Línea de servicio de Sensores Industriales
Atención al cliente para protección contra explosiones

AS-Interface safety module VBA-4E1A-KE3-ZEJ/SR

VBA-4E1A-KE3-ZEJ/SR
  • Safety output module with diagnostic node
  • Safe relay output with galvanically isolated contact sets
  • Assigns a complete address for the safe output and one A/B address for the inputs
  • 4 inputs can be used either for diagnostics and EDM or as standard inputs
  • Applications up to category 4/PL e/SIL 3
  • Several safe output modules can be grouped into one enabling circuit

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Descargue la hoja de datos completa en PDF:


Extracto de la hoja de datos: Información técnica del  VBA-4E1A-KE3-ZEJ/SR

Descripción del producto
KE3 control cabinet module, 4 inputs, 1 control-safe relay output
General specifications
Node typeA/B node
AS-Interface specificationV2.1
Required gateway specification≥ V2.1
UL File NumberE223772
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL e
Indicators/operating means
LED FAULTerror display; LED red
red: communication error
LED PWRAS-Interface voltage; LED green
LED INswitching state (input); 4 LED yellow
LED OUTFor flashing patterns see diagnostics table
LED ALARMPLC reports alarm; red LED
Electrical specifications
Auxiliary voltage (input)12 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 30 mA (without sensors) / max. 200 mA
Protection classIII
Surge protectionUEXT, Ue: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
Supplyfrom AS-Interface
Voltage21 ... 31 V DC
Current loading capacity≤ 90 mA, overload- and short-circuit proof (INT)
Input current≤ 8 mA (limited internally)
Sensor supply≤ 90 mA
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)≤ 2 mA
1 (attenuated)≥ 4 mA
Signal delay< 2 ms (input/AS-Interface)
Signal frequency≤ 250 Hz
Output
Number/Type1 safety relay output
Supplyfrom AS-Interface
Nominal load
Per contact3 A / 24 V DC; 3 A / 230 V AC
Usage categoryDC-13 and AC-15
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Standard conformity
Degree of protectionEN 60529:2000
InputEN 61131-2
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005 EN 62026-2:2013
Programming instructions
ProfileS-7.A.E
IO code7
ID codeA
ID1 code5 (Can be changed to 7 or F)
ID2 codeE
Data bits (function via AS-Interface)InputOutput
D0 E0 LED ALARM
Diagnosis (see table Device colors)
D1 E1 OUT1 (see P1)
D2 E2 -
D3 E3 = 1.Y1 -
Parameter bits (programmable via AS-i)function
P0not used
P1Output linkage:
P1 = 1: safe output switches on release.
P1 = 0: safe output switches on release and OUT1=1
P2ID1=5
not used
ID1=7 or F
P2 = 0 IN3 is input
P2 = 1 IN3 notifies of release
P3not used
Ambient conditions
Ambient temperature0 ... 55 °C (32 ... 131 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Connectionremovable terminals
rated connection capacity:
rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2
for multiple-wire connection with two wires of equal cross-section:
flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material
HousingPA 66-FR
Dimensions
Height99 mm
Width22.5 mm
Length107 mm
MountingDIN mounting rail

Classifications

SystemClasscode
ECLASS 13.027272603
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Details: VBA-4E1A-KE3-ZEJ/SR

Product Documentation: VBA-4E1A-KE3-ZEJ/SR

Seleccionar idioma:
Brief InstructionsIdiomaTipo de archivoTamaño
Mounting Instruction VBA-4E1A-KE3-ZEJ/SR / Montageanleitung VBA-4E1A-KE3-ZEJ/SRALLPDF969 KB
Safety and Security Documentation
Instruction Manual VBA-4E1A-KE3-ZEJ/SR / Betriebsanleitung VBA-4E1A-KE3-ZEJ/SRALLPDF2862 KB
Manuals
Manual VBA-4E1A-KE3-ZEJ/SRENGPDF2769 KB

Design / Simulation: VBA-4E1A-KE3-ZEJ/SR

Seleccionar idioma:
CADIdiomaTipo de archivoTamaño
CAD 3-D / CAD 3-DALLSTP4525 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ1055 KB

Approvals: VBA-4E1A-KE3-ZEJ/SR

Seleccionar idioma:
CertificatesNúmero de CertificadoIdiomaTipo de archivoTamaño
EU TUV Nord Functional Safety44 205 16000804ALLPDF66 KB
US CA ULE223772ALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2489EALLPDF222 KB

Software: VBA-4E1A-KE3-ZEJ/SR

Seleccionar idioma:
Software ToolsLiberar InfoTipo de archivoTamaño
SISTEMA SLB Library AS-Interface Safety / SISTEMA SLB Library AS-Interface SafetyZIP622 KB

Productos asociados: VBA-4E1A-KE3-ZEJ/SR

Accessories

AS-Interface Handheld with accessoryfa

Adapter cable module/hand-held programming devicefa
25-point wiring link for control cabinet modules with screw terminalsfa
Gama de productos AS-Interface

Conozca la gama completa de los productos AS-Interface.