Serviceline Industrial Sensors
Serviceline Explosion Protection

HART Multiplexer Master HiDMux2700

HiDMux2700
  • 32-channel
  • 24 V DC supply
  • HART field device input (revision 5 to 7)
  • RS-485 interface
  • Up to SIL 3 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HiDMux2700

Product Description
HART Multiplexer Master
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Rated voltage20.4 ... 30 V DC via Termination Board
Rated current28 mA at 24 V , RS-485, quiescent current
Power dissipation0.7 W at 24 V
HART signal channels (non-intrinsically safe)
Number of channels32
ConformityHART field device input (revision 5 to 7)
Signal range0.12 Vpp < signal < 1.5 Vpp
Leakage current< 3 µA at -20 ... 85 °C (-4 ... 185 °F)
Terminating resistorexternal 230 ... 500 Ω standard (up to 1000 Ω possible)
Output voltage≥ 400 mV ss (with the terminator resistance specified above)
Output resistance100 Ω or smaller, capacitive coupling
DC isolationdual capacitor each channel
Common mode voltageup to 30 V
Input impedance> 5 kΩ , according to HART specification
Input voltage range0.12 ... 1.5 V ss
Common mode voltagemax. 30 V
Differential mode clamping± 5.2 V , for transient or AC signals
Common mode clamping± 10 V , for transient or AC signals
Carrier detect levelsignal > 0.12 Vpp, carrier detection activated
signal < 0.08 Vpp, carrier detection not activated
Transmit amplitude200 Ω load, 0.43 Vpp < signal < 0.49 Vpp
500 Ω load, 1.1 Vpp < signal < 1.2 Vpp
Device typeDC isolated bus device
Impedancehigh impedance
Data link typeHART primary and secondary
Field multi point supportoption available upon request
Interface
Transfer rate9600 MBit/s, 19200 MBit/s or 38400 MBit/s, selectable via switch
Address1 ... 31 , adjustable via DIP switch
TypeRS-485 , differential pair and grounding
Topologymulti point, master/slave connection
Galvanic isolation
Interface/power supply500 Vrms
Interface/field channels1000 Veff
Power supply/field channels1000 Veff
Indicators/settings
Display elementsLEDs
LED PWR ON (power supply), one green LED
LED HART TX (HART transmission), one yellow LED
LED FAULT (lead fault), one red LED
Control elementsDIP switches at the housing side for:
- unit slave address
- baud rate
- test mode on/off
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012
For further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Relative humidity5 ... 95 %, noncondensing
Mechanical specifications
Degree of protectionIP20
Massapprox. 140 g
Dimensions18 x 114 x 130 mm (0.7 x 4.5 x 5.1 inch) (W x H x D)
Height114 mm
Width18 mm
Depth130 mm
Mountingon termination board
Data for application in connection with hazardous areas
CertificateCML 17 ATEX 3337X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018
International approvals
CSA approval
CSA certificate1256050
Approved forClass I, Division 2, Groups A, B, C, D and non-explosion hazardous area
IECEx approval
IECEx certificateIECEx CML 17.0178X
IECEx markingEx ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210190
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127242692
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001597
UNSPSC 12.139121008

Details: HiDMux2700

Function

The HART Multiplexer Master provides 32 signal channels for connection to SMART transmitters or control devices supporting digital communication according to the HART standard.

Full three-port isolation is included and each input channel has dual capacitor isolation for freedom of loop connection.

Each HART Multiplexer Master is networked simply by connecting the high-speed RS 485 output in a multidrop configuration.

The device interrogates each field device, under the supervision of the workstation, retrieving information for storage in its internal database, which is then easily accessed.

This module is intended to mount on an HiD Termination Board or HART Communcation Board. Also special boards for DCS integration are available.

For additional information, refer to the manual and www.pepperl-fuchs.com.

