Serviceline Industrial Sensors
Serviceline Explosion Protection
Not available for purchase
Not available for purchase

Transmitter Power Supply with Trip Value (sls compatible) 3/422(sls/422)

3/422(sls/422)
  • 1-channel isolated barrier
  • 2 trip relays
  • 2-wire SMART transmitters or current sources
  • Output 0/4 mA ... 20 mA and 2 trip amplifiers
  • Short-circuit proof outputs
  • LCD display
  • Galvanic isolation between input, output, power supply and contact output

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  3/422(sls/422)

General specifications
Signal typeAnalog input
Supply
Connectiondz2+, dz4-, dz6 (PE)
Rated voltage15.5 V at 20 mA (UO 28 V)
14.5 V at 20 mA (UO 24 V)
Input
ConnectionInput I: dz30+, dz32- (+), dz28(-)
Input resistancedynamic 250 Ω , static 150 Ω
Output
ConnectionOutput I: d10, z12, z10; z14, d12
Output II: z20, d18, d20; z16, z18
Output Analog: d14+, d16-
Load750 Ω
Relay
Switching voltage50 V
Switching current1.2 A AC/DC
Switching power60 VA / 30 W
Mechanical life10 Mio. cycles
Electrical life0.5 Mio. cycles
Response time20 ms
Current output4 ... 20 mA
Response time22 ms (10 ... 90%)
Transfer characteristics
Influence of temperature< 0.2 %/10 K
Linearity< 0.2 %
Galvanic isolation
Input/Output2.5 kV (test voltage)
Input/power supply2.5 kV (test voltage)
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECThe device has been used for the same applications for several years. It therefore features an appropriate electromagnetic field immunity. The device must not be used in new plants.
Ambient conditions
Ambient temperature-10 ... 60 °C (14 ... 140 °F)
Storage temperature-25 ... 80 °C (-13 ... 176 °F)
Relative humidity< 75 % (annual mean)
< 95 % (30 d/year), no moisture condensation
Mechanical specifications
Degree of protectionIP20 (installed in 19" rack)
Connectionplug connector acc. to DIN 41612, 32-pin, type F, rows d and z provided
Massapprox. 250 g
Dimensions22 x 143 x 193 mm (0.9 x 5.6 x 7.6 inch)
Height143 mm
Width22 mm
Length193 mm
Construction typeEurocard 100 x 160 mm (3.9 x 6.3 inch) acc. to DIN 41494, front panel 4TE, mountable in 19 inch rack
Coding02/03/11
Data for application in connection with hazardous areas
EU-type examination certificateTÜV 98 ATEX 1373 X
MarkingEx-Hexagon II (1)GD [Ex ia] IIC
Voltage27.1 V 5 V
Current93 mA 50 mA
Power630 mW 62 mW
Supply
Maximum safe voltage250 V eff
Output
Contact loading250 V AC/1.25 A/60 VA oder 150 V AC/1.25 A/30 W resistive load
Directive conformity
Directive 94/9/ECEN 50014:1997+A1 +A2, EN 50020:2002
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210119
ECLASS 12.027210119
ECLASS 11.027210119
ECLASS 10.0.127210119
ECLASS 9.027210119
ECLASS 8.027210119
ECLASS 5.127210119
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: 3/422(sls/422)

Product Documentation: 3/422(sls/422)

Language Selection:
Safety and Security DocumentationLanguageFile TypeFile Size
Operating instructions 3/422 / Betriebsanleitung 3/422ALLPDF326 KB