Serviceline Industrial Sensors
Serviceline Explosion Protection
Not available for purchase
Not available for purchase

Signal Converter with Trip Values EU137A

EU137A
  • 1-channel isolated barrier
  • 24 V AC/DC supply voltage
  • Input Pt100, 2-, 3- and 4-wire, potentiometer (up to 600 Ω), thermocouple, mA, mV
  • Output 0/4 mA ... 20 mA or 0/2 V ... 10 V, 2 trip amplifiers
  • Configurable via PC

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  EU137A

Supply
Connectiondz2+, dz4-, dz6 (PE)
Rated voltage20.4 ... 30 V DC
20.4 ... 26.4 V AC, 48 ... 62 Hz
Power consumption< 5 VA (AC)
< 2.4 W (DC)
Input
Connectiondz22, dz24, dz26, dz28, dz30, dz32
Input voltagemax. 10 V
RTDPt100, Ni100
Types of measuring2-, 3-, 4-wire technology
Measurement range-200 ... 850 °C (-328 ... 1562 °F) (Pt100) (Default setting: 0 ... 100 °C)
-60 ... 250 °C (-76 ... 482 °F) (Ni100)
ThermocouplesTyp B, E, J, K, L, N, R, S, T, U, Pallaplat, min. span 3 mV
Input currentmax. 20 mA
Slide-wire sensor
Types of measuring2-, 3-, 4-wire technology
Transmission rangewithin rated sensor limits
Hysteresis0 ... 100 % , within rated sensor limits
Compensation (reference junction CJC)intern/extern
mV input-10 ... 80 mV min. span 3 mV
Output
ConnectionOutput I: d8, d10, d12
Output II: z8, z10, z12
Output III: dz14+, dz16-
Response time0.42 ... 0.7 s
Output I, IIrelay
Contact loading50 V AC/DC; 30 W resistive load
Output IIIAnalog current output (Voltage input can be activated via soldered jumper)
Current range0/4 ... 20 mA
Voltage range0/2 ... 10 V
Load750 Ω (mA), > 22 kΩ (V)
Fault signal0 mA/V, 0%, 108%, freezing measurement value, variable default value (effectless with I and U input)
Transfer characteristics
Influence of temperature< 0.1 %/10 K
Influence of supply voltage0.05 %
Linearity< 0.1 %
Galvanic isolation
Input/Output1.5 kV (test voltage)
Input/power supply1.5 kV (test voltage)
Output/power supply1.5 kV (test voltage)
Indicators/settings
Display elementsLED POWER (power supply), one green LED
LED STATUS (output status), one yellow LED per channel
LED BURN OUT (fault signal), one red LED
Control elementstrimmers at the front side for:
- ZERO (factory adjustment zero)
- SPAN (factory adjustment span)
test socket TEST -, +
Configurationvia RS-485 interface at the front side
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECThe device has been used for the same applications for several years. It therefore features an appropriate electromagnetic field immunity. The device must not be used in new plants.
Conformity
Galvanic isolationEN 61010
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-10 ... 60 °C (14 ... 140 °F)
Storage temperature-25 ... 80 °C (-13 ... 176 °F)
Relative humiditymax. 90 % non-condensing up to 35 °C (95 °F)
Mechanical specifications
Degree of protectionIP20 (installed in 19" rack)
Connectionplug connector acc. to DIN 41612, 32-pin, type F, rows d and z provided
Massapprox. 200 g
Dimensions22 x 143 x 193 mm (0.9 x 5.6 x 7.6 inch)
Height143 mm
Width22 mm
Length193 mm
Construction typeEurocard 100 x 160 mm (3.9 x 6.3 inch) acc. to DIN 41494, front panel 4TE, 3HE, mountable in 19 inch rack
Coding01/02/07 (see "Notes")
Data for application in connection with hazardous areas
EU-type examination certificateTÜV 02 ATEX 1945 X , for additional certificates see www.pepperl-fuchs.com
MarkingEx-Hexagon II (1/2)GD [EEx ia/ib] IIC/IIB (-10 °C ≤ Tamb ≤ 60 °C)
InputEEx ia/ib IIC/IIB
Voltage6 V
Current12 mA
Power47 mW (trapezoid characteristic curve)
Internal capacitance150 nF
Supply
Maximum safe voltage250 V eff
(Attention! Um is no rated voltage.)
Galvanic isolation
Input/Outputsafe galvanical isolation acc. to EN50020:2002, voltage peak value 375 V
Input/power supplysafe galvanical isolation acc. to EN50020:2002, voltage peak value 375 V
Directive conformity
Directive 94/9/ECEN 50014:1997+A1 +A2, EN 50020:2002
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210129
ECLASS 12.027210129
ECLASS 11.027210129
ECLASS 10.0.127210129
ECLASS 9.027210129
ECLASS 8.027210190
ECLASS 5.127210107
ETIM 9.0EC002919
ETIM 8.0EC002919
ETIM 7.0EC002919
ETIM 6.0EC002919
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: EU137A

Product Documentation: EU137A

Language Selection:
Brief InstructionsLanguageFile TypeFile Size
Instruction Manual EU137A / Betriebsanleitung EU137AALLPDF1108 KB

Software: EU137A

Language Selection:
Software ToolsRelease InfoFile TypeFile Size
Parameterization Software / Parametriersoftware07/2009ZIP41730 KB