Product Documentation: HiDMux2700

Language Selection:
Safety and Security DocumentationLanguageFile TypeFile Size
Instruction manualENGPDF162 KB
Manuals
Manual DTM description HiDMux2700ENGPDF2278 KB
Manual HiDMux2700ENGPDF8581 KB

Design / Simulation: HiDMux2700

Language Selection:
CADLanguageFile TypeFile Size
CAD 2-D / CAD 2-DALLZIP16364 KB

Approvals: HiDMux2700

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
ATEX CertificateCML 17 ATEX 3337XALLPDF126 KB
Canada, USA CSACoC 1256050ALLPDF143 KB
China SITIIAS CCC Ex Certificate2020322310003539 (Singapore)ALLPDF813 KB
IECEx Certificate of ConformityIECEx CML 17.0178XALLLINK---
Korea Radio ApprovalKCC-REI-PF1-HiDMUX2700ALLPDF474 KB
exida Functional Safety AssessmentP+F 02/4-11 R006ALLPDF348 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-0226FENGENGPDF1128 KB
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F)DOC-5295BALLPDF1037 KB

Software: HiDMux2700

Language Selection:
FrameworksRelease InfoFile TypeFile Size
PACTware 4.1 SP6 / PACTware 4.1 SP64.1.0.53ZIP43327 KB
PACTware 5.0 / PACTware 5.05.0.5.31ZIP44203 KB
Device Description Files/Drivers
DTM Collection HART-Multiplexer / DTM Collection HART-Multiplexer2.0.1.208ZIP13306 KB

Associated Products: HiDMux2700

Accessory of

For 8 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO/UIO, Hazardous area: screw terminals, blue, Non-hazardous area: screw terminals, black, Number of modules: 8, Number of channels per module: 1 , 2, Signal type: Universal, Manufacturer: Generic, Control system type: Universalpa

For 16 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO/UIO, Hazardous area: screw terminals, blue, Non-hazardous area: screw terminals, black, Number of modules: 16, Number of channels per module: 1 , 2, Signal type: Universal, Manufacturer: Generic, Control system type: Universalpa
System board for Schneider Electric, Tricon CX series by Triconex, For 32-channel (16+16) AI cards 3722X and 3723X, For 16 modules, Recommended modules: HiC2027 (AI), HiC2027ES (AI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: screw terminals, black, Non-hazardous area: ELCO socket, 56-pin, Up to SIL 3 acc. to IEC/EN 61508, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon CX, Safety Integrity Level (SIL): SIL 3pa
For 8 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO/UIO, Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 8, Number of channels per module: 1 , 2, Signal type: Universal, Manufacturer: Generic, Control system type: Universalpa
System board for Honeywell Safety Manager, For 16-channel AI card SAI-1620m, For 16 modules, Recommended module: HiC2025(A) (AI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: SiC plug, 20-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Honeywell, Control system type: Safety Managerpa
System board for Honeywell Safety Manager, For four 2-channel AO cards SAO-0220m, For 8 modules, Recommended module: HiC2031 (AO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: SiC plug, 20-pin, Number of modules: 8, Signal type: Analog output, Manufacturer: Honeywell, Control system type: Safety Managerpa
For 16 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO/UIO, Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Universal, Manufacturer: Generic, Control system type: Universalpa
For 8 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO/UIO, Hazardous area: spring terminals, blue, Non-hazardous area: spring terminals, black, Number of modules: 8, Number of channels per module: 1 , 2, Signal type: Universal, Manufacturer: Generic, Control system type: Universalpa
For 32 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO/UIO, Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 32, Signal type: Universal, Manufacturer: Generic, Control system type: Universalpa
For 16 modules, 24 V DC supply, Supported signal types: DI/DO/AI/TI/AO/UIO, Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Number of channels per module: 1 , 2, Signal type: Universal, Manufacturer: Generic, Control system type: Universalpa
System board for Honeywell Experion PKS, Series C, For 16-channel AI card CC-TAIX01/11, For 16-channel AO card CC-TAOX01/11, For 32-channel DI card CC-TDIL01/11, For 32-channel DO card CC-TDOB01/11, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2031 (AO), HiC2821 (DI), HiC2871 (DO), Recommended system cable: CAB-HON-**-S37C32-MX-01000, 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Number of modules: 16, Signal type: Universal, Manufacturer: Honeywellpa
System board for Schneider, Foxboro FBM series, For 8 modules, For 8-channel cards FBM201/214(b)/216(b) (AI), FBM215/218/237 (AO), FBM204/205 (AO/AI), FBM244 (AI/AO), FBM247/248 (UIO), 24 V DC supply, Recommended modules: HiC2025(A) (AI), HiC2031 (AO), HiC2081 (TI), HiC2831R5 (DI), HiC2883 (DO), HiC2441 (UIO), Hazardous area: spring terminals, blue, Non-hazardous area: Sub-D connector (male), 25-pin, Number of modules: 8, Signal type: Universal, Manufacturer: Foxboro, Control system type: FBMpa
System board for Schneider Electric, Tricon CX series by Triconex, For 32-channel (16+16) AI cards 3722X and 3723X, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2081 (TI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon CXpa
System board for Schneider Electric, Tricon CX series by Triconex, For 32-channel (16+16) AI cards 3722X and 3723X, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2081 (TI), 24 V DC supply, Field side: spring terminals, black, Control side: ELCO socket, 56-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon CXpa
System board for Schneider Electric, Tricon CX series by Triconex, TAN48 approval, For 32-channel (16+16) AI cards 3722X and 3723X, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2025ES (AI), HiC2081 (TI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon CXpa
System board for HIMA, HIMax, For 32-channel cards X-AI 32 01 or X-AI 32 02 (AI), For 32 modules, Recommended modules: HiC2025(A) (AI), HiC2081 (TI), HiC2441 (UIO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Number of modules: 32, Signal type: Analog input, Manufacturer: HIMA, Control system type: HIMaxpa
System board for HIMA, HIMax, For 32-channel cards X-AI 32 01 or X-AI 32 02 (AI), For 32 modules, Recommended module: HiC2027 (AI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Non-hazardous area: spring terminals, black, Number of modules: 32, Signal type: Analog input, Manufacturer: HIMA, Control system type: HIMaxpa
System board for HIMA, HIMax, For 16-channel card X-AO 1601 (AO, single mode), 16-channel card X-AO 1601 (AO, redundant mode on request), For 16 modules, Recommended module: HiC2031 (AO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: HIMA system connector, 96-pin, Number of modules: 16, Signal type: Analog output, Manufacturer: HIMA, Control system type: HIMaxpa
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 8-channel AO card 3805E, For 8 modules, Recommended module: HiC2031 (AO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 8, Signal type: Analog output, Manufacturer: Triconex, Control system type: Triconpa
System board for Schneider Electric, Tricon series by Triconex, For 64-channel (32+32) AI cards 3704E and 3720, For 32 modules, Recommended modules: HiC2025(A) (AI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 32, Signal type: Analog input, Manufacturer: Triconex, Control system type: Triconpa
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 32-channel (16+16) AI cards 3700A, and 3721, For 16 modules, Recommended modules: HiC2025(A) (AI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Triconpa
Matching System Components

2 x 16-channel, 24 V DC supply, Suitable for HART communication, Dual RS 485 connections, Used with HiC Termination Boards, LED indicator for supply status, Splitting: 2 x 16pa

4 x 8-channel, 24 V DC supply, Suitable for HART communication, Dual RS 485 connections, Used with HiC Termination Boards, LED indicator for supply status, Splitting: 4 x 8pa
4 x 8-channel, 24 V DC supply, Suitable for HART communication, Dual RS 485 connections, Used with HiC Termination Boards, LED indicator for supply status, Splitting: 4 x 8pa
Matching System Components
Serial Device Server 1-port DIN Rail Screw Terminalfa
Accessories
Triconex 3604E replacement FTA, Outputs: 2 x 16 channels, 24 V DC, opto-isolated, non commoned, Short-circuit protected, Plug-n-play wiring capabilities, Number of channels: 32 unbalanced signal loopspa
Triconex 3701 replacement FTA, 2- or 3-wire or self powered transmitters, Outputs: 2 x 16 channels, 0 V ... 10 V differential, DC coupled (makes 32 channels), Short-circuit protected, Plug-n-play wiring capabilities, Number of channels: 32 unbalanced signal loopspa
Triconex 3704E and 3720 replacement FTA, 2- or 3-wire or self powered transmitters, Outputs: 1 x 32 channels, 0 V ... 5 V differential, DC coupled, Short-circuit protected, Plug-n-play wiring capabilities, Number of channels: 32 unbalanced signal loopspa
64-channel, 24 V DC supply, Connection of two Multiplexers to HART enabled Honeywell TDC 3000 FTA's , Redundant power supply connections, Dual RS 485 connections, HART loop connection via four 20-pin flat ribbon connectors, Compact design, Number of channels: 64 unbalanced signal loopspa
Yokogawa Centum 3000 CS AAI835 replacement FTA, 32 channels of I/O, 16 channels AI and 16 channels AO, 2- or 3-wire or self powered transmitters or valves, Short-circuit protected, Plug-n-play wiring capabilities, Number of channels: 32 unbalanced signal loopspa
Yokogawa Centum 3000 CS AAI135 replacement FTA, 32 channels of I/O, 2- or 3-wire or self powered transmitters, Short-circuit protected, Plug-n-play wiring capabilities, Number of channels: 32 unbalanced signal loopspa
APACS/QUADLOG replacement FTA, Bailey Infi 90 replacement FTA, Product connector; PCS wiring, Easy switch selectable configurations for AO and AI, Number of channels: 32 unbalanced signal loopspa
Triconex 3805E replacement FTA, 32 channels of I/O, Outputs: 4 x 8 channels, 4 mA ... 20 mA current loop, DC coupled, Short-circuit protected, HART analog output filters, Number of channels: 32 unbalanced signal loopspa
Triconex 3700A and 3721 replacement FTA, 2- or 3-wire or self powered transmitters, Outputs: 2 x 16 channels, 0 V ... 10 V differential, DC coupled (makes 32 channels), Short-circuit protected, Plug-n-play wiring capabilities, Number of channels: 32 unbalanced signal loopspa
TDC 3000 replacement FTA, Short-circuit protected, HART analog output filters, Redundant PCS wirings, Redundant power supply connections, Field terminal blocks that are Honeywell FTA compatible, Honeywell "B" size footprint, Number of channels: 32 unbalanced signal loopspa
TDC 3000 replacement FTA, Short-circuit protected, Process control system wirings, Redundant power supply connections, Field terminal blocks that are Honeywell FTA compatible, Honeywell "B" size footprint, Number of channels: 32 unbalanced signal loopspa
TDC 3000 replacement FTA, Short-circuit protected, Redundant PCS wirings, Redundant power supply connections, Field terminal blocks that are Honeywell FTA compatible, Honeywell "B" size footprint, Number of channels: 32 unbalanced signal loopspa
IA 200 replacement FTA, Designed for FBMs 201, 204, 215 and 237, 25-pin Sub-D connectors, PCS wiring, Redundant power supply connections, Easy to add line impedance, Number of channels: 32 unbalanced signal loopspa
32-channel, 24 V DC supply, Interface for serial or parallel wiring options, 37-pin Sub-D connectors, Slot for HART Multiplexer, Number of channels: 32 unbalanced signal loopspa
Communication DTM, Frame application, like e. g. PACTware, must be installed separatelypa
Human machine interface, For HiDMux2700, For KFD2-HMM-16/KFD0-HMS-16pa
Device DTM, For HART multiplexers, Communication DTMpa
H-System accessory, Connection cable between HART Communication Board and Termination Board, 34-pin cablepa
H-System accessory, Connection cable between HART Communication Board and Termination Board, 34-pin cablepa
H-System accessory, Connection cable between HART Communication Board and Termination Board, 34-pin cablepa
H-System accessory, Connection cable between HART Communication Board and Termination Board, 34-pin cablepa
H-System accessory, Connection cable between HART Communication Board and Termination Board, 34-pin cablepa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Functional Safety Hub from Pepperl+Fuchs

Several hundred products with a SIL/PL assessment, free tools, and brochures in one place: the "Functional Safety Hub" is your starting point when you have to implement safety functions.