Serviceline Industrial Sensors
Serviceline Explosion Protection
Not available for purchase
Not available for purchase

Frequency converter KSD2-FI-Ex

KSD2-FI-Ex
  • 1-channel
  • Input EEx ia IIC
  • Device installation in Zone 2
  • Lead breakage (LB) and short-circuit (SC) monitoring
  • Frequency measurement, pulse-rate measurement, flow-rate measurement
  • Rotation direction detection, flow direction detection
  • Rotational speed monitoring
  • Standstill monitoring
  • Batch controller
  • EMC acc. to NAMUR NE 21

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Datasheet excerpt: Technical data of  KSD2-FI-Ex

Supply
ConnectionPower Rail
Rated voltage20 ... 30 V DC
Ripple< 10 %
Power consumption1 W
Input
Connectionterminals 2+, 3-; 5+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Pulse/Pause ratio40 ... 60 % of period at 1000 Hz , 10 ... 90 % of period at 250 Hz
Line fault detectionbreakage I < 0.1 mA , short-circuit I > 6 mA
Output
InterfaceCAN protocol via Power Rail bus
ConnectionPower Rail
Transfer characteristics
Deviation< 0.1 %
Switching frequency0.3 ... 1500 Hz
If the maximum input frequency of 1500 Hz is exceeded, the signal value is undefined! No further messages.
Rotation direction detection< 350 Hz
Phase difference between pulse input signal and auxiliary pulse signal min. ± 700 µs
(= ± 90 ° at 350 Hz)
Galvanic isolation
Input/power supply, internal busbasic insulation acc. to EN 50178:1997, rated insulation voltage 253 V AC
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Explosion protection
Directive 94/9/ECEN 60079-0:2006, EN 60079-11:2007, EN 60079-15:2005
Standard conformity
Insulation coordinationEN 50178:1997
Galvanic isolationEN 60079-11:2007
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529
Climatic conditionsIEC 60721
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Damaging gasacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20
Connectionterminal connection ≤ 2.5 mm2
Massapprox. 100 g
Dimensions20 x 100 x 115 mm (0.8 x 3.9 x 4.5 inch)
MountingDIN rail mounting
Data for application in connection with hazardous areas
EC-Type Examination CertificateZELM 99 ATEX 0012 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1)GD [EEx ia] IIC
Voltage9.6 V
Current16 mA
Power38 mW (linear characteristic)
Statement of conformityTÜV 00 ATEX 1617 X , observe statement of conformity
Group, category, type of protection, temperature classEx-Hexagon II 3G EEx nA II T4
Galvanic isolation
Input/power supply, internal bussafe galvanic isolation acc. to EN 60079-11:2007

Classifications

SystemClasscode
ECLASS 13.027210128
ECLASS 12.027210128
ECLASS 11.027210128
ECLASS 10.0.127210128
ECLASS 9.027210128
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC002918
ETIM 8.0EC002918
ETIM 7.0EC002918
ETIM 6.0EC002918
ETIM 5.0EC002475
UNSPSC 12.139121007

Details: KSD2-FI-Ex

Datasheet: KSD2-FI-Ex

DatasheetFile TypeFile Size
Datasheet KSD2-FI-ExPDF163 KB
Datenblatt KSD2-FI-ExPDF164 KB

Documents: KSD2-FI-Ex

ManualsFile TypeFile Size
ManualPDF8037 KB
HandbuchPDF8686 KB
Instruction manuals
Operating instructions RPI-SystemPDF1459 KB
Betriebsanleitung RPI-SystemPDF1461 KB

Approvals+Certificates: KSD2-FI-Ex

CertificatesFile TypeFile Size
TUV Nord IECEx Certificate of ConformityLINK---