Serviceline Industrial Sensors
Serviceline Explosion Protection
Not available for purchase
Not available for purchase

Switch Amplifier EG4-R

EG4-R
  • 4-channel isolated barrier
  • 24 V DC supply
  • Dry contact or NAMUR inputs
  • Relay output and active transistor output
  • Line fault detection (LFD)
  • Reversible mode of operation
  • Up to SIL 2 acc. to IEC 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  EG4-R

General specifications
Signal typeDigital Input
Supply
Connectiond14+, z14-
Rated voltage20.4 ... 27.6 V DC
Ripple≤ 10 %
Rated currentapprox. 130 mA
Input
Input (intrinsically safe)
Number of channels4
Connectionchannel 1: d2-, z2+
channel 2: d4-, z4+
channel 3: d6-, z6+
channel 4: d8-, z8+
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I ≤ 0.1 mA
Pulse/Pause ratio≥ 0.5 ms / ≥ 0.5 ms
Input (non-intrinsically safe)mode of operation reversible
Connectionchannal 1: z18
channel 2: z22
channel 3: z 26
channel 4: z30
Input current1 mA
Signal level1-signal: 15 ... 30 V DC
0-signal: 0 ... 5 V DC or open input
Input delay5 ... 20 ms (typical 10 ms)
Output
Connectionchannel 1: output I: d20, d18, output II: b20, b18, output III: z20
channel 2: output IV: d24, d22, output V: b24, b22, output VI: z24
channel 3: output VII: d28, d26, output VIII: b28, b26, output IX: z28
channel 4: output X: d32, d30, output XI: b32, b30, output XII: z32
Switching currentoutput III, VI, IX, XII : 10 mA , short-circuit protected
Outputoutput III, VI, IX, XII : electronic output, active
Signal leveloutput III, VI, IX, XII :
1-signal: (L+) -5 V/0.9 V
0-Signal: blocked output (off-state current ≤ 10 µA)
Contact loadingin conjunction with SIL2 applications
output I, II, IV, V, VII, VIII, X, XI: 50 V AC/1 A/cos φ = 1/0.5 A/cos φ = 0.3; 40 V DC/1 A/50 W resistive load
Energized/De-energized delayoutput I, II, IV, V, VII, VIII, X, XI: < 12 ms / < 10 ms
Mechanical lifeoutput I, II, IV, V, VII, VIII, X, XI: 2 x 105 switching cycles
Transfer characteristics
Switching frequencyoutput I, II, IV, V, VII, VIII, X, XI: ≤ 25 Hz
output III, VI, IX, XII 1 kHz ≤ max. 1 kHz
Galvanic isolation
Output/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECThe device has been used for the same applications for several years. It therefore features an appropriate electromagnetic field immunity. The device must not be used in new plants.
Conformity
Insulation coordinationEN 50178
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connection48-pin plug connector acc. to DIN 41612 , series 2 , type F , z, b and d provided
Massapprox. 300 g
Dimensions20 x 128 x 193 mm (0.8 x 5 x 7.5 inch)
Height128 mm
Width20 mm
Length190 mm
Construction typeEurocard 100 x 160 mm (3.9 x 6.3 inch) acc. to DIN 41494, front panel 4TE
Mountingin 19" rack
Codinga3/c7
Data for application in connection with hazardous areas
EU-type examination certificatePTB 00 ATEX 2210 , for additional certificates see www.pepperl-fuchs.com
MarkingEx-Hexagon II (1)GD [EEx ia] IIC
InputEEx ia IIC
Voltage12.7 V
Current20 mA
Power62 mW (linear characteristic)
Output
Contact loadingoutput I, II, IV, V, VII, VIII, X, XI: 50 V AC/2 A/cos φ = 1/1 A/cos φ = 0.3; 40 V DC/2 A/100 W resistive load
Galvanic isolation
Input/Outputsafe galvanic isolation acc. to EN 50020, voltage peak value 375 V
Input/power supplysafe galvanic isolation acc. to EN 50020, voltage peak value 375 V
Directive conformity
Directive 94/9/ECEN 50014:1997, EN 50020:1994
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: EG4-R

Function

This isolated barrier is used for intrinsic safety applications.

The device transfers digital signals (NAMUR sensors or dry contacts) from a hazardous area to a safe area.

Each proximity sensor or switch controls a relay output for the safe area load. The mode of operation and the line fault detection can be determined for each individual channel. This allows a desired mix of sensors and mechanical contacts with or without LB/SC.

A fault is signalized by LEDs acc. to NAMUR NE44.

Product Documentation: EG4-R

Language Selection:
ManualsLanguageFile TypeFile Size
Brief Instructions - E-systemENGPDF320 KB

Approvals: EG4-R

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
exida Functional Safety AssessmentP+F 03/3-25 R010ALLPDF468 KB