Serviceline Industrial Sensors
Serviceline Explosion Protection
Not available for purchase
Not available for purchase

SMART Transmitter Power Supplies HiD3010

HiD3010
  • 2-channel
  • Fully floating operation
  • Analog input or output on both channels
  • 2-wire SMART transmitters or current sources
  • SMART I/P and valve positioners
  • Connections to HART multiplexer and HART HHC
  • Line fault detection (LFD)

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Datasheet excerpt: Technical data of  HiD3010

Supply
Connectionvia Termination Board
Rated voltage20.4 ... 30 V
Rated current50 mA at 24 V, 20 mA output (per channel)
Power dissipation0.9 W at 24 V (per channel)
Input
Input current0 ... 24 mA , overload-protected
Input resistance50 Ω , PTC protected
Voltage15 V at 20 mA
Output
Connectionterminals 1+, 4, 7-; 2+, 5; 6-
Current range0 ... 20 mA
Load0 ... 750 Ω
Response time40 ms , 10 ... 90 % step change
Transfer characteristics
Calibrated accuracy< 20 µA, 10 µA typ.
Influence of temperature< ± 0.01%/K < ± 0.005%/K typisch
Influence of load< ± 0.1 % of full-scale value from 0 ... 750 Ω
Directive conformity
Electromagnetic compatibility
Directive 89/336/EECEN 61326
Conformity
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature0 ... 60 °C (32 ... 140 °F)
Storage temperature-20 ... 70 °C (-4 ... 158 °F)
Relative humidity5 ... 90 %, non-condensing up to 35 °C (95 °F)
Mechanical specifications
Degree of protectionIP30
MaterialPolycarbonate
Massapprox. 140 g
Dimensions18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Height106 mm
Width18 mm
Length128 mm
Data for application in connection with hazardous areas
EU-type examination certificateCESI 03 ATEX 061 , for additional certificates see www.pepperl-fuchs.com
MarkingEx-Hexagon II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2]
InputEEx ia IIC
Voltage26.1 V
Current93 mA
Power607 mW
Supply
Maximum safe voltage42 V AC / 60 V DC
Galvanic isolation
Input/inputsafe galvanic isolation acc. to EN 50020, 500 Vrms
Input/Outputsafe galvanic isolation acc. to EN 50020, 1500 Vrms
Input/power supplysafe galvanic isolation acc. to EN 50020, 1500 Vrms
Directive conformity
Directive 94/9/ECEN 50014, EN 50020, EN 50284
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210119
ECLASS 12.027210119
ECLASS 11.027210119
ECLASS 10.0.127210119
ECLASS 9.027210119
ECLASS 8.027210119
ECLASS 5.127210119
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiD3010

Datasheet: HiD3010

DatasheetFile TypeFile Size
DatasheetPDF74 KB