Línea de servicio de Sensores Industriales
Atención al cliente para protección contra explosiones

AS-Interface sensor/actuator module VBA-4E2A-G2-XE/E2

VBA-4E2A-G2-XE/E2
  • AS-Interface certificate
  • Degree of protection IP67
  • A/B node with extended addressing possibility for up to 62 nodes
  • Addressing jack
  • Flat cable connection with cable piercing technique, variable flat cable guide
  • Communication monitoring
  • Inputs for 3-wire sensors (PNP) and mechanical contacts
  • Power supply of the inputs and outputs from the external auxiliary voltage
  • Ground connection (FE) possible
  • Function display for bus, ext. auxiliary voltage, inputs and outputs
  • Detection of output overload

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Descargue la hoja de datos completa en PDF:


Extracto de la hoja de datos: Información técnica del  VBA-4E2A-G2-XE/E2

Descripción del producto
G2 flat module
4 inputs and 2 electronic outputs
General specifications
Node typeA/B node
AS-Interface specificationV2.1
Required gateway specification≥ V2.1
UL File NumberE223772
Indicators/operating means
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of outputs
LED PWRAS-Interface voltage; LED green
LED AUXext. auxiliary voltage UAUX ; LED green
LED INswitching state (input); 4 LED yellow
LED OUTSwitching state (output); 2 LED yellow
Electrical specifications
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 30 mA
Protection classIII
Current loading capacity2 A (IAUX)
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type4 inputs for mechanical contacts or 3-wire sensors (PNP), DC
Supplyfrom external auxiliary voltage UAUX
Input current3 mA (typically)
Switching pointaccording to DIN EN 61131-2 (type 1)
0 (unattenuated)≤ 0.5 mA
1 (attenuated)≥ 2 mA
Signal delay< 2 ms (input/AS-Interface)
Signal frequency≤ 250 Hz
Output
Number/Type2 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Voltage≥ (UAUX - 0.5 V)
Current1 A per output , 2 A per module
Usage categoryDC-13
Galvanic isolation
Input/Outputnone
Input/AS-InterfaceBasic insulation, rated insulation voltage 120 V DC
Output/AS-InterfaceBasic insulation, rated insulation voltage 120 V DC
Directive conformity
Electromagnetic compatibilityobserve notices on the certificate of conformity.
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Galvanic isolationEN 60947-1:2007
Degree of protectionEN 60529:2000
Mech. capacityEN 60068-2-6:2008, EN 60068-2-27:1995
InputEN 61131-2:2007
Usage categoryEN 60947-5-1:2005
Emitted interferenceEN 61000-6-4:2001
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61326-1:2006
Programming instructions
ProfileS-7.A.E
IO code7
ID codeA
ID1 code7
ID2 codeE
Data bits (function via AS-Interface)InputOutput
D0 IN1 O1
D1 IN2 O2
D2 IN3 -
D3 IN4 -
Parameter bits (programmable via AS-i)function
P0not used
P1not used
P2not used
P3not used
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Pollution degree3
Mechanical specifications
Degree of protectionIP67
ConnectionCable piercing method
flat cable yellow/flat cable black
inputs/outputs: M12 round connector
Material
HousingPBT
Massapprox. 100 g
Tightening torque, cable gland0.4 Nm
MountingMounting plate

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Details: VBA-4E2A-G2-XE/E2

Product Documentation: VBA-4E2A-G2-XE/E2

Seleccionar idioma:
Brief InstructionsIdiomaTipo de archivoTamaño
Instruction leaflet / BeipackzettelALLPDF188 KB

Design / Simulation: VBA-4E2A-G2-XE/E2

Seleccionar idioma:
CADIdiomaTipo de archivoTamaño
CAD 3-D / CAD 3-DALLSTP149 KB
CAD Portal / CAD PortalALLLINK---

Approvals: VBA-4E2A-G2-XE/E2

Seleccionar idioma:
CertificatesNúmero de CertificadoIdiomaTipo de archivoTamaño
US CA ULE223772ALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-1018CALLPDF118 KB

Productos asociados: VBA-4E2A-G2-XE/E2

Matching System Components
AS-Interface module mounting base for connection to flat cable (AS-Interface and external auxiliary power)fa
Accessories

AS-Interface Handheld with accessoryfa

Adapter cable module/hand-held programming devicefa
Descarga gratuita: Documento técnico sobre protocolos de comunicación basados en TCP (PDF)

Este documento técnico gratuito en formato PDF compara los diferentes protocolos de comunicación basados en TCP (AMQP, OPC UA, MQTT, REST API) que se han hecho un hueco en el sector y se consideran los habilitadores del IIoT y de la Industria 4.0. Descárguelo ahora de forma gratuita.

Módulo de armario de conmutación AS-Interface KE5 – Manejo sencillo y manipulación mejorada

El diseño único de la carcasas del nuevo módulo de armario de conmutación KE5 permite una visibilidad superior y simplifica el montaje, cableado y mantenimiento dentro de los armarios de conmutación y cajas de conexiones.

Gama de productos AS-Interface

Conozca la gama completa de los productos AS-Interface.