhousing: polycarbonate
Massapprox. 825 g
Dimensions273 x 155 x 153 mm (L x W x H) , height including module assembly
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateCESI 06 ATEX 022
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Non-hazardous area
Maximum safe voltage250 V (Attention! Um is no rated voltage.)
CertificateDEMKO 18 ATEX 2116 X
MarkingEx-Hexagon II 3G Ex ec nC IIC T4 Gc
Galvanic isolation
Field circuit/control circuitsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , IEC 60079-15:2017 , EN 50303:2000
International approvals
UL approval
Control drawing116-0327
IECEx approval
IECEx certificateIECEx CES 06.0003
IECEx UL 18.0111 X
IECEx marking[Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
Ex ec nC IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Designationprovided accessory: Label Carrier HiALC-HI*TF-SET-1**
optional accessories: system cable CAB-HON-**-S37C32-MX-01000

Documents: FC-GPCS-RIO16-PF

ManualsLanguageFile TypeFile Size
Manual Termination Board Solutions HoneywellENGPDF852 KB
Handbuch Termination Board-Lösungen HoneywellGERPDF854 KB
Instruction manuals
ИнструкцииBULPDF151 KB
Návod k poużitíCZEPDF145 KB
Instruktions manualDANPDF144 KB
Instruction manualENGPDF75 KB
KasutusjuhendESTPDF140 KB
KäyttöohjeFINPDF140 KB
Manuel d'instructionsFRAPDF148 KB
BetriebsanleitungGERPDF75 KB
Οδηγίες χρήσηςGREPDF154 KB
HandleidingHOLPDF146 KB
Instruction manual / BetriebsanleitungHRVPDF143 KB
Használati útmutatóHUNPDF147 KB
Manuale di istruzioniITAPDF145 KB
Lietošanas pamācībaLAVPDF144 KB
Instrukciju vadovasLITPDF145 KB
Instrukcja obsługiPOLPDF147 KB
Manual de instruçõesPORPDF147 KB
Manual de utilizareRONPDF146 KB
Návod na poużitieSLKPDF145 KB
Navodila za uporaboSLVPDF142 KB
Manual de instruccionesSPAPDF146 KB
ManualSWEPDF142 KB

Approvals+Certificates: FC-GPCS-RIO16-PF

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-4242PDF163 KB
Certificates
CESI IECEx Certificate of ConformityIECEx CES 06.0003LINK---
Canada UL cULE106378 cUL (QUZW7)LINK---
Canada UL cULE106378 cUL (QVAJ7)LINK---
China NEPSIGYJ17.1292PDF1919 KB
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB
Europe CESI ATEX Category (1) GD ATEX Category (M1)CESI 06 ATEX 022PDF869 KB
Europe DEMKO ATEX Category 3 GDEMKO 18 ATEX 2116XPDF446 KB
Russia Belarus Kazakhstan EAC EAC TP TC 012/2011EAEC RU C-DE.EX01.B.00102/19PDF9815 KB
TUV Rheinland BrazilTÜV 14.0084 XPDF625 KB
UL IECEx Certificate of ConformityIECEx UL 18.0111XLINK---
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20180415 - E106378 RepRef 20100930PDF576 KB
USA ULE106378 UL (QUZW)LINK---
USA ULE106378 UL (QVAJ)LINK---
Control drawings
Control drawing UL / Control drawing UL   PDF168 KB

Associated Products: FC-GPCS-RIO16-PF

Accessories
Honeywell specific system cable for Honeywell Experion Series C I/O and Universal Safety I/O to Pepperl+Fuchs H-System termination boards, Connects terminal plug on Honeywell series C300 Input Output Termination Assembly (IOTA) to a single 37-pin Sub-D connector on H-System termination boards, Universal usage for all signal types (AI, AO, DI, DO)pa

Function: FC-GPCS-RIO16-PF

The function of the termination board and the connector pin assignment is exactly fitted to the requirements of Honeywell system.

Information about a missing supply voltage of the isolators is available for the system as a volt-free contact.

It is possible to transfer a fault signal to channel 1 of the card via the loop-in function.

The termination board is supplied with a robust plastic housing. This design permits the fast and reliable installation on 35 mm DIN mounting rail according to  EN 60715 in the switch cabinet.