Supply |
Connection | via Termination Board |
Rated voltage | 20.4 ... 30 V |
Rated current | 50 mA at 24 V, 20 mA output (per channel) |
Power dissipation | 0.9 W at 24 V (per channel) |
Input |
Input current | 0 ... 24 mA , overload-protected |
Input resistance | 50 Ω , PTC protected |
Voltage | 15 V at 20 mA |
Output |
Connection | terminals 1+, 4, 7-; 2+, 5; 6- |
Current range | 0 ... 20 mA |
Load | 0 ... 750 Ω |
Response time | 40 ms , 10 ... 90 % step change |
Transfer characteristics |
Calibrated accuracy | < 20 µA, 10 µA typ. |
Influence of temperature | < ± 0.01%/K < ± 0.005%/K typisch |
Influence of load | < ± 0.1 % of full-scale value from 0 ... 750 Ω |
Directive conformity |
Electromagnetic compatibility | |
| Directive 89/336/EEC | EN 61326 |
Conformity |
Degree of protection | IEC 60529 |
Ambient conditions |
Ambient temperature | 0 ... 60 °C (32 ... 140 °F) |
Storage temperature | -20 ... 70 °C (-4 ... 158 °F) |
Relative humidity | 5 ... 90 %, non-condensing up to 35 °C (95 °F) |
Mechanical specifications |
Degree of protection | IP30 |
Material | Polycarbonate |
Mass | approx. 140 g |
Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
| Height | 106 mm |
| Width | 18 mm |
| Length | 128 mm |
Data for application in connection with hazardous areas |
EU-type examination certificate | CESI 03 ATEX 061 , for additional certificates see www.pepperl-fuchs.com |
| Marking | II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2] |
| Input | EEx ia IIC |
| Voltage | 26.1 V |
| Current | 93 mA |
| Power | 607 mW |
Supply | |
| Maximum safe voltage | 42 V AC / 60 V DC |
Galvanic isolation | |
| Input/input | safe galvanic isolation acc. to EN 50020, 500 Vrms |
| Input/Output | safe galvanic isolation acc. to EN 50020, 1500 Vrms |
| Input/power supply | safe galvanic isolation acc. to EN 50020, 1500 Vrms |
Directive conformity | |
| Directive 94/9/EC | EN 50014, EN 50020, EN 50284 |
General information |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |