KFD2-EB2.RPI
  • 24 V DC supply voltage
  • Device installation in Zone 2
  • Supply current ≤ 4 A
  • Replaceable fuse
  • Fault indication output with adjustable mode of operation
  • Bus access via terminals
  • EMC acc. to NAMUR NE 21

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Datasheet excerpt: Technical data of  KFD2-EB2.RPI

Supply
Connectionterminals 11+, 12-
terminals 8+, 9-
Rated voltage20 ... 30 V DC
The maximum rated operating voltage of the devices plugged onto the Power Rail must not be exceeded.
Power dissipation≤ 1 W
Output
SupplyOutput current: max. 4 A
Fault signalrelay output: NO contact
Contact loading40 V DC ; 2 A
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Fuse rating5 A
recommended maximum utilization of the fuse: 80 %
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Damaging gasacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20
Connectionterminal connection ≤ 2.5 mm2
Massapprox. 100 g
Dimensions20 x 115 x 115 mm (0.8 x 4.5 x 4.5 inch)
Height107 mm
Width20 mm
Length115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
CertificateTÜV 00 ATEX 1618 X
MarkingEx-Hexagon II 3G Ex nA nC IIC T4
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-15:2010
International approvals
FM approval
Control drawing116-0160
Approved forClass I, Division 2, Groups A, B, C, D; Class I, Zone 2, IIC
UL approvalClass I, Division 2, Groups A, B, C, D; Class I, Zone 2, IIC
CSA approval
Control drawing116-0160
Approved forClass I, Division 2, Groups A, B, C, D; Class I, Zone 2, IIC
IECEx approvalIECEx UL 16.0051X
Approved forEx nA nC IIC T4 Gc
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210119
ECLASS 12.027210119
ECLASS 11.027210119
ECLASS 10.0.127210119
ECLASS 9.027210119
ECLASS 8.027210119
ECLASS 5.127210119
ETIM 9.0EC002653
ETIM 8.0EC002653
ETIM 7.0EC002653
ETIM 6.0EC002653
ETIM 5.0EC002542
UNSPSC 12.139121004

Details: KFD2-EB2.RPI

Datasheet: KFD2-EB2.RPI

DatasheetFile TypeFile Size
Datasheet KFD2-EB2.RPIPDF214 KB
Datenblatt KFD2-EB2.RPIPDF215 KB

Documents: KFD2-EB2.RPI

ManualsFile TypeFile Size
ManualPDF8037 KB
HandbuchPDF8686 KB
Instruction leaflets
Instruction leaflet / BeipackzettelPDF79 KB

CAD+CAE: KFD2-EB2.RPI

CADFile TypeFile Size
CAD 3-D / CAD 3-DSTP2510 KB

Approvals+Certificates: KFD2-EB2.RPI

CertificatesFile TypeFile Size
Canada CSAPDF43 KB