Línea de servicio de Sensores Industriales
Atención al cliente para protección contra explosiones

AS-Interface analog module VBA-2E-G11-I/U/PT100-V1

VBA-2E-G11-I/U/PT100-V1
  • Function display for bus, internal and external sensor power supply, inputs
  • Supply for inputs from AS-Interface or auxiliary voltage
  • Degree of protection IP68 / IP69K
  • Accuracy ± 0.1 %
  • Channel-specific input monitoring
  • Inputs for current, voltage or Pt100 temperature sensor

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Descargue la hoja de datos completa en PDF:


Extracto de la hoja de datos: Información técnica del  VBA-2E-G11-I/U/PT100-V1

Descripción del producto
G11 analog module
2 analog inputs
General specifications
Node typeStandard node
AS-Interface specificationV3.0
Required gateway specification≥ V2.1
UL File NumberE223772
Functional safety related parameters
MTTFd190 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Indicators/operating means
LED AS-i/FAULTStatus display; multi-colour LED
Green: normal operation
Red: communication fault
Flashing yellow/red: address 0
Flashing green/red: peripheral fault
LED ANALOGstatus of input signal; LED yellow
off: not active
on: signal within measurement range
flashing: signal outside of measurement range
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INT/EXTstatus display input supply; LED green
green: input supply from AS-Interface
off: input supply from auxiliary voltage
Electrical specifications
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 60 mA (without sensors) / max. 200 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type2 analog inputs
Current: 0 ... 20 mA/4 ... 20 mA
voltage: 0 ... 10 V
Pt100: -200 ... 850 °C
Supplyfrom AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT)
Current loading capacity≤ 140 mA from AS-Interface; overload and short-circuit resistant
≤ 600 mA from external auxiliary voltage UAUX , overload and short-circuit protected
Input resistancecurrent input: max. 70 Ω
voltage input: 100 kΩ
Measuring currentfor Pt100: approx. 1 mA
AccuracyVoltage/current: 0.1% of accumulated value
Pt100: 0.1% of indicated temperature [°C] + 0.3 °C
Resolution16 Bit / 1 µA (current input) or
16 bit / 1 mV (voltage input) or
16 Bit / 0.1°C (temperature input)
Temperature influenceVoltage/current: 20 ppm/K
Pt100: (10 ppm of indicated temperature [°C] + 0.003 °C)/K
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
InputEN 61131-2:2007
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Programming instructions
ProfileS-7.3.D
IO code7
ID code3
ID1 codeF
ID2 codeD
Data bits (function via AS-Interface)The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i)function
P050/60 Hz filter
P0=1, enabled
P0=0, disabled
P1projecting of the 2nd channel
P1=1, channel 2 is projected
P1=0, channel 2 is not projected
P2Indication of the peripheral fault by exceeding measuring range
P2=1, peripheral fault is reported
P2=0, peripheral fault is not reported
P3P3=1, normal operating mode
P3=0, both channels in current mode and without recognition of wire breakage
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Pollution degree3
Mechanical specifications
Degree of protectionIP68 / IP69K
ConnectionAS-Interface/UAUX: M12 round connector
Inputs: M12 round connector
Material
HousingPBT PC
Mounting screwStainless steel 1.4305 / AISI 303
Mass200 g
Tightening torque, housing screws1.8 Nm
Tightening torque, cable gland0.4 Nm
MountingMounting plate

Classifications

SystemClasscode
ECLASS 11.027242601
ECLASS 10.0.127242601
ECLASS 9.027242601
ECLASS 8.027242601
ECLASS 5.127242601
ETIM 8.0EC001596
ETIM 7.0EC001596
ETIM 6.0EC001596
ETIM 5.0EC001596
UNSPSC 12.139121535

Documents: VBA-2E-G11-I/U/PT100-V1

ManualsIdiomaTipo de archivoTamaño
Manual VBA-2E-G11-I/U/PT100-*ENGPDF2561 KB
Handbuch VBA-2E-G11-I/U/PT100-*GERPDF2563 KB
Instruction leaflets
Instruction leaflet / Beipackzettel ALLPDF683 KB

CAD+CAE: VBA-2E-G11-I/U/PT100-V1

CADTipo de archivoTamaño
3-D model / 3-D-ModellSTP4756 KB
CAD Portal / CAD PortalLINK---

Approvals+Certificates: VBA-2E-G11-I/U/PT100-V1

Statements of complianceNúmero de CertificadoTipo de archivoTamaño
EU-Declaration of conformity / EU-KonformitätserklärungDOC-2931APDF165 KB
Certificates
EU Ecolab Material ResistanceECOLABPDF1797 KB
US CA ULE223772LINK---
Worldwide AS-International Association AS-Interface94201PDF379 KB

Productos asociados: VBA-2E-G11-I/U/PT100-V1

Accessories

Blind plug for M12 socketsfa
Connecting cable, M12 to M12, PUR cable, 4-pin, bridged, shieldedfa
Connecting cable, M12 to M12, PUR cable, 4-pin, bridged, shieldedfa
Descarga gratuita: Documento técnico sobre protocolos de comunicación basados en TCP (PDF)

Este documento técnico gratuito en formato PDF compara los diferentes protocolos de comunicación basados en TCP (AMQP, OPC UA, MQTT, REST API) que se han hecho un hueco en el sector y se consideran los habilitadores del IIoT y de la Industria 4.0. Descárguelo ahora de forma gratuita.

Módulo de armario de conmutación AS-Interface KE5 – Manejo sencillo y manipulación mejorada

El diseño único de la carcasas del nuevo módulo de armario de conmutación KE5 permite una visibilidad superior y simplifica el montaje, cableado y mantenimiento dentro de los armarios de conmutación y cajas de conexiones.

Gama de productos AS-Interface

Conozca la gama completa de los productos AS-Interface.