General specifications |
AS-Interface specification | V3.0 |
PLC-Functionality | activateable |
Duplicate address detection | from AS-Interface slaves |
Earth fault detection | integrated |
EMC monitoring | integrated |
Diagnostics function | Extended function via display |
Switch-on delay | < 10 s |
Response delay | < 40 ms |
UL File Number | E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 3 |
Performance level (PL) | PL e |
MTTFd | 200 a |
B10d | 2 E+7 |
Indicators/operating means |
Display | Illuminated graphical LC display for addressing and error messages |
LED PROFIBUS | PROFIBUS master detected; LED green |
LED AS-i ACTIVE | AS-Interface operation normal; LED green |
LED CONFIG ERR | configuration error; LED red |
LED PRG ENABLE | autom. programming; LED green |
LED POWER | voltage ON; LED green |
LED PRJ MODE | projecting mode active; LED yellow |
LED U AS-i | AS-Interface voltage; LED green |
Switch SET | Selection and setting of a slave address |
OK button | Mode selection traditional-graphical/confirmation |
Button MODE | Mode selection PRJ-operation/save configuration/cursor |
ESC button | Mode selection traditional-graphical/cancel |
Electrical specifications |
Insulation voltage | ≥ 500 V |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface; Output K3 and K4 24 V DC |
Rated operating current | ≤ 300 mA from AS-Interface |
Interface 1 |
Interface type | RS-485 |
Protocol | PROFIBUS DP V1 |
Transfer rate | 9.6 kBit/s / 12 MBit/s , Automatic baud rate detection |
Interface 2 |
Interface type | RS 232, serial Diagnostic Interface |
Transfer rate | 19,2 kBit/s |
Interface 3 |
Interface type | Chip card slot |
Input |
Number/Type | 2 EDM inputs: Inputs for external device monitoring circuits 1 and 2 (protection control) 2 Start inputs: Output circuits 1 and 2: Static switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 μs) |
Output |
Safety output | 2 x 2 output switch elements: Output circuits 1 and 2 max. contact loading: 3 A DC-13 at 30 V DC, 3 A AC-15 at 30 V AC |
Connection |
PROFIBUS | Sub-D interface |
AS-Interface | spring terminals, removable |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
Standard conformity |
Electromagnetic compatibility | EN 61000-6-2:2005, EN 61000-6-4:2007 |
Degree of protection | EN 60529:2000 |
Fieldbus standard | PROFIBUS according to DIN 19245 Part 3 |
AS-Interface | EN 62026-2:2013 |
Shock resistance | EN 61131-2:2004 |
Standards | EN 61000-6-2:2005, EN 61000-6-4:2007 EN 954-1:1996 (up to Kategorie 4), IEC 61508:2001 and EN 62061:2005 (up to SIL3) EN 13849:2008 (PL e) |
Approvals and certificates |
UL approval | An isolated source with a secondary open circuit voltage of ≤ 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device. |
Ambient conditions |
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | 800 g |
Dimensions | |
| Height | 120 mm |
| Width | 100 mm |
| Length | 89 mm |
Construction type | Low profile housing , Stainless steel